Type Request Date Result Inspector
GAS FINAL 09/08/2006 FINAL APPROVED JMCGOWEN
GAS ROUGH 03/30/2006 APPROVED JHINDMAN

Review History

Department Status Date In Date Out
BLD COMPLETE 03/14/2006 03/14/2006
Note: Released By: CCOTE Approved for Release.
BLD HOLD 03/13/2006 03/13/2006
Note: Held By: CCOTE Revised drawings addressing the following items must be submitted in order to complete the Building Permit Application plan review. 1. The pipe sizes given do not appear to meet the load given, there appears to be 6 drops and only 5 are indicated. Table 402.2 of the Florida Gas Code was used for approximate gas inputs for a total gas load of 285,000 BTU. Specific appliance BTU's should be used if known. a. Fireplace: 40,000 BTU b. Grill: 40,000 BTU c. Fire Pit (Gas Log): 80,000 BTU d. Clothes Dryer: 35,000 BTU e. Fireplace: 40,000 BTU f. Water Heater (50 gallon): 50,000 BTU 2. I have attached a copy of a printout of a gas riser from TracPipe software. A gas riser identifying pipe lengths as well as each appliance BTU and pipe sizing of each branch is required. Please provide a gas riser specific to this job.
BLD HOLD 03/07/2006 03/10/2006
Note: Held By: CCOTE Need tank size, location and whether it is above or below ground. Need supply pressure and pressure drop information. Need pipe size, material and length of run from tank to house. Need pipe lengths for each branch line in house. Need BTU use for each gas appliance. Clarify whether line to fire pit will be underground. If underground identify pipe material. In additional clarify when it will teminate.

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
PLUMBING FEE ¤31.20 03/14/2006
Fees Total Due: ¤0.00 Total Paid: ¤31.20