Permit #2006120170
Permit Details
Status: COED
| Parcel Id: 06-12-31-5815-00000-0200 |
| Total Square Footage: 2587 sqft |
| Block: 00000 |
| Subdivision: 2118 - Town Center Phase I |
| Job Phone: (904)260-2900 |
| Location Address: 21 HOSPITAL DR |
| Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION |
| Issue Date: 02/27/2007 |
| NOC: RECORDED |
| Applicant name: RONALD H FOSTER |
| Owner: PALM COAST MEDICAL SPECIALISTS LTD |
|
Address 21 HOSPITAL DR STE 200 PALM COAST, FL 32164 |
| Lot: 0200 |
| Contracted Stated Job Value: ¤318,980.00 |
| Job Description: JOHN ZAK,III, M.D. BUILD-OUT SUITE 250 (MEDICAL OFFICE) |
| Type: CN |
Contractor
STELLAR GROUP INC
| Status | Location Address | State License Number | Phone |
| INACTIVE |
2900 HARTLEY ROAD JACKSONVILLE, FL 32257 |
CGC052029 (Exp: 08/31/2024) | 904-899-9214 |
Sub Contractors
RONALD A AUTREY
| Status | Location Address | State License Number | Phone |
| CANCEL |
PO Box 1799 Jacksonville, Fl., 32201 |
ECOOOO388 (Exp: 08/31/2018) | (904) 388-8000 |
ERIC TIMOTHY HOLCOMB
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
101 MUNDY MEMORIAL MT JULIET, TN 37122 |
CMC1249492 (Exp: 09/30/2008) | (800)222-1819 | (615)773-8108 |
GARY S WELBORN
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
1709 North Nova Road Holly Hill, FL 32117 |
CFC037140 (Exp: 08/31/2018) | (386) 257-1172 | (386)252-5979 |
ANTHONY JAMES PARETE
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
6900 PHILLIPS INDUSTRIAL BLVD. JACKSONVILLE, FL 32256 |
CCC044057 (Exp: 08/31/2026) | (904)880-6005 | (904)880-3377 |
WILLIAM W GAY
| Status | Location Address | State License Number | Phone | Fax |
| DECEASED |
524 STOCKTON STREET JACKSONVILLE, FL 32204 |
CMC008140 (Exp: 08/31/2020) | (904)388-2696 | 904-394-7944 |
JOHN W BARBER JR
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
1514 BERNITA STREET JACKSONVILLE, FL 32211 |
CCC057141 (Exp: 08/31/2020) | (904)744-4067 | (904)744-4209 |
Inspection History
| Type | Request Date | Result | Inspector |
| FINAL COMPLETE BUILDING INSPECTION | 04/10/2008 | FINAL APPROVED | LWOODROME |
| Note: per Larry Woodrone - 99 permit | |||
| FINAL COMPLETE BUILDING INSPECTION | 04/08/2008 | FINAL APPROVED | JLEVRAULT |
| UTILITY COMMERCIAL FINAL | 04/08/2008 | APPROVED | DSPENCER |
| FIRE FINAL | 04/04/2008 | APPROVED | JPATTEE |
| ELECTRICAL FINAL | 04/02/2008 | APPROVED | RMARVEL |
| Note: THIS IS A REINSPECTION | |||
| ELECTRICAL FINAL | 03/24/2008 | Disapproved -FEE REQUIRED | RMARVEL |
| Note: NEED REVISION WHERE RECEPTACLES ARE ADDED. | |||
| PLUMBING FINAL | 03/11/2008 | APPROVED | JGIBSON |
| H.V.A.C. FINAL | 03/11/2008 | APPROVED | JLEVRAULT |
| ABOVE CEILING | 12/17/2007 | CANCELLED BY APPLICANT | JEANNE |
| FIREWALL FINAL INSPECTION | 12/14/2007 | APPROVED | JPATTEE |
| FIREWALL INSPECTION | 12/10/2007 | Disapproved -FEE REQUIRED | JPATTEE |
| Note: Holes not caulked throughout, Spray application not heavy enough | |||
| COMMERCIAL POWER INSPECTION | 11/13/2007 | APPROVED | LHITES |
| INSULATION INSPECTION | 08/28/2007 | APPROVED | JLEVRAULT |
| FIRE SPRINKLER 2ND ROUGH HYDROSTATIC PRESSURE TEST | 08/27/2007 | APPROVED | JPATTEE |
| FIREWALL INSPECTION | 08/24/2007 | APPROVED | JPATTEE |
| Note: floor penetrations suite 250 | |||
| 2ND ROUGH ELECTRICAL | 08/24/2007 | APPROVED | RMARVEL |
| H.V.A.C. ROUGH | 08/21/2007 | APPROVED | JLEVRAULT |
| FRAMING | 08/02/2007 | APPROVED | JHINDMAN |
| SECOND ROUGH PLUMBING INSPECTION | 07/26/2007 | APPROVED - AS NOTED | JGIBSON |
| Note: CHECK WATER PRESSURE ON NEXT INSPECTION |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 03/31/2008 | 03/31/2008 |
| Note: Released By: SKNOPF Approved for Release. Revision - Medical Records room 2512 telephone added - Waiting room 2500 telephone and receptacle added - Updated RTU load in panel | |||
| BLD | COMPLETE | 03/27/2008 | 03/27/2008 |
| Note: Released By: FREODICA Revision: paper towel dispensers dishwasher connection installed for future use corner guards have been deleted from suite flooring medical records has been changed to VCT flooring in IT/Data closet has been changed to VCT | |||
| ELEC | COMPLETE | 03/20/2008 | 03/20/2008 |
| Note: Released By: SKNOPF Approved for Release. Revision: Various electrical changes (see electrical comments 3-14-2008). Released by L.W. | |||
| ELEC | HOLD | 03/11/2008 | 03/14/2008 |
| Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Revision to Permit #2006120170 (Suite 250 John Zak @ 21 Hospital Dr) 3/13/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. E001-250: a. Please verify the nameplate load for the refrigerator circuit 21. b. Circuit 38 RTU-2-4-A shows a load of 10.7KVA in the panel schedule. Sheet M001-250 shows a running total load of 37.1A yielding 13.36KVA. Please review and revise. c. Please verify nameplate loads for CU-2-4-A & AHU-2-4-A. Mechanical Schedule does not provide enough electrical data for load calculation verification. d. Revise Load Calculation to conform to NEC 220 standards including actual lighting, receptacle, equipment, HVAC and largest motor loads. 2. E001-250 & E102-250 - Panel schedule shows circuit 23 as receptacle for copier and fax. Circuit 23 does not appear on floor plan E102-250. Please review and revise. 3. E102-250: a. Circuit 15 shows duplex receptacles for a copier, a fax, and (3) convenience receptacles. Please identify the nameplate loads of the copier and fax to verify the actual circuit load. b. Room 2523 Breakroom is showing a Dishwasher with no circuit identified on the floor plan. Panel schedule shows circuit 31 as a dishwasher, but does not show the nameplate load. Add circuit identification to floor plan for this equipment, and add nameplate load to panel schedule. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us | |||
| FI1 | COMPLETE | 01/24/2007 | 02/16/2007 |
| Note: Released By: JPATTEE 1. Sent one (1) set of drawings to FD on 1/16/07. 2. Sent one (1) set of revised drawings on 1/24/07. | |||
| BLD | COMPLETE | 01/16/2007 | 02/23/2007 |
| Note: Released By: LWOODROME | |||
| BLD | HOLD | 12/14/2006 | 01/11/2007 |
| Note: Held By: FREODICA CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application No. 2006120170 - John Zak lll, MD - Suite250 1. Dwg. No. M001-250: a. Clarify name designation of AHU-1-7-A/CU-1-7-A listed on A/C Split System Equipment Schedule as those names can not be found anywhere on the drawings. 2. Dwg. No. M101-250: a. AHU-2-4-A was not listed on Equipment Schedule. See comment 1a. b. Provide duct size on VAV-2-4-A1. 3. Dwg. No. M401-250: a. Show CU-2-4-A and its refrigerant lines. b. Show RTU-2-4-A in solid lines and show equipments for Suite 140 in dashed lines as Reference Only, for clarity. 4. Dwg. No. P-101-250: a. Provide reference information on RTU's condensate line tied to existing system. b. Provide Name Designation of AHU, indicate size of condensate drain, and where it is discharged. 5. Dwg. No. E-102-250: a. Clarify whether individual exhaust fan will be used for each toilet as shown on plan or only one (1) exhaust fan for all toilets as shown on mechanical. Revise drawing accordingly. | |||
| DSD | COMPLETE | 01/30/2007 | |
| Note: Released By: DCHAUDOIN | |||
| UD1 | COMPLETE | 01/25/2007 | |
| Note: Released By: CJOHNSON |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADDITIONAL FEE | ¤40.00 | 04/04/2008 |
| ADDITIONAL FEE | ¤40.00 | 04/04/2008 |
| REINSPECTION FEE | ¤40.00 | 04/04/2008 |
| REINSPECTION FEE | ¤40.00 | 04/04/2008 |
| RENEW PERMIT FEES | ¤40.00 | 04/04/2008 |
| REVISION | ¤40.00 | 04/04/2008 |
| REVISION | ¤40.00 | 04/04/2008 |
| REVISION | ¤40.00 | 04/04/2008 |
| ADMIN FEE | ¤20.00 | 02/27/2007 |
| ELECTRIC FEE | ¤221.39 | 02/27/2007 |
| FIRE PLANS REVIEW | ¤25.87 | 02/27/2007 |
| MECHANICAL FEE | ¤221.39 | 02/27/2007 |
| PERMIT FEE | ¤2,232.86 | 02/27/2007 |
| PLAN CHECK FEE | ¤366.83 | 02/27/2007 |
| PLUMBING FEE | ¤221.39 | 02/27/2007 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤3,629.73 |