Permit Details

Status: COED

COMMERCIAL SQUARE FOOTAGE: 7780 sqft
Total Square Footage: 7780 sqft
Subdivision: 2085 - Tidelands at the Village Phase II
Job Phone: (407)838-1486
Location Address: 2 RIVERVIEW BEND N
Type: BC - BUILDING COMMERCIAL
Issue Date: 02/07/2006
NOC: RECORDED
Applicant name: JAMES NICHOLSON BOYCE IV
Owner: CENTEX DESTINATION PROPERTIES
Contracted Stated Job Value: ¤1,500,000.00
Job Description: CLUBHOUSE
Type: CN

Contractor

CENTEX DESTINATION PROPERTIES
Status Location Address Mailing Address State License Number Phone
CANCEL

1064 GREENWOOD BLVD

LAKE MARY, FL 32746

STE. 200

LAKE MARY, FL 32746

CGC1508651 (Exp: 08/31/2010) (407)838-1486

Sub Contractors

TRUMAN E GAILEY JR
Status Location Address State License Number Phone Fax
ACTIVE

231 Jean St.

DAYTONA BEACH, FL 32114

EC0000265 (Exp: 08/31/2026) (386) 255-1418 (386)255-3429
ROBERT G DELLO RUSSO
Status Location Address State License Number Phone Fax
DECEASED

531 CODISCO WAY

SANFORD, FL 32771

CAC032448 (Exp: 08/31/2022) (407)831-2665 (407)333-3853
GARY WAYNE EVERS
Status Location Address State License Number Phone Fax
ACTIVE

PO BOX 740106

ORANGE CITY, FL 32763

CFC050566 (Exp: 08/31/2026) 386-775-0909 386-775-0918
WAYNE STEED
Status Location Address State License Number Phone
CANCEL

318 N. PINE AVENUE

IVERNESS, FL 34450

CCC058299 (Exp: 08/31/2010) (352)637-2422
RICHARD PHILLIP HOUGHTON
Status Location Address State License Number Phone Fax
CANCEL

12815 AUTOMOBILE BLVD.

CLEARWATER, FL 33762

CAC050371 (Exp: 09/30/2008) (727)573-5733 (727)573-2573
RONALD D PIERSON
Status Location Address State License Number Phone Fax
CANCEL

1510 DILLARD RD

ASTOR, FL 32102

16425 (Exp: 08/31/2008) (000)000-0000 (386)749-0293

Inspection History

Type Request Date Result Inspector
FINAL COMPLETE BUILDING INSPECTION 05/10/2007 FINAL APPROVED JLEVRAULT
ENGINEERING FINAL 04/18/2007 APPROVED DMAY
UTILITY COMMERCIAL FINAL 04/18/2007 APPROVED KKING
Note: THIS IS A REINSPECTION
LANDSCAPE FINAL 04/12/2007 APPROVED WBUTLER
FIRE FINAL 04/12/2007 APPROVED JPATTEE
UTILITY COMMERCIAL FINAL 04/12/2007 Disapproved - NO FEE KKING
Note: The grade work around the grease interseptor is to low. Raise the grade then raise the grease interseptor to match. The interseptor can not be in a depression.
PLUMBING FINAL 04/10/2007 APPROVED PGALLMANN
Note:
GAS FINAL 03/29/2007 APPROVED JMCGOWEN
Note:
GAS ROUGH 03/16/2007 APPROVED JMCGOWEN
ELECTRICAL FINAL 03/16/2007 APPROVED RMARVEL
H.V.A.C. FINAL 03/16/2007 APPROVED JMCGOWEN
ALL ROUGH 03/14/2007 APPROVED - AS NOTED JLEVRAULT
Note: NEED TO INSPECT COMPLETE GAS LINE AND TRACER.
GAS ROUGH 03/06/2007 APPROVED JLEVRAULT
Note:
GAS ROUGH 03/05/2007 Disapproved -FEE REQUIRED JLEVRAULT
Note: NO PRESSURE ON GAUGE. INSTALL CLAMPS ON GAS RISER.
ALL ROUGH 02/21/2007 APPROVED JLEVRAULT
Note: CEILING CLOSE-IN.
COMMERCIAL POWER INSPECTION 02/06/2007 APPROVED RMARVEL
H.V.A.C. ROUGH 01/24/2007 APPROVED - AS NOTED JMCGOWEN
Note: This inspection is for the walk-in refrigeration units-as per Mark NEED 4" SEPERATION OF DUCSTS WEST MECHANICAL ROOM WORKING CLEARANCE. NEED TO TERMINATE RETURN IN ACTIVITIES ROOM. WILL CHECK AT ABOVE CEILING INSPECTION
SECOND ROUGH PLUMBING INSPECTION 12/29/2006 APPROVED - AS NOTED JGIBSON
Note: grease interceptor
INSULATION INSPECTION 11/22/2006 APPROVED JLEVRAULT
ALL ROUGH 11/20/2006 APPROVED - AS NOTED JLEVRAULT
Note: CHECK ALL LEDGER BOLTS AT INSULATION INSPECTION.
THRESHOLD/AFFIDAVIT 10/31/2006 APPROVED PPROVIDER
Note: Law & Associates, Inc. Threshold inspectors report dated 10/31/06
FOOTER 10/06/2006 APPROVED PPROVIDER
ROOF SHEATHING/BRACES/TIES/ DOWN CELL 08/28/2006 APPROVED - AS NOTED CMINI
Note: FINISH ANCHOR BOLTS ON TRUSS LEDGER BOARDS 2' O.C. PER PLAN,FINISH SHEATHING PIECES. CHECK ON ALL ROUGH.
LINTEL 08/21/2006 APPROVED PPROVIDER
Note: Threshold inspectors report
POURED CELL 06/19/2006 APPROVED PPROVIDER
Note: Threshold inspectors report
MONOLITHIC SLAB INSPECTION/SLAB 06/09/2006 APPROVED PPROVIDER
Note: Threshold inspectors report.
FIRST ROUGH PLUMBING INSPECTION 06/06/2006 APPROVED JMCGOWEN
STEM FOOTING FOUNDATION 05/08/2006 APPROVED PPROVIDER
Note: Threshold inspectors report.
FOOTER 04/27/2006 APPROVED PPROVIDER
Note: Threshold inspectors report
TEMPORARY POLE 04/07/2006 APPROVED JMCGOWEN
Note: called on 4-12-06 Susan at FPL for a temp pole. Some confusion with the dates of inspection being approved.
FIRST ROUGH PLUMBING INSPECTION 03/14/2006 APPROVED TOUTLAND

Review History

Department Status Date In Date Out
BLD COMPLETE 01/23/2006 01/24/2006
Note: Released By: LWOODROME
BLD HOLD 12/07/2005 12/07/2005
Note: Held By: FREODICA CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application Number 2005110586-Tidelands Clubhouse 1. Provide copies of product approval data and installation instructions for exterior windows and doors, at the job site at the time inspection. 2. Provide copies of the roofing manufacturer specifications & installation instructions at the job site. 3. Provide energy calculations. 4. Provide details of barrel vaulted tile roof over exercise room to meet FBC 2004/B section 1507.3.2 5. Provide draftstop location in attic spaces per note 3, sheet A3.1. 6. Clarify roof sheeting thickness. (Drawing A3.1 references ½" while A6.1 & S-4 references 5/8". 7. Provide subcontractor name, phone No. &license No. on building permit application for LP gas installation or indicate on drawing if LP gas system installation will be installed in a separate building permit application. 8. Provide size of LP gas underground tank. 9. Provide separate permit application for kitchen hood and equipments for plan review. 7. On M1, clarify plan key notes 5 & 11 for outside air duct as there are (2) number 5. 8. On M2, clarify split system schedule as there are (2) AHU-2/CU-2. 9. On E-3, clarify if location of condensing units for freezer, cooler & ice maker is allowed by Galvin Design group Inc. as reference note indicate that those equipments shall be located on roof (FS-2).
FD1 COMPLETE 11/29/2005 11/29/2005
Note: Released By: JPATTEE Very good set of food service plans, however, there is a seperate submittal for permitting for hood installtion and for extinguishing system installation. ( these submittals are not approved at this time)

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION FEE ¤40.00 05/10/2007
REVISION ¤40.00 05/10/2007
ADMIN FEE ¤20.00 02/07/2006
BUILDING CODE ADMIN FUND ¤38.90 02/07/2006
ELECTRIC FEE ¤930.00 02/07/2006
FIRE COMM IMPACT FEE 4-1-05 ¤3,740.62 02/07/2006
FIRE PLANS REVIEW ¤77.80 02/07/2006
MECHANICAL FEE ¤930.00 02/07/2006
PERMIT FEE ¤8,250.00 02/07/2006
PLAN CHECK FEE ¤1,725.00 02/07/2006
PLUMBING FEE ¤930.00 02/07/2006
RADON FEE ¤38.90 02/07/2006
Fees Total Due: ¤0.00 Total Paid: ¤16,761.22