Permit #2006120179

Permit Details

Status: COED

Parcel Id: 06-12-31-5815-00000-0200
Total Square Footage: 2841 sqft
Block: 00000
Subdivision: 2118 - Town Center Phase I
Job Phone: (904)260-2900
Location Address: 21 HOSPITAL DR
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 02/27/2007
NOC: RECORDED
Applicant name: RONALD H FOSTER
Owner: PALM COAST MEDICAL SPECIALISTS LTD

Address

21 HOSPITAL DR STE 200

PALM COAST, FL 32164

Lot: 0200
Contracted Stated Job Value: ¤294,985.00
Job Description: PALM COAST WOMEN'S CENTER BUILD-OUT SUITE 270
Type: CN

Contractor

STELLAR GROUP INC
Status Location Address State License Number Phone
INACTIVE

2900 HARTLEY ROAD

JACKSONVILLE, FL 32257

CGC052029 (Exp: 08/31/2024) 904-899-9214

Sub Contractors

RONALD A AUTREY
Status Location Address State License Number Phone
CANCEL

PO Box 1799

Jacksonville, Fl., 32201

ECOOOO388 (Exp: 08/31/2018) (904) 388-8000
ERIC TIMOTHY HOLCOMB
Status Location Address State License Number Phone Fax
CANCEL

101 MUNDY MEMORIAL

MT JULIET, TN 37122

CMC1249492 (Exp: 09/30/2008) (800)222-1819 (615)773-8108
GARY S WELBORN
Status Location Address State License Number Phone Fax
CANCEL

1709 North Nova Road

Holly Hill, FL 32117

CFC037140 (Exp: 08/31/2018) (386) 257-1172 (386)252-5979
ANTHONY JAMES PARETE
Status Location Address State License Number Phone Fax
INACTIVE

6900 PHILLIPS INDUSTRIAL BLVD.

JACKSONVILLE, FL 32256

CCC044057 (Exp: 08/31/2026) (904)880-6005 (904)880-3377
JOHN W BARBER JR
Status Location Address State License Number Phone Fax
INACTIVE

1514 BERNITA STREET

JACKSONVILLE, FL 32211

CCC057141 (Exp: 08/31/2020) (904)744-4067 (904)744-4209
WILLIAM W GAY
Status Location Address State License Number Phone Fax
DECEASED

524 STOCKTON STREET

JACKSONVILLE, FL 32204

CMC008140 (Exp: 08/31/2020) (904)388-2696 904-394-7944

Inspection History

Type Request Date Result Inspector
FINAL COMPLETE BUILDING INSPECTION 04/09/2008 FINAL APPROVED JLEVRAULT
FIRE FINAL 04/08/2008 APPROVED JPATTEE
Note: requested by contractor
ELECTRICAL FINAL 04/02/2008 APPROVED RMARVEL
Note: THIS IS A REINSPECTION
ELECTRICAL FINAL 03/24/2008 Disapproved -FEE REQUIRED RMARVEL
Note: need to get revision where receptacles were added.
PLUMBING FINAL 03/19/2008 FINAL APPROVED PGALLMANN
H.V.A.C. FINAL 03/18/2008 APPROVED JLEVRAULT
ABOVE CEILING 01/07/2008 APPROVED JLEVRAULT
ABOVE CEILING 12/17/2007 PARTIALLY APPROVED JLEVRAULT
Note: RECEPTION AREA.
FRAMING 12/14/2007 PARTIALLY APPROVED JHINDMAN
Note: HARD CEILING FRAMING
2ND ROUGH ELECTRICAL 12/14/2007 APPROVED RMARVEL
FIREWALL FINAL INSPECTION 12/14/2007 APPROVED JPATTEE
FIREWALL INSPECTION 12/10/2007 Disapproved -FEE REQUIRED JPATTEE
Note: penetrations not sealed, spray application not heavy enough
COMMERCIAL POWER INSPECTION 12/07/2007 APPROVED JHINDMAN
INSULATION INSPECTION 10/02/2007 APPROVED JHINDMAN
FIREWALL INSPECTION 10/02/2007 APPROVED - AS NOTED JPATTEE
Note: Floor penetrations
SECOND ROUGH PLUMBING INSPECTION 09/27/2007 APPROVED - AS NOTED JGIBSON
Note: THIS IS A REINSPECTION CLEANOUTS NEED TO BE RAISED TO MIN 12``
SECOND ROUGH PLUMBING INSPECTION 09/25/2007 Disapproved -FEE REQUIRED PGALLMANN
Note: 1) WATER HAMMER ARRESTERS APPEAR TO BE SIGNIFICANTLY UNDERSIZED. PROVIDE AN APPROVED SPECIFICATION FROM THE MECHANICAL ENGINEER. 2) BAR HANGERS ARE IN THE WAY OF A FEW WALL CLEANOUTS @ LAVATORYS AND/OR EXAM SINKS. 3) FERNCO COUPLING IS BEING USED ON BREAK ROOM SINK VENT IN LIEU OF A COUPLING WITH A FULL METAL JACKET. 4) BACKING IS MISSING @ MOP SINK FAUCET. 5) DOUBLE/LOCK NUTS ARE MISSING FROM WATER HEATER PLATFORM. 6) NOTE: PER CODE, A VACUUM RELIEF VALVE IS NEEDED FOR THE ELEVATED WATER HEATER.
H.V.A.C. ROUGH 09/24/2007 PARTIALLY APPROVED JMCGOWEN
Note: main trunk lines OK
2ND ROUGH ELECTRICAL 09/21/2007 APPROVED LHITES
Note: WALLS ONLY
FRAMING 08/22/2007 APPROVED - AS NOTED JHINDMAN
Note: PARTIAL FRAMING

Review History

Department Status Date In Date Out
ELEC COMPLETE 03/31/2008 03/31/2008
Note: Released By: SKNOPF Approved for Release. Revision - Rm 2708 duplex receptacle added. - Some circuit loads updated in panel schedule
BLD COMPLETE 03/27/2008 03/27/2008
Note: Released By: FREODICA Revisions; paper towel dispensers bulkhead constructed on corridor side in lieu of full soffit
ELEC COMPLETE 03/20/2008 03/20/2008
Note: Released By: SKNOPF Approved for release. Revision: Various electrical changes (see electrical comments 3-13-2008). Released by L.W.
ELEC HOLD 03/11/2008 03/13/2008
Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Revision to Permit #2006120179 (Suite 270 Palm Coast Women's Center @ 21 Hospital Dr) 3/13/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. E001-270: a. The following equipment requires its nameplate load shown for load calculations in the Panel Schedule: Bone Density (circuit 21), EQ (circuit 23), Autoclave (circuit 27), (2) Refrigerators (circuits 29 & 31), Copier (circuit 35), and Microwave (circuit 14). Please review and revise. b. Please identify name plate loads in panel schedule for CU-2-7-A and AHU-2-7-A for load calculation verification. Mechanical Schedule is incomplete for electrical data. c. The following circuits have undersized loads in the panel: circuits 3,4,7,10 & 11. Please review and revise. d. Revise Load Calculations to conform to NEC 220 standards including actual lighting, receptacle, equipment, HVAC and largest motor. It appears that the demand calculation may be greater than the panel size shown. Please provide details on calculation. 2. E101-270: a. Circuit 6 has (22) type 'C/CE', (4) type 'K', (5) type 'E' fixtures and (1) receptacle @ Dictation for a total of 2678VA on this circuit. This exceeds the maximum load allowed for a 20A lighting circuit (1920VA) per NEC 210.19(A)(1). Please review and revise. 3. E101-270 & E102-270: a. Most recent plan on file sheet A101-270 dated 1-5-2007 shows Toilet room 2725. These 2 electrical revision sheets do not show correct walls, switching, GFI requirements, etc. Please review and revise. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us
FI1 HOLD 01/24/2007 03/16/2007
Note: Held By: JPATTEE 1. Sent one(1) set of drawings to FD on 1/16/07. 2. Sent one(2) set of revised drawings to FD on 1/24/27.
BLD COMPLETE 01/16/2007 02/23/2007
Note: Released By: LWOODROME
BLD HOLD 12/14/2006 01/12/2007
Note: Held By: FREODICA CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application No. 2006120179 - Palm Coast Women's Center - Suite270: 1. Dwg. No. A501-270: a. Provide dimension on the pull side of door for HDCP Toilet 2712. It seems barely meets the code of 18 inches minimum clearance. 2. Dwg. No. M001-270: a. Revise name tags of AHU-1-7-A/CU-1-7-A as listed on A/C Split System Equipment Schedule to match the name tags on plan. b. Revise the A/C Split System Equipment Schedule from Suite 180 to Suite 270. 3. Dwg. No. P101-270: a. Provide condensate drain and tie-in information for AHU-2-7-A. b. Provide reference information on condensate drain tie-in to existing of RTU. 4. Dwg. Nos. E102-270: a. Clarify whether individual exhaust fan will be used for each toilet/soiled utility as shown on plan or ONLY One (1) exhaust fan, EF-2-7-A on roof will be used for all toilets/soiled utility as shown on mechanical drawing. Revise drawing accordingly. 5. Dwg. No. E103-270: a. Exhaust fans, EF-2-7-A/B located on roof and their power supply were missing.
DSD COMPLETE 01/30/2007
Note: Released By: DCHAUDOIN
UD1 COMPLETE 01/25/2007
Note: Released By: CJOHNSON
FI1 COMPLETE 02/23/2007
Note: Released By: BBEMBRY per Jeff Pattee

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADDITIONAL FEE ¤40.00 04/04/2008
ADDITIONAL FEE ¤40.00 04/04/2008
REINSPECTION FEE ¤40.00 04/04/2008
REINSPECTION FEE ¤40.00 04/04/2008
REINSPECTION FEE ¤40.00 04/04/2008
RENEW PERMIT FEES ¤40.00 04/04/2008
REVISION ¤40.00 04/04/2008
REVISION ¤40.00 04/04/2008
REVISION ¤40.00 04/04/2008
ADMIN FEE ¤20.00 02/27/2007
ELECTRIC FEE ¤206.99 02/27/2007
FIRE PLANS REVIEW ¤28.41 02/27/2007
MECHANICAL FEE ¤206.99 02/27/2007
PERMIT FEE ¤2,064.90 02/27/2007
PLAN CHECK FEE ¤339.24 02/27/2007
PLUMBING FEE ¤206.99 02/27/2007
Fees Total Due: ¤0.00 Total Paid: ¤3,433.52