I want to search for...
Permit #2021051757
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7035-00720-0040 |
| Block: 00720 |
| Subdivision: 2172 - SECTION 35-BELLE TERRE |
| Job Phone: 904-282-5050 |
| Location Address: 6 BUTTONWELL LN |
| Type: ME - MECHANICAL |
| Issue Date: 05/28/2021 |
| NOC: Unknown |
| Applicant name: MICHAEL R NIQUETTE |
| Owner: BURNS CAROL A |
|
Address 6 BUTTONWELL LANE PALM COAST, FL 32137 |
| Lot: 0040 |
| Contracted Stated Job Value: ¤4,500.00 |
| Job Description: REPLACE 4 ton split heat pump system, 14 SEER |
| Type: CN |
Contractor
TOTAL AIR CARE INC
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
PO BOX 2004 ORANGE PARK, FL 32065 |
CAC1815232 (Exp: 08/31/2022) | 904-282-5050 | 904-291-5956 |
Inspection History
| Type | Request Date | Result | Inspector |
| HVAC FINAL | 07/06/2021 | FINAL APPROVED | CPISCITELLI |
| HVAC FINAL | 06/02/2021 | Disapproved -FEE REQUIRED | CPISCITELLI |
| Note: 1. ODU calls for 40 AMP max. There is a 50 AMP in panel. 2. AHU calls for 60 AMP. There is a 40 AMP in panel 3. Garage wall behind unit needs to be sealed with 1/2 gypsum board. Cannot use particle board. (R302.6)FBC Residential 2020 7Th edition |
Review History
| Department | Status | Date In | Date Out |
| MECH | COMPLETE | 05/27/2021 | 05/28/2021 |
| Note: Released By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 06/23/2021 |
| SURCHARGE FS 533.721 | ¤2.00 | 05/28/2021 |
| SURCHARGE - FS 468.631 | ¤2.00 | 05/28/2021 |
| ADMIN FEE | ¤20.00 | 05/28/2021 |
| BUILDING DISCOUNT 100% | (¤60.00) | 05/28/2021 |
| INSPECTION 40 | ¤40.00 | 05/28/2021 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤44.00 |