Permit #2006110483

Permit Details

Status: CANCEL

Parcel Id: 07-11-31-7028-00160-0150
CONDITIONED SPACE: 1234 sqft
CONDITIONED SPACE: 1566 sqft
GARAGE: 419 sqft
OPENED PORCH (WITH ROOF) : 23 sqft
Total Square Footage: 3242 sqft
Block: 00160
Subdivision: -
Location Address: 29 POPE LN
Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY
Issue Date: 01/24/2007
NOC: Unknown
Applicant name: NO CONTRACTOR OF RECORD
Owner: QIN YI LIN

Address

91-10 WHITNEY AVENUE

ELMHURST, NY 11373

Lot: 0150
Contracted Stated Job Value: ¤150,000.00
Job Description: SINGLE FAMILY RESIDENCE
Type: CN

Contractor

NO CONTRACTOR OF RECORD
Status State License Number
CANCEL CGC1111111 (Exp: 05/20/2016)

Sub Contractors

RICHARD R EDWARDS
Status Location Address State License Number Phone
CANCEL

P. O. Box 1637

Bunnell, FL 32110

ER0011603 (Exp: 08/31/2022) (386) 437-1537
RICHARD LEE VONBROCKEN
Status Location Address State License Number Phone Fax
INACTIVE

1738 STATE AVE

HOLLY HILL, FL 32117

CAC035516 (Exp: 08/31/2026) (386)672-1950 (386)672-1952
MARTIN GEORGE LANGILLE
Status Location Address State License Number Phone
CANCEL

1727 Maryland Ave

Ormond Beach, FL 32174

CFC026550 (Exp: 08/31/2018) (386) 673-3233
ANTHONY FALLONE
Status Location Address State License Number Phone Fax
CANCEL

P.O. BOX 351222

PALM COAST, FL 32137

CBC1250596 (Exp: 08/31/2022) 386-503-0906 (386)986-1305

Inspection History

Type Request Date Result Inspector
PROJECT STATUS INSPECTION 11/21/2008 Disapproved - NO FEE ACOOPER
Note: Inspection Resulted at 11/21/2008 1:13:38 PM HOME HAS BEEN LEFT OPEN AND VANDALIZED. ELECTRICAL WIRING IS CUT, GRASS AND WEEDS ARE UNCUT, WINDOWS BROKEN ALL AROUND, SEE PHOTOS. THIS HOME CURRENTLY IS A SAFETY HAZARD DUE TO BROKEN GLASS AND WINDOWS. ART
ALL ROUGH 01/04/2008 APPROVED JHINDMAN
Note: THIS IS A REINSPECTION
ALL ROUGH 12/17/2007 Disapproved -FEE REQUIRED PGALLMANN
Note: THIS IS A REINSPECTION MENDING PLATES ABOVE PANEL STILL MISSING,VENT FOR UPSTAIRS WATER CLOSET NOT TO CODE/ ROLLED UP VENT, STILL MISSING NAIL PLATES ON PLUMBING AND ELECTRIC, NEED TO FIRE BLOCK PLUMBING VENT AND WASTE STACKS ON FIRST FLOOR, SEAL FLOOR @ TUB DRAINS, SHOW 5` HEAD PRESSURE ON SECOND FLOOR TEST, SERVICE CABLE FOR 200 AMP SERVICE UNDER SIZED. PAUL GALLMANN..............931-7400
ALL ROUGH 12/11/2007 Disapproved -FEE REQUIRED JHINDMAN
Note: LOOSE GROUND SCREWS IN MANY ELECTRICAL BOXES, MISSING NAIL PLATES MANY LOCATIONS,NEED RECEPTACLE AT UPSTAIRS HALL AND AT JACUZZI TUB, RESTRAP UPSTAIRS RIGHT REAR WINDOW JACK, ALL TOP PLATES THAT HAVE BEEN NOTCHED OVER 60 % MUST HAVE APPROVED MENDING PLATES.
EXTERIOR WALL SHEATHING/SHEAR WALL 05/17/2007 APPROVED DROCKWELL
ROOF SHEATHING/BRACES/TIES/ DOWN CELL 05/17/2007 APPROVED - AS NOTED DROCKWELL
LINTEL 04/04/2007 APPROVED ACOOPER
FOUNDATION SURVEY APPROVED BY STORMWATER 04/03/2007 APPROVED - AS NOTED LAPTEKAR
Note: FFE adjusted / advised care in grading on left side
TEMPORARY POLE 03/20/2007 APPROVED LHITES
Note:
MONOLITHIC SLAB INSPECTION/SLAB 02/09/2007 APPROVED ACOOPER
Note:
FIRST ROUGH PLUMBING INSPECTION 02/06/2007 APPROVED ACOOPER
Note:
LATH /BRICK FLASHING
INSULATION INSPECTION
STORMWATER FINAL INSPECTION
UTILITY COMPANY FINAL
FINAL COMPLETE BUILDING INSPECTION

Review History

Department Status Date In Date Out
BLD COMPLETE 12/28/2006 01/03/2007
Note: Released By: CCOTE Approved for Release per plan cover sheet. Review by Auba.
ZON COMPLETE 12/19/2006 12/19/2006
Note: Released By: DRAMIREZ Changes to roof pitch,color material sheet and landscaping schedule was submitted.
BLD HOLD 12/19/2006 12/19/2006
Note: Held By: JJOSEPH Please provide the second copy of your revision signed and sealed (3 of 5 and 4 of 5) Provide the new energy form (600A-04R,600B-04R,600C-04R) using the computer Program FLA/RES version 4.5.
ZON HOLD 11/30/2006 12/05/2006
Note: Held By: DRAMIREZ Roof pitch has to be over min. 5/12. Plans show a roof pitch of 4/12. Please revise plan to meet the requirements of the LDC code.
ZON HOLD 11/27/2006 11/28/2006
Note: Held By: DRAMIREZ Hold for a color material sheet. Need color samples or numbering. Need landscaping plans. Need 5.12 roof pitch -
ZON HOLD 11/29/2006
Note: Held By: ECOYNE for ARC meeting 12/01/06
SW1 COMPLETE 11/28/2006
Note: Released By: WKINELL

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADMIN FEE ¤20.00 01/24/2007
ARC HOUSE REVIEW ¤125.00 01/24/2007
BUILDING CODE ADMIN FUND ¤16.21 01/24/2007
ELECTRIC FEE ¤184.80 01/24/2007
FIRE IMPACT FEE 4-1-06 ¤179.37 01/24/2007
MECHANICAL FEE ¤184.80 01/24/2007
PERMIT FEE ¤1,006.20 01/24/2007
PARKS IMPACT FEE 4/1/06 ¤1,159.02 01/24/2007
PLAN CHECK FEE ¤103.20 01/24/2007
PLUMBING FEE ¤184.80 01/24/2007
RADON FEE ¤16.21 01/24/2007
SCHOOL BOARD IMPACT FEE RES ¤3,600.00 01/24/2007
STORM WATER PERMIT FEES ¤80.00 01/24/2007
10/06 TRANS IMPACT FEE/MULTI ¤3,631.83 01/24/2007
REINSPECTION FEE ¤40.00
REINSPECTION FEE ¤40.00
RENEW PERMIT FEES ¤40.00
Fees Total Due: ¤120.00 Total Paid: ¤10,491.44