I want to search for...

Permit #2006030595

Permit Details

Status: FINAL

Parcel Id: 07-11-31-7022-00060-0170
Block: 00060
Subdivision: 0 -
Job Phone: (386) 437-4800
Location Address: 74 WESTCEDAR LN
Type: ME - MECHANICAL
Issue Date: 03/16/2006
NOC: Unknown
Applicant name: RONALD E BANKS
Owner: PAYNE CHARLES E & FREDDA I H&W

Address

74 WESTCEDAR LANE

PALM COAST, FL 32164

Lot: 0170
Contracted Stated Job Value: ¤1,975.00
Job Description: HVAC CHANGEOUT
Type: CN

Contractor

REBCO AIR
Status Location Address State License Number Phone Fax
CANCEL

PO BOX 353741

PALM COAST, FL 32164

CAC049308 (Exp: 08/31/2010) (386) 437-4800 (386)445-0030

Inspection History

Type Request Date Result Inspector
H.V.A.C. FINAL 04/21/2006 FINAL APPROVED PGALLMANN
Note: THIS IS A REINSPECTION
H.V.A.C. FINAL 04/18/2006 Disapproved -FEE REQUIRED JLEVRAULT
Note: ANCHOR CONDENSING UNIT TO SLAB. INSTALL CLAMP WITHIN 12" OF CONDENSING UNIT DISCONNECT. MAXIMUM OVERCURRENT DEVICE LISTED ON CONDENSING UNIT IS 45 AMPS - A 50 AMP BREAKER IS INSTALLED. DRAFTSTOP HOLE IN CEILING FOR CONDENSING LINE ABOVE AHU IN GARAGE.

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION FEE ¤40.00 04/20/2006
MECHANICAL FEE ¤31.18 03/16/2006
Fees Total Due: ¤0.00 Total Paid: ¤71.18