Permit #2006020171

Permit Details

Status: FINAL

Subdivision: 2085 - Tidelands at the Village Phase II
Job Phone: (407)838-1486
Location Address: 2 RIVERVIEW BEND N
Type: HD - HOOD SYSTEM
Issue Date: 05/12/2006
NOC: RECORDED
Applicant name: JAMES NICHOLSON BOYCE IV
Owner: CENTEX HOMES

Address

1064 GREENWOOD BLVD

LAKE MARY, FL 32746

Address

SUITE 200

LAKE MARY, FL 32746

Contracted Stated Job Value: ¤10,500.00
Job Description: CLUBHOUSE BUILDING/ KITCHEN HOOD & EQUIPMENT
Type: CN

Contractor

CENTEX DESTINATION PROPERTIES
Status Location Address Mailing Address State License Number Phone
CANCEL

1064 GREENWOOD BLVD

LAKE MARY, FL 32746

STE. 200

LAKE MARY, FL 32746

CGC1508651 (Exp: 08/31/2010) (407)838-1486

Sub Contractors

ROBERT G DELLO RUSSO
Status Location Address State License Number Phone Fax
DECEASED

531 CODISCO WAY

SANFORD, FL 32771

CAC032448 (Exp: 08/31/2022) (407)831-2665 (407)333-3853
THEODORE BARRON JOHNSON
Status Location Address State License Number Phone
ACTIVE

PO BOX 479

Flagler Beach, FL 32136

CAC057081 (Exp: 08/31/2026) 386-333-1672

Inspection History

Type Request Date Result Inspector
HOOD FINAL 03/30/2007 FINAL APPROVED JLEWIS
COMMERCIAL HOOD & DUCT LIGHT TEST INSPECTION 02/19/2007 APPROVED BMEYERS

Review History

Department Status Date In Date Out
BLD COMPLETE 02/14/2007 02/14/2007
Note: Released By: CCOTE Approved for Release. Review by Fred R. REVISION: Revised layout.
BLD HOLD 01/31/2007 02/01/2007
Note: Submitted revised plan for kitchen exhaust hood system - 1/31/07. Held By: FREODICA 1. Comments on submitted revised plan for kitchen exhaust hood system only: a. Provide section/detail indicating the size and location of make-up fresh air intake louver. b. Grease duct horizontal cleanout shall comply with FBC/M section 506.3.9 c. Indicate grease duct slope per FBC/M section 506.3.7. d. Provide section/detail showing make-up air connection to kitchen hood with fire dampers to comply with FBC/M section 506.3.1.2.
BLD COMPLETE 04/27/2006 04/28/2006
Note: Released By: LWOODROME Checked by FR
BLD HOLD 02/14/2006 03/08/2006
Note: Held By: FREODICA 1. Recalculate the size of grease exhaust duct connection from exhaust hood thorough roof to KEF-1 (plan key note 10 on M1) to comply with FBC 2004 section 506.3.4. 2. Verify if there is an electrical source of 3 phase system in the clubhouse. The kitchen exhaust hood supply & exhaust fans are shown on equipment schedule (FS-6) to be 3 phase, 208 volts while these equipments are both shown on mechanical sheet M2 to be 1 phase, 208 volts.
FD1 COMPLETE 02/13/2006 02/13/2006
Note: Released By: JPATTEE This is for a hood installation permit only not for fire extinguishing system.

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
RENEW PERMIT FEES ¤40.00 03/29/2007
REVISION ¤80.00 03/29/2007
REVISION ¤40.00 03/29/2007
FIRE PLANS REVIEW ¤25.00 05/12/2006
PERMIT FEE ¤73.50 05/12/2006
Fees Total Due: ¤0.00 Total Paid: ¤258.50