I want to search for...
Permit #2006080522
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-5112-00000-0120 |
| Block: 00000 |
| Subdivision: - |
| Job Phone: (386) 672-3464 |
| Location Address: 2 COMMERCE BLVD |
| Type: ME - MECHANICAL |
| Issue Date: 08/21/2006 |
| NOC: Unknown |
| Applicant name: DANNY LEE WILSON |
| Owner: CITY OF PALM COAST |
|
Address 2 COMMERCE BLVD PALM COAST, FL 32164 |
| Lot: 0120 |
| Contracted Stated Job Value: ¤4,593.00 |
| Job Description: HVAC CHANGE OUT |
| Type: CN |
Contractor
WILSON'S AIR CONDITIONING INC. (AC CONTRACTOR)
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
1532 State Avenue Unit K Holly Hill, FL 32117 |
CAC058288 (Exp: 08/31/2010) | (386) 672-3464 | (386)672-0153 |
Inspection History
| Type | Request Date | Result | Inspector |
| H.V.A.C. FINAL | 02/26/2008 | FINAL APPROVED | JMCGOWEN |
| Note: THIS IS A REINSPECTION | |||
| H.V.A.C. FINAL | 02/13/2008 | Disapproved -FEE REQUIRED | JLEVRAULT |
| Note: THIS IS A REINSPECTION UNIT NOT ANCHORED TO ROOF. MISSING BUSHING IN DISCONNECT AT UNIT. ELECTRICAL PANEL NOT LABELED - CANNOT CHECK M.O.P.. TWO FANS ON UNIT MISSING SCREW ON TOP OF CAGE TO HOLD FAN IN PLACE. | |||
| H.V.A.C. FINAL | 01/04/2007 | Disapproved - NO FEE | JLEVRAULT |
| Note: THIS IS A REINSPECTION CONTRACTOR CALLED TO SCHEDULE A FINAL INSPECTION FOR 1/4/07 UNIT NOT STRAPPED DOWN. THERMOSTAT WIRE NOT CONNECTED. EMT NEEDS TO BE REPLACED - IT IS BROKEN AND LAYING IN WATER ON ROOF. CONDENSATE LONE NOT CONNECTED. SUPPORT REFRIDGERANT LINE. ANCHOR DISCONNECT PROPERLY AND FIRMLY TO UNIT. | |||
| H.V.A.C. FINAL | 08/24/2006 | Disapproved - NO FEE | JMCGOWEN |
| Note: need to strap down unit, conditioned area is not getting cool, need to check controls |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| MECHANICAL FEE | ¤32.76 | 08/21/2006 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤32.76 |