Permit #2006120167
Permit Details
Status: COED
| Parcel Id: 06-12-31-5815-00000-0200 |
| COMMERCIAL SQUARE FOOTAGE: 3243 sqft |
| Total Square Footage: 3243 sqft |
| Block: 00000 |
| Subdivision: 2118 - Town Center Phase I |
| Job Phone: (904)260-2900 |
| Location Address: 21 HOSPITAL DR |
| Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION |
| Issue Date: 02/06/2007 |
| NOC: RECORDED |
| Applicant name: RONALD H FOSTER |
| Owner: PALM COAST MEDICAL SPECIALISTS LTD |
|
Address 21 HOSPITAL DR STE 200 PALM COAST, FL 32164 |
| Lot: 0200 |
| Contracted Stated Job Value: ¤394,595.00 |
| Job Description: BUILD-OUT SUITE 180 - "FOFSA" |
| Type: CN |
Contractor
STELLAR GROUP INC
| Status | Location Address | State License Number | Phone |
| INACTIVE |
2900 HARTLEY ROAD JACKSONVILLE, FL 32257 |
CGC052029 (Exp: 08/31/2024) | 904-899-9214 |
Sub Contractors
RONALD A AUTREY
| Status | Location Address | State License Number | Phone |
| CANCEL |
PO Box 1799 Jacksonville, Fl., 32201 |
ECOOOO388 (Exp: 08/31/2018) | (904) 388-8000 |
ERIC TIMOTHY HOLCOMB
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
101 MUNDY MEMORIAL MT JULIET, TN 37122 |
CMC1249492 (Exp: 09/30/2008) | (800)222-1819 | (615)773-8108 |
GARY S WELBORN
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
1709 North Nova Road Holly Hill, FL 32117 |
CFC037140 (Exp: 08/31/2018) | (386) 257-1172 | (386)252-5979 |
ANTHONY JAMES PARETE
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
6900 PHILLIPS INDUSTRIAL BLVD. JACKSONVILLE, FL 32256 |
CCC044057 (Exp: 08/31/2026) | (904)880-6005 | (904)880-3377 |
WILLIAM W GAY
| Status | Location Address | State License Number | Phone | Fax |
| DECEASED |
524 STOCKTON STREET JACKSONVILLE, FL 32204 |
CMC008140 (Exp: 08/31/2020) | (904)388-2696 | 904-394-7944 |
JOHN W BARBER JR
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
1514 BERNITA STREET JACKSONVILLE, FL 32211 |
CCC057141 (Exp: 08/31/2020) | (904)744-4067 | (904)744-4209 |
Inspection History
| Type | Request Date | Result | Inspector |
| UTILITY COMMERCIAL FINAL | 04/08/2008 | APPROVED | DSPENCER |
| FINAL COMPLETE BUILDING INSPECTION | 04/08/2008 | FINAL APPROVED | JLEVRAULT |
| FIRE FINAL | 04/04/2008 | APPROVED | JPATTEE |
| ELECTRICAL FINAL | 04/02/2008 | APPROVED | RMARVEL |
| PLUMBING FINAL | 03/28/2008 | APPROVED | JGIBSON |
| ABOVE CEILING | 02/04/2008 | APPROVED | JLEVRAULT |
| COMMERCIAL POWER INSPECTION | 01/24/2008 | APPROVED | LHITES |
| FIREWALL INSPECTION | 01/04/2008 | APPROVED | JPATTEE |
| FIREWALL INSPECTION | 01/03/2008 | Disapproved - NO FEE | JPATTEE |
| Note: Not ready for inspection | |||
| INSULATION INSPECTION | 12/20/2007 | APPROVED | JHINDMAN |
| SECOND ROUGH PLUMBING INSPECTION | 12/17/2007 | APPROVED - AS NOTED | JGIBSON |
| Note: THIS IS A REINSPECTION SECOND ROUGH PLUMBING OK PLAN REVEIW APPROVED REVISIONS THAT WERE MADE. | |||
| SECOND ROUGH PLUMBING INSPECTION | 11/16/2007 | Disapproved -FEE REQUIRED | JGIBSON |
| Note: NEED TEST TEES TURNED OUT OF WALL PER PLAN, NEED PAGE P002 THAT WAS DELETED FOR MED GAS SPECS, NEED REVISIONS ON ALL CHANGES OF ALARM PANELS AND MED GAS PANELS INSIDE OF ROOMS. | |||
| 2ND ROUGH ELECTRICAL | 11/13/2007 | APPROVED | LHITES |
| Note: WALLS ONLY | |||
| FRAMING | 09/04/2007 | APPROVED | JHINDMAN |
| H.V.A.C. ROUGH | 08/16/2007 | APPROVED | JLEVRAULT |
| Note: called by contractor | |||
| FIRE SPRINKLER 2ND ROUGH HYDROSTATIC PRESSURE TEST | 07/18/2007 | APPROVED | JPATTEE |
| Note: THIS IS A REINSPECTION | |||
| FIRE SPRINKLER 1ST ROUGH | 07/12/2007 | APPROVED | JPATTEE |
| FIRE SPRINKLER 2ND ROUGH HYDROSTATIC PRESSURE TEST | 07/12/2007 | CANCELLED BY APPLICANT | JPATTEE |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 03/31/2008 | 03/31/2008 |
| Note: Released By: SKNOPF Approved for Release. Revision - (1) Receptacle added to each of the following rooms: ckt #3 (1807) ckt #5 (1810, 1811) ckt #7 (1812) ckt #15 (1804) ckt #21 (1816) ckt #23 (1817) | |||
| BLD | COMPLETE | 03/27/2008 | 03/27/2008 |
| Note: Released By: FREODICA Revision: paper towel dispensers adidtional workstation installation at work area. flooring base for Alcover 1 and 2 rooms have changed to VCT and Vinyl base Nurse "call system" not installed per owner's request. | |||
| ELEC | COMPLETE | 03/20/2008 | 03/20/2008 |
| Note: Released By: SKNOPF Approved for Release. Revision: Various electrical changes (see electrical comments 3-13-2008). Released by L.W. | |||
| ELEC | HOLD | 03/11/2008 | 03/13/2008 |
| Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Revision to Permit #2006120167 (Suite 180 Florida Oral and Facial Surgical Associates @ 21 Hospital Dr.) 3/13/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. E001-180: a. Provide actual nameplate loads in the panel schedule for the following equipment for Load Calculation verification: (2) Refrigerators (circuits 29 & 35), crash cart (31), Water Feature (33), Autoclave (39), Ultrasonic (41), Processor (16), Med Gas Panel (40), Air Compressor (24), X-ray (32), Dryer (36). b. Please verify CU-1-7-A and AHU-1-7-A nameplate loads for load calculations. Mechanical Schedule is incomplete for electrical data. c. Identify loads in panel for circuits 20, 22, and 40. d. The following circuits have undersized loads in the panel. Please review and revise: circuits 3,5,7,11,15,23. e. Circuit 74 Water Heater in Panel is shown as 12KW with a 3P50A circuit breaker. P001-180 shows this equipment as a 6KW Water Heater. Confirm nameplate load for water heater, and provide proper size disconnect, circuit breaker, wire size for this circuit. f. Revise Load Calculations to conform to NEC 220 with actual loads for lighting, receptacles, equipment, HVAC and largest motor. Provide detailed load calculation as Demand load appears to be close to panelboard size. 2. E101-180: a. Identify lighting circuits for fixtures in room 1821 Treatment 4, 1815/1818/1825 Corridor, 1819 Sterilization (both 2x4's and undercounter lights). b. Floor plan room 1820 shows lighting on circuit 12. Panel Schedule circuit 16 shows lighting for this room. Sheet E102-180 shows a Processor equipment receptacle on circuit 16. Clarify which circuit is correct for the lighting, and which is correct for the Processor in room 1820. 3. E102-180: a. Circuit 25 is shown both as a receptacle in Med Gas room and as a junction box in 1818. Panel Schedule load appears to only include the load for the receptacle. Identify what the additional load is at the junction box in 1818. b. Circuit 33 is shown in (2) locations, for both a Washer in Utility 1830, and for a Water Feature in Skin Care Procedure 1806. Please review loads for both equipment items and revise panel loads as necessary. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us | |||
| BLD | COMPLETE | 12/12/2007 | 12/13/2007 |
| Note: Released By: FREODICA Rev.- Misc. rev. See sheets A101, A102,A201, P103, P501, P801, P802, P803 & E102. | |||
| BLD | COMPLETE | 01/29/2007 | 02/02/2007 |
| Note: Released By: CCOTE Approved for Release. Review by Fred R. | |||
| FI1 | COMPLETE | 01/24/2007 | 01/29/2007 |
| Note: Released By: JPATTEE 1. One (1) set of drawings sent to FD on 1/8/2007. 2. One (1) set of revised drawings to FD on 1/24/07. | |||
| BLD | HOLD | 12/14/2006 | 01/08/2007 |
| Note: Held By: FREODICA CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application No. 2006120167 - Florida Oral & Facial Surgical Associates - Suite180 1. Dwg. No. M001-180: a. Revise Fan Schedule title from Suite 110 to Suite 180. b. Add Exhaust Fan EF-1-7-D for Medical Gas 1823 to Fan Schedule. See comment 2.b. 2. Dwg. No. M101-180: a. Provide space sensor for VAV-1-7-A1. b. Provide mechanical exhaust for Medical Gas 1823 per Florida Mechanical Code 2004 Section 502.9.1. The layout was shown on electrical Dwg. No. E102-180. c. Indicate duct outlet sizes on VAV-1-7-A3 and VAV-1-7-A5. 3. Dwg. No. M401-180: a. Clarify the name designation of Exhaust Fan EF-2-7-A as it did not match with the Exhaust Fan Schedule. 4. Dwg. No. P-001-180: a. Revise Plumbing Fixture Schedule title from Suite 220 to Suite 180. b. Clarify water heater tag designation. c. Reference sheet P002-2200 for medical gas valve specifications can not be found. Provide referenced sheet or indicate specifications on Plumbing Fixture Schedule. 5. Dwg. No. P-101-180: a. Provide reference information on condensate lines tied to existing system. b. Show on plan AHU-1-7-A and its condensate line. 6. Dwg. No. P803-180: a. Clarify pipe sizes of medical vacuum header as two(2) ½" branch pipes were tied into ¼" header. 7. Dwg. No. E103-180: a. Exhaust fan EF-1-7-A or EF-2-7-A? on roof and its power supply was missing. | |||
| DSD | COMPLETE | 01/30/2007 | |
| Note: Released By: DCHAUDOIN | |||
| UD1 | COMPLETE | 01/25/2007 | |
| Note: Released By: CJOHNSON |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADDITIONAL FEE | ¤40.00 | 04/04/2008 |
| ADDITIONAL FEE | ¤40.00 | 04/04/2008 |
| REINSPECTION FEE | ¤40.00 | 04/04/2008 |
| REVISION | ¤40.00 | 04/04/2008 |
| REVISION | ¤60.00 | 04/04/2008 |
| REVISION | ¤40.00 | 04/04/2008 |
| REVISION | ¤40.00 | 04/04/2008 |
| ADMIN FEE | ¤20.00 | 02/06/2007 |
| ELECTRIC FEE | ¤267.00 | 02/06/2007 |
| FIRE PLANS REVIEW | ¤32.43 | 02/06/2007 |
| MECHANICAL FEE | ¤267.00 | 02/06/2007 |
| PERMIT FEE | ¤2,765.00 | 02/06/2007 |
| PLAN CHECK FEE | ¤454.25 | 02/06/2007 |
| PLUMBING FEE | ¤267.00 | 02/06/2007 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤4,372.68 |