Permit #2006060680

Permit Details

Status: COED

Parcel Id: 09-12-31-5117-00000-0080
Total Square Footage: 13308 sqft
Block: 00000
Subdivision: 2121 - Pinnacles Professional Park
Job Phone: (386)677-8736
Location Address: 80 PINNACLES DR
Type: BC - BUILDING COMMERCIAL
Issue Date: 09/22/2006
NOC: RECORDED
Applicant name: LEONARD MARINACCO
Owner: SEMINOLE 100 DEVELOPERS INC

Address

4 INDIAN MOUND COURT

FLAGLER BEACH, FL 32136

Lot: 0080
Contracted Stated Job Value: ¤1,125,000.00
Job Description: OFFICE BUILDING # B
Type: CN

Contractor

BOMAR CONSTRUCTION INC
Status Location Address State License Number Phone Fax
INACTIVE

27 S ORCHARD STREET

ORMOND BEACH, FL 32174

CGC015648 (Exp: 08/31/2022) (386)677-8736 (386)677-7726

Sub Contractors

BRADLEY S GILES
Status Location Address State License Number Phone Fax
ACTIVE

PO BOX 214176

S. DAYTONA, FL 32119

EC0001538 (Exp: 08/31/2026) (386) 767-5895 (386)767-6260
DONALD G MEYER
Status Location Address State License Number Phone
CANCEL

P. O. Drawer 730008

Ormond Beach, FL 32174

CAC039739 (Exp: 08/31/2016) (386) 253-7774
ROBERT V VON KAAS
Status Location Address State License Number Phone
CANCEL

909 Carswell Avenue

Holly Hill, FL 32117

CFC057448 (Exp: 08/31/2010) (386) 253-8222
ROBERT HARRIS SIPES
Status Location Address State License Number Phone Fax
CANCEL

515 LPGA BLVD

HOLLY HILL, FL 32117

CCC057312 (Exp: 08/31/2010) (386) 252-3377 (386)257-9490

Inspection History

Type Request Date Result Inspector
FINAL COMPLETE BUILDING INSPECTION 07/27/2007 FINAL APPROVED JLEVRAULT
Note: THIS IS A REINSPECTION Per Joe
FINAL COMPLETE BUILDING INSPECTION 07/26/2007 Disapproved -FEE REQUIRED JLEVRAULT
Note: SUPER GIVEN LONG CORRECTION SHEET.
UTILITY COMMERCIAL FINAL 07/26/2007 APPROVED KKING
UTILITY COMPANY FINAL 07/25/2007 APPROVED TSCHWEERS
LANDSCAPE FINAL 07/25/2007 APPROVED CBENNETT
Note: BOMAR NEEDS TO REMOVE CONCRETE BLOCKS ON THE LEFT AND NEIGHBORING PROPERTY, - LIGUSTROM TREES CHANGED WITH CRAPE MYRTLES ALONG POND UNDER POWER LINES. INSTALL 2 VIBURNUM SHRUBS AROUND BACK FLOW IN FRONT OF BUILDING B-- RELOCATED OAK ALONG BUILDING B TO A CENTER PARKING LOT ISLAND DUE TO UTILITY CONFLICTS-- PLEASE PRUNE AND FIX BROKEN BRANCHES ON TREES. REMOVED THE SOD BEHIND BACK FLOW AND REPLACE WITH PITTOSPURM SHRUBS--
STORMWATER FINAL INSPECTION 07/25/2007 CANCELLED BY INSPECTOR LAPTEKAR
Note: This inspection will be handled with the engineering dep.///duplicate
ENGINEERING FINAL 07/25/2007 APPROVED KKRUGER
FIRE FINAL 07/20/2007 APPROVED JLEWIS
FIREWALL INSPECTION 07/18/2007 APPROVED - AS NOTED JPATTEE
Note: recieved sealed letter from engineer
INSULATION INSPECTION 07/13/2007 APPROVED PPROVIDER
Note: Letter from Bechtol Engineering Re:missed insulation inspection
H.V.A.C. FINAL 07/06/2007 APPROVED JL
PLUMBING FINAL 07/06/2007 APPROVED PGALLMANN
ELECTRICAL FINAL 07/05/2007 APPROVED LHITES
Note: THIS IS A REINSPECTION
ELECTRICAL FINAL 07/02/2007 Disapproved -FEE REQUIRED LHITES
Note: OUTLETS IN MENS AND WOMENS RESTROOMS NEED TO BE GFCI PROTECTED. WASHER OUTLET SHOULD BE A SINGLE OUTLET. STRAP LFMC AT WATER HEATERS. BLANK OFF UNUSED OUTLET FOR RECIRCULATING PUMP. NEED COVER PLATE FOR SWITCH-OUTLET COMBO
H.V.A.C. FINAL 06/22/2007 Disapproved -FEE REQUIRED JLEVRAULT
Note: INSTALL SERVICE OUTLET ON ROOF TOP UNIT ON NORTH EAST CORNER OF ROOF.
SIDEWALK 06/19/2007 CANCELLED BY APPLICANT AIRS WEB
SIDEWALK 06/19/2007 Disapproved -FEE REQUIRED DMAY
SIDEWALK 06/18/2007 CANCELLED BY APPLICANT AIRS WEB
SIDEWALK 06/17/2007 APPROVED DMAY
Note: THIS IS A REINSPECTION
COMMERCIAL POWER INSPECTION 05/30/2007 APPROVED LHITES
Note: called fpl 5/30
2ND ROUGH ELECTRICAL 05/30/2007 APPROVED LHITES
Note: THIS IS A REINSPECTION
2ND ROUGH ELECTRICAL 05/25/2007 Disapproved -FEE REQUIRED MMOORE
Note: 1. BLUE EMT STRAP EVERY 3' 2. STRAP EMT WHERE IT IS ON TOP OF SPRINKLER LINES / SUPPORTS TOO FAR APART / NOT SECURED PROPERLY
H.V.A.C. ROUGH 05/25/2007 APPROVED - AS NOTED JLEVRAULT
Note: ABOVE CEILING HVAC.
COMMERCIAL POWER INSPECTION 05/01/2007 APPROVED LHITES
Note: CALLED FPL 5/1
SECOND ROUGH PLUMBING INSPECTION 03/28/2007 APPROVED JGIBSON
Note:
SECOND ROUGH PLUMBING INSPECTION 03/15/2007 Disapproved -FEE REQUIRED JGIBSON
Note: MISSING MANY NAIL PLATES ON WATER AND WASTE AND VENT STACKS, ALSO ISOLATE COPPER LINES @ ALL DROPS, MISSING SHOWER UNIT MUST BE FOR SECOND ROUGH INSPECTION.
FRAMING 03/14/2007 APPROVED JHINDMAN
Note:
H.V.A.C. ROUGH 03/08/2007 APPROVED - AS NOTED JLEVRAULT
Note: SOUTH HALF OF GROUND FLOOR RETURN AIR AND EXHAUST DUCTWORK.
2ND ROUGH ELECTRICAL 03/06/2007 APPROVED RMARVEL
ROOF SHEATHING/BRACES/TIES/ DOWN CELL 01/12/2007 APPROVED - AS NOTED JHINDMAN
Note: Canopy inspected.
LINTEL 12/12/2006 APPROVED - AS NOTED JHINDMAN
Note: PARAPIT
LINTEL 12/01/2006 APPROVED - AS NOTED JHINDMAN
Note: TIE BEAM
LINTEL 11/16/2006 APPROVED JHINDMAN
Note:
LINTEL 11/15/2006 APPROVED - AS NOTED JHINDMAN
Note: 3rd lift 3RD LIFT SIDES AND REAR
LINTEL 11/13/2006 APPROVED - AS NOTED DROCKWELL
Note: 2nd lift O.K
LINTEL 11/09/2006 APPROVED - AS NOTED JLEVRAULT
Note: FIRST LIFT.
MONOLITHIC SLAB INSPECTION/SLAB 11/02/2006 APPROVED JHINDMAN
Note:
STEM FOOTING FOUNDATION 11/01/2006 APPROVED JHINDMAN
Note:
FIRST ROUGH PLUMBING INSPECTION 10/26/2006 APPROVED JGIBSON
FOOTER 10/16/2006 APPROVED JHINDMAN
Note:

Review History

Department Status Date In Date Out
BLD COMPLETE 09/07/2006 09/11/2006
Note: Released By: LWOODROME
BLD HOLD 07/24/2006 08/14/2006
Note: Held By: LWOODROME PLAN REVIEW COMMENTS: " Clarify the scope of work for this project by removing all sheets, from the plan(s), which do not pertain to Building "B" (sheets marked building "A") and on sheets which show details or schedules for both buildings, X out the details or schedules which do not pertain to Building "B". The removal of sheets and/or the X'ing out of details must be preformed by your representative. Work space will be provided for you to perform this task. " Verify that door hardware complies with the Florida Building Code, section 11-4.13.9 for H. C. accessibility. " Specify a labeled door frame, door and appropriate hardware for door(s) 801A, 800B, 718B and at the electrical room, which are for openings in rated assemblies. " Clarify detail mark 4/A6.01, 0n sheet A3.1, sheet A6.01 is not included in the plan. " Revise and coordinate detail mark(s) on sheet A3.2 to reference the correct detail(s) on sheet A6.3. " Specify, on sheet A4.3, the wall type for the wall(s) between the vestibule and the public restrooms. " Provide fire damper(s) in the 8"X4" return air duct and the 5" round supply duct, where these ducts penetrated the rated wall assembly of vestibule #725. " Revise sanitary and water diagrams to include the drinking fountain(s), shown on the floor plan, in the common lobby. " Relocate electrical panel for Suite 800, to a space with in Suite 800 or otherwise indicate compliance with National Electrical Code, Article 225.35. " Verify adequate working space, per NEC, Article 110.26, at panel(s) located in the closet off corridor #718. " Provide WPGFCI receptacle outlets, on the roof, spaced so that no piece of roof mounted equipment is more than 25' from a receptacle outlet. " Provide receptacle outlet for electric water cooler. " Provide GFCI protection for receptacle outlets, in the therapy room(s), which are with in 6' of a sink. " Provide electrical disconnect(s) at water heater(s). " Provide additional directional exit signs, where corridor #708 meets with corridor #700 and corridor #718. " Provide emergency egress illumination for the public restrooms, x-ray and consult (area). Larry Woodrome, CBO Chief Plans Examiner City of Palm Coast 386-986-3786
FI1 COMPLETE 06/19/2006 07/07/2006
Note: Released By: JPATTEE Held By: JPATTEE Provide design criteria for the automatic fire sprinkler system per FAC 61G15-32 (5)
FI1 COMPLETE 07/24/2006
Note: Released By: JPATTEE

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION FEE ¤40.00 07/27/2007
MISCELLANEOUS ¤40.00 07/17/2007
REINSPECTION FEE ¤40.00 07/16/2007
REINSPECTION FEE ¤40.00 07/16/2007
REINSPECTION FEE ¤40.00 07/16/2007
REINSPECTION FEE ¤40.00 07/16/2007
REINSPECTION FEE ¤40.00 07/16/2007
TRANSPORTATION IMPACT FEE ¤118,949.43 09/22/2006
PERMIT FEE ¤6,187.50 09/22/2006
PLAN CHECK FEE ¤1,293.75 09/22/2006
PLUMBING FEE ¤705.00 09/22/2006
RADON FEE ¤66.54 09/22/2006
ADMIN FEE ¤20.00 09/22/2006
BUILDING CODE ADMIN FUND ¤66.54 09/22/2006
ELECTRIC FEE ¤705.00 09/22/2006
FIRE COMM IMPACT FEE 4-1-05 ¤6,615.41 09/22/2006
FIRE PLANS REVIEW ¤133.08 09/22/2006
MECHANICAL FEE ¤705.00 09/22/2006
Fees Total Due: ¤0.00 Total Paid: ¤135,727.25