Permit #2006120167

Permit Details

Status: COED

Parcel Id: 06-12-31-5815-00000-0200
COMMERCIAL SQUARE FOOTAGE: 3243 sqft
Total Square Footage: 3243 sqft
Block: 00000
Subdivision: 2118 - Town Center Phase I
Job Phone: (904)260-2900
Location Address: 21 HOSPITAL DR
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 02/06/2007
NOC: RECORDED
Applicant name: RONALD H FOSTER
Owner: PALM COAST MEDICAL SPECIALISTS LTD

Address

21 HOSPITAL DR STE 200

PALM COAST, FL 32164

Lot: 0200
Contracted Stated Job Value: ¤394,595.00
Job Description: BUILD-OUT SUITE 180 - "FOFSA"
Type: CN

Contractor

STELLAR GROUP INC
Status Location Address State License Number Phone
INACTIVE

2900 HARTLEY ROAD

JACKSONVILLE, FL 32257

CGC052029 (Exp: 08/31/2024) 904-899-9214

Sub Contractors

RONALD A AUTREY
Status Location Address State License Number Phone
CANCEL

PO Box 1799

Jacksonville, Fl., 32201

ECOOOO388 (Exp: 08/31/2018) (904) 388-8000
ERIC TIMOTHY HOLCOMB
Status Location Address State License Number Phone Fax
CANCEL

101 MUNDY MEMORIAL

MT JULIET, TN 37122

CMC1249492 (Exp: 09/30/2008) (800)222-1819 (615)773-8108
GARY S WELBORN
Status Location Address State License Number Phone Fax
CANCEL

1709 North Nova Road

Holly Hill, FL 32117

CFC037140 (Exp: 08/31/2018) (386) 257-1172 (386)252-5979
ANTHONY JAMES PARETE
Status Location Address State License Number Phone Fax
INACTIVE

6900 PHILLIPS INDUSTRIAL BLVD.

JACKSONVILLE, FL 32256

CCC044057 (Exp: 08/31/2026) (904)880-6005 (904)880-3377
WILLIAM W GAY
Status Location Address State License Number Phone Fax
DECEASED

524 STOCKTON STREET

JACKSONVILLE, FL 32204

CMC008140 (Exp: 08/31/2020) (904)388-2696 904-394-7944
JOHN W BARBER JR
Status Location Address State License Number Phone Fax
INACTIVE

1514 BERNITA STREET

JACKSONVILLE, FL 32211

CCC057141 (Exp: 08/31/2020) (904)744-4067 (904)744-4209

Inspection History

Type Request Date Result Inspector
UTILITY COMMERCIAL FINAL 04/08/2008 APPROVED DSPENCER
FINAL COMPLETE BUILDING INSPECTION 04/08/2008 FINAL APPROVED JLEVRAULT
FIRE FINAL 04/04/2008 APPROVED JPATTEE
ELECTRICAL FINAL 04/02/2008 APPROVED RMARVEL
PLUMBING FINAL 03/28/2008 APPROVED JGIBSON
ABOVE CEILING 02/04/2008 APPROVED JLEVRAULT
COMMERCIAL POWER INSPECTION 01/24/2008 APPROVED LHITES
FIREWALL INSPECTION 01/04/2008 APPROVED JPATTEE
FIREWALL INSPECTION 01/03/2008 Disapproved - NO FEE JPATTEE
Note: Not ready for inspection
INSULATION INSPECTION 12/20/2007 APPROVED JHINDMAN
SECOND ROUGH PLUMBING INSPECTION 12/17/2007 APPROVED - AS NOTED JGIBSON
Note: THIS IS A REINSPECTION SECOND ROUGH PLUMBING OK PLAN REVEIW APPROVED REVISIONS THAT WERE MADE.
SECOND ROUGH PLUMBING INSPECTION 11/16/2007 Disapproved -FEE REQUIRED JGIBSON
Note: NEED TEST TEES TURNED OUT OF WALL PER PLAN, NEED PAGE P002 THAT WAS DELETED FOR MED GAS SPECS, NEED REVISIONS ON ALL CHANGES OF ALARM PANELS AND MED GAS PANELS INSIDE OF ROOMS.
2ND ROUGH ELECTRICAL 11/13/2007 APPROVED LHITES
Note: WALLS ONLY
FRAMING 09/04/2007 APPROVED JHINDMAN
H.V.A.C. ROUGH 08/16/2007 APPROVED JLEVRAULT
Note: called by contractor
FIRE SPRINKLER 2ND ROUGH HYDROSTATIC PRESSURE TEST 07/18/2007 APPROVED JPATTEE
Note: THIS IS A REINSPECTION
FIRE SPRINKLER 1ST ROUGH 07/12/2007 APPROVED JPATTEE
FIRE SPRINKLER 2ND ROUGH HYDROSTATIC PRESSURE TEST 07/12/2007 CANCELLED BY APPLICANT JPATTEE

Review History

Department Status Date In Date Out
ELEC COMPLETE 03/31/2008 03/31/2008
Note: Released By: SKNOPF Approved for Release. Revision - (1) Receptacle added to each of the following rooms: ckt #3 (1807) ckt #5 (1810, 1811) ckt #7 (1812) ckt #15 (1804) ckt #21 (1816) ckt #23 (1817)
BLD COMPLETE 03/27/2008 03/27/2008
Note: Released By: FREODICA Revision: paper towel dispensers adidtional workstation installation at work area. flooring base for Alcover 1 and 2 rooms have changed to VCT and Vinyl base Nurse "call system" not installed per owner's request.
ELEC COMPLETE 03/20/2008 03/20/2008
Note: Released By: SKNOPF Approved for Release. Revision: Various electrical changes (see electrical comments 3-13-2008). Released by L.W.
ELEC HOLD 03/11/2008 03/13/2008
Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Revision to Permit #2006120167 (Suite 180 Florida Oral and Facial Surgical Associates @ 21 Hospital Dr.) 3/13/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. E001-180: a. Provide actual nameplate loads in the panel schedule for the following equipment for Load Calculation verification: (2) Refrigerators (circuits 29 & 35), crash cart (31), Water Feature (33), Autoclave (39), Ultrasonic (41), Processor (16), Med Gas Panel (40), Air Compressor (24), X-ray (32), Dryer (36). b. Please verify CU-1-7-A and AHU-1-7-A nameplate loads for load calculations. Mechanical Schedule is incomplete for electrical data. c. Identify loads in panel for circuits 20, 22, and 40. d. The following circuits have undersized loads in the panel. Please review and revise: circuits 3,5,7,11,15,23. e. Circuit 74 Water Heater in Panel is shown as 12KW with a 3P50A circuit breaker. P001-180 shows this equipment as a 6KW Water Heater. Confirm nameplate load for water heater, and provide proper size disconnect, circuit breaker, wire size for this circuit. f. Revise Load Calculations to conform to NEC 220 with actual loads for lighting, receptacles, equipment, HVAC and largest motor. Provide detailed load calculation as Demand load appears to be close to panelboard size. 2. E101-180: a. Identify lighting circuits for fixtures in room 1821 Treatment 4, 1815/1818/1825 Corridor, 1819 Sterilization (both 2x4's and undercounter lights). b. Floor plan room 1820 shows lighting on circuit 12. Panel Schedule circuit 16 shows lighting for this room. Sheet E102-180 shows a Processor equipment receptacle on circuit 16. Clarify which circuit is correct for the lighting, and which is correct for the Processor in room 1820. 3. E102-180: a. Circuit 25 is shown both as a receptacle in Med Gas room and as a junction box in 1818. Panel Schedule load appears to only include the load for the receptacle. Identify what the additional load is at the junction box in 1818. b. Circuit 33 is shown in (2) locations, for both a Washer in Utility 1830, and for a Water Feature in Skin Care Procedure 1806. Please review loads for both equipment items and revise panel loads as necessary. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us
BLD COMPLETE 12/12/2007 12/13/2007
Note: Released By: FREODICA Rev.- Misc. rev. See sheets A101, A102,A201, P103, P501, P801, P802, P803 & E102.
BLD COMPLETE 01/29/2007 02/02/2007
Note: Released By: CCOTE Approved for Release. Review by Fred R.
FI1 COMPLETE 01/24/2007 01/29/2007
Note: Released By: JPATTEE 1. One (1) set of drawings sent to FD on 1/8/2007. 2. One (1) set of revised drawings to FD on 1/24/07.
BLD HOLD 12/14/2006 01/08/2007
Note: Held By: FREODICA CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application No. 2006120167 - Florida Oral & Facial Surgical Associates - Suite180 1. Dwg. No. M001-180: a. Revise Fan Schedule title from Suite 110 to Suite 180. b. Add Exhaust Fan EF-1-7-D for Medical Gas 1823 to Fan Schedule. See comment 2.b. 2. Dwg. No. M101-180: a. Provide space sensor for VAV-1-7-A1. b. Provide mechanical exhaust for Medical Gas 1823 per Florida Mechanical Code 2004 Section 502.9.1. The layout was shown on electrical Dwg. No. E102-180. c. Indicate duct outlet sizes on VAV-1-7-A3 and VAV-1-7-A5. 3. Dwg. No. M401-180: a. Clarify the name designation of Exhaust Fan EF-2-7-A as it did not match with the Exhaust Fan Schedule. 4. Dwg. No. P-001-180: a. Revise Plumbing Fixture Schedule title from Suite 220 to Suite 180. b. Clarify water heater tag designation. c. Reference sheet P002-2200 for medical gas valve specifications can not be found. Provide referenced sheet or indicate specifications on Plumbing Fixture Schedule. 5. Dwg. No. P-101-180: a. Provide reference information on condensate lines tied to existing system. b. Show on plan AHU-1-7-A and its condensate line. 6. Dwg. No. P803-180: a. Clarify pipe sizes of medical vacuum header as two(2) ½" branch pipes were tied into ¼" header. 7. Dwg. No. E103-180: a. Exhaust fan EF-1-7-A or EF-2-7-A? on roof and its power supply was missing.
DSD COMPLETE 01/30/2007
Note: Released By: DCHAUDOIN
UD1 COMPLETE 01/25/2007
Note: Released By: CJOHNSON

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADDITIONAL FEE ¤40.00 04/04/2008
ADDITIONAL FEE ¤40.00 04/04/2008
REINSPECTION FEE ¤40.00 04/04/2008
REVISION ¤40.00 04/04/2008
REVISION ¤60.00 04/04/2008
REVISION ¤40.00 04/04/2008
REVISION ¤40.00 04/04/2008
ADMIN FEE ¤20.00 02/06/2007
ELECTRIC FEE ¤267.00 02/06/2007
FIRE PLANS REVIEW ¤32.43 02/06/2007
MECHANICAL FEE ¤267.00 02/06/2007
PERMIT FEE ¤2,765.00 02/06/2007
PLAN CHECK FEE ¤454.25 02/06/2007
PLUMBING FEE ¤267.00 02/06/2007
Fees Total Due: ¤0.00 Total Paid: ¤4,372.68