I want to search for...
Permit #2006030595
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7022-00060-0170 |
| Block: 00060 |
| Subdivision: 0 - |
| Job Phone: (386) 437-4800 |
| Location Address: 74 WESTCEDAR LN |
| Type: ME - MECHANICAL |
| Issue Date: 03/16/2006 |
| NOC: Unknown |
| Applicant name: RONALD E BANKS |
| Owner: PAYNE CHARLES E & FREDDA I H&W |
|
Address 74 WESTCEDAR LANE PALM COAST, FL 32164 |
| Lot: 0170 |
| Contracted Stated Job Value: ¤1,975.00 |
| Job Description: HVAC CHANGEOUT |
| Type: CN |
Contractor
REBCO AIR
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
PO BOX 353741 PALM COAST, FL 32164 |
CAC049308 (Exp: 08/31/2010) | (386) 437-4800 | (386)445-0030 |
Inspection History
| Type | Request Date | Result | Inspector |
| H.V.A.C. FINAL | 04/21/2006 | FINAL APPROVED | PGALLMANN |
| Note: THIS IS A REINSPECTION | |||
| H.V.A.C. FINAL | 04/18/2006 | Disapproved -FEE REQUIRED | JLEVRAULT |
| Note: ANCHOR CONDENSING UNIT TO SLAB. INSTALL CLAMP WITHIN 12" OF CONDENSING UNIT DISCONNECT. MAXIMUM OVERCURRENT DEVICE LISTED ON CONDENSING UNIT IS 45 AMPS - A 50 AMP BREAKER IS INSTALLED. DRAFTSTOP HOLE IN CEILING FOR CONDENSING LINE ABOVE AHU IN GARAGE. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 04/20/2006 |
| MECHANICAL FEE | ¤31.18 | 03/16/2006 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤71.18 |