Permit #2006020171
Permit Details
Status: FINAL
| Subdivision: 2085 - Tidelands at the Village Phase II |
| Job Phone: (407)838-1486 |
| Location Address: 2 RIVERVIEW BEND N |
| Type: HD - HOOD SYSTEM |
| Issue Date: 05/12/2006 |
| NOC: RECORDED |
| Applicant name: JAMES NICHOLSON BOYCE IV |
| Owner: CENTEX HOMES |
|
Address 1064 GREENWOOD BLVD LAKE MARY, FL 32746 |
|
Address SUITE 200 LAKE MARY, FL 32746 |
| Contracted Stated Job Value: ¤10,500.00 |
| Job Description: CLUBHOUSE BUILDING/ KITCHEN HOOD & EQUIPMENT |
| Type: CN |
Contractor
CENTEX DESTINATION PROPERTIES
| Status | Location Address | Mailing Address | State License Number | Phone |
| CANCEL |
1064 GREENWOOD BLVD LAKE MARY, FL 32746 |
STE. 200 LAKE MARY, FL 32746 |
CGC1508651 (Exp: 08/31/2010) | (407)838-1486 |
Sub Contractors
ROBERT G DELLO RUSSO
| Status | Location Address | State License Number | Phone | Fax |
| DECEASED |
531 CODISCO WAY SANFORD, FL 32771 |
CAC032448 (Exp: 08/31/2022) | (407)831-2665 | (407)333-3853 |
THEODORE BARRON JOHNSON
| Status | Location Address | State License Number | Phone |
| ACTIVE |
PO BOX 479 Flagler Beach, FL 32136 |
CAC057081 (Exp: 08/31/2026) | 386-333-1672 |
Inspection History
| Type | Request Date | Result | Inspector |
| HOOD FINAL | 03/30/2007 | FINAL APPROVED | JLEWIS |
| COMMERCIAL HOOD & DUCT LIGHT TEST INSPECTION | 02/19/2007 | APPROVED | BMEYERS |
Review History
| Department | Status | Date In | Date Out |
| BLD | COMPLETE | 02/14/2007 | 02/14/2007 |
| Note: Released By: CCOTE Approved for Release. Review by Fred R. REVISION: Revised layout. | |||
| BLD | HOLD | 01/31/2007 | 02/01/2007 |
| Note: Submitted revised plan for kitchen exhaust hood system - 1/31/07. Held By: FREODICA 1. Comments on submitted revised plan for kitchen exhaust hood system only: a. Provide section/detail indicating the size and location of make-up fresh air intake louver. b. Grease duct horizontal cleanout shall comply with FBC/M section 506.3.9 c. Indicate grease duct slope per FBC/M section 506.3.7. d. Provide section/detail showing make-up air connection to kitchen hood with fire dampers to comply with FBC/M section 506.3.1.2. | |||
| BLD | COMPLETE | 04/27/2006 | 04/28/2006 |
| Note: Released By: LWOODROME Checked by FR | |||
| BLD | HOLD | 02/14/2006 | 03/08/2006 |
| Note: Held By: FREODICA 1. Recalculate the size of grease exhaust duct connection from exhaust hood thorough roof to KEF-1 (plan key note 10 on M1) to comply with FBC 2004 section 506.3.4. 2. Verify if there is an electrical source of 3 phase system in the clubhouse. The kitchen exhaust hood supply & exhaust fans are shown on equipment schedule (FS-6) to be 3 phase, 208 volts while these equipments are both shown on mechanical sheet M2 to be 1 phase, 208 volts. | |||
| FD1 | COMPLETE | 02/13/2006 | 02/13/2006 |
| Note: Released By: JPATTEE This is for a hood installation permit only not for fire extinguishing system. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| RENEW PERMIT FEES | ¤40.00 | 03/29/2007 |
| REVISION | ¤80.00 | 03/29/2007 |
| REVISION | ¤40.00 | 03/29/2007 |
| FIRE PLANS REVIEW | ¤25.00 | 05/12/2006 |
| PERMIT FEE | ¤73.50 | 05/12/2006 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤258.50 |