Permit #2006120179
Permit Details
Status: COED
| Parcel Id: 06-12-31-5815-00000-0200 |
| Total Square Footage: 2841 sqft |
| Block: 00000 |
| Subdivision: 2118 - Town Center Phase I |
| Job Phone: (904)260-2900 |
| Location Address: 21 HOSPITAL DR |
| Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION |
| Issue Date: 02/27/2007 |
| NOC: RECORDED |
| Applicant name: RONALD H FOSTER |
| Owner: PALM COAST MEDICAL SPECIALISTS LTD |
|
Address 21 HOSPITAL DR STE 200 PALM COAST, FL 32164 |
| Lot: 0200 |
| Contracted Stated Job Value: ¤294,985.00 |
| Job Description: PALM COAST WOMEN'S CENTER BUILD-OUT SUITE 270 |
| Type: CN |
Contractor
STELLAR GROUP INC
| Status | Location Address | State License Number | Phone |
| INACTIVE |
2900 HARTLEY ROAD JACKSONVILLE, FL 32257 |
CGC052029 (Exp: 08/31/2024) | 904-899-9214 |
Sub Contractors
RONALD A AUTREY
| Status | Location Address | State License Number | Phone |
| CANCEL |
PO Box 1799 Jacksonville, Fl., 32201 |
ECOOOO388 (Exp: 08/31/2018) | (904) 388-8000 |
ERIC TIMOTHY HOLCOMB
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
101 MUNDY MEMORIAL MT JULIET, TN 37122 |
CMC1249492 (Exp: 09/30/2008) | (800)222-1819 | (615)773-8108 |
GARY S WELBORN
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
1709 North Nova Road Holly Hill, FL 32117 |
CFC037140 (Exp: 08/31/2018) | (386) 257-1172 | (386)252-5979 |
ANTHONY JAMES PARETE
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
6900 PHILLIPS INDUSTRIAL BLVD. JACKSONVILLE, FL 32256 |
CCC044057 (Exp: 08/31/2026) | (904)880-6005 | (904)880-3377 |
JOHN W BARBER JR
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
1514 BERNITA STREET JACKSONVILLE, FL 32211 |
CCC057141 (Exp: 08/31/2020) | (904)744-4067 | (904)744-4209 |
WILLIAM W GAY
| Status | Location Address | State License Number | Phone | Fax |
| DECEASED |
524 STOCKTON STREET JACKSONVILLE, FL 32204 |
CMC008140 (Exp: 08/31/2020) | (904)388-2696 | 904-394-7944 |
Inspection History
| Type | Request Date | Result | Inspector |
| FINAL COMPLETE BUILDING INSPECTION | 04/09/2008 | FINAL APPROVED | JLEVRAULT |
| FIRE FINAL | 04/08/2008 | APPROVED | JPATTEE |
| Note: requested by contractor | |||
| ELECTRICAL FINAL | 04/02/2008 | APPROVED | RMARVEL |
| Note: THIS IS A REINSPECTION | |||
| ELECTRICAL FINAL | 03/24/2008 | Disapproved -FEE REQUIRED | RMARVEL |
| Note: need to get revision where receptacles were added. | |||
| PLUMBING FINAL | 03/19/2008 | FINAL APPROVED | PGALLMANN |
| H.V.A.C. FINAL | 03/18/2008 | APPROVED | JLEVRAULT |
| ABOVE CEILING | 01/07/2008 | APPROVED | JLEVRAULT |
| ABOVE CEILING | 12/17/2007 | PARTIALLY APPROVED | JLEVRAULT |
| Note: RECEPTION AREA. | |||
| FRAMING | 12/14/2007 | PARTIALLY APPROVED | JHINDMAN |
| Note: HARD CEILING FRAMING | |||
| 2ND ROUGH ELECTRICAL | 12/14/2007 | APPROVED | RMARVEL |
| FIREWALL FINAL INSPECTION | 12/14/2007 | APPROVED | JPATTEE |
| FIREWALL INSPECTION | 12/10/2007 | Disapproved -FEE REQUIRED | JPATTEE |
| Note: penetrations not sealed, spray application not heavy enough | |||
| COMMERCIAL POWER INSPECTION | 12/07/2007 | APPROVED | JHINDMAN |
| INSULATION INSPECTION | 10/02/2007 | APPROVED | JHINDMAN |
| FIREWALL INSPECTION | 10/02/2007 | APPROVED - AS NOTED | JPATTEE |
| Note: Floor penetrations | |||
| SECOND ROUGH PLUMBING INSPECTION | 09/27/2007 | APPROVED - AS NOTED | JGIBSON |
| Note: THIS IS A REINSPECTION CLEANOUTS NEED TO BE RAISED TO MIN 12`` | |||
| SECOND ROUGH PLUMBING INSPECTION | 09/25/2007 | Disapproved -FEE REQUIRED | PGALLMANN |
| Note: 1) WATER HAMMER ARRESTERS APPEAR TO BE SIGNIFICANTLY UNDERSIZED. PROVIDE AN APPROVED SPECIFICATION FROM THE MECHANICAL ENGINEER. 2) BAR HANGERS ARE IN THE WAY OF A FEW WALL CLEANOUTS @ LAVATORYS AND/OR EXAM SINKS. 3) FERNCO COUPLING IS BEING USED ON BREAK ROOM SINK VENT IN LIEU OF A COUPLING WITH A FULL METAL JACKET. 4) BACKING IS MISSING @ MOP SINK FAUCET. 5) DOUBLE/LOCK NUTS ARE MISSING FROM WATER HEATER PLATFORM. 6) NOTE: PER CODE, A VACUUM RELIEF VALVE IS NEEDED FOR THE ELEVATED WATER HEATER. | |||
| H.V.A.C. ROUGH | 09/24/2007 | PARTIALLY APPROVED | JMCGOWEN |
| Note: main trunk lines OK | |||
| 2ND ROUGH ELECTRICAL | 09/21/2007 | APPROVED | LHITES |
| Note: WALLS ONLY | |||
| FRAMING | 08/22/2007 | APPROVED - AS NOTED | JHINDMAN |
| Note: PARTIAL FRAMING |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 03/31/2008 | 03/31/2008 |
| Note: Released By: SKNOPF Approved for Release. Revision - Rm 2708 duplex receptacle added. - Some circuit loads updated in panel schedule | |||
| BLD | COMPLETE | 03/27/2008 | 03/27/2008 |
| Note: Released By: FREODICA Revisions; paper towel dispensers bulkhead constructed on corridor side in lieu of full soffit | |||
| ELEC | COMPLETE | 03/20/2008 | 03/20/2008 |
| Note: Released By: SKNOPF Approved for release. Revision: Various electrical changes (see electrical comments 3-13-2008). Released by L.W. | |||
| ELEC | HOLD | 03/11/2008 | 03/13/2008 |
| Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Revision to Permit #2006120179 (Suite 270 Palm Coast Women's Center @ 21 Hospital Dr) 3/13/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. E001-270: a. The following equipment requires its nameplate load shown for load calculations in the Panel Schedule: Bone Density (circuit 21), EQ (circuit 23), Autoclave (circuit 27), (2) Refrigerators (circuits 29 & 31), Copier (circuit 35), and Microwave (circuit 14). Please review and revise. b. Please identify name plate loads in panel schedule for CU-2-7-A and AHU-2-7-A for load calculation verification. Mechanical Schedule is incomplete for electrical data. c. The following circuits have undersized loads in the panel: circuits 3,4,7,10 & 11. Please review and revise. d. Revise Load Calculations to conform to NEC 220 standards including actual lighting, receptacle, equipment, HVAC and largest motor. It appears that the demand calculation may be greater than the panel size shown. Please provide details on calculation. 2. E101-270: a. Circuit 6 has (22) type 'C/CE', (4) type 'K', (5) type 'E' fixtures and (1) receptacle @ Dictation for a total of 2678VA on this circuit. This exceeds the maximum load allowed for a 20A lighting circuit (1920VA) per NEC 210.19(A)(1). Please review and revise. 3. E101-270 & E102-270: a. Most recent plan on file sheet A101-270 dated 1-5-2007 shows Toilet room 2725. These 2 electrical revision sheets do not show correct walls, switching, GFI requirements, etc. Please review and revise. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us | |||
| FI1 | HOLD | 01/24/2007 | 03/16/2007 |
| Note: Held By: JPATTEE 1. Sent one(1) set of drawings to FD on 1/16/07. 2. Sent one(2) set of revised drawings to FD on 1/24/27. | |||
| BLD | COMPLETE | 01/16/2007 | 02/23/2007 |
| Note: Released By: LWOODROME | |||
| BLD | HOLD | 12/14/2006 | 01/12/2007 |
| Note: Held By: FREODICA CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application No. 2006120179 - Palm Coast Women's Center - Suite270: 1. Dwg. No. A501-270: a. Provide dimension on the pull side of door for HDCP Toilet 2712. It seems barely meets the code of 18 inches minimum clearance. 2. Dwg. No. M001-270: a. Revise name tags of AHU-1-7-A/CU-1-7-A as listed on A/C Split System Equipment Schedule to match the name tags on plan. b. Revise the A/C Split System Equipment Schedule from Suite 180 to Suite 270. 3. Dwg. No. P101-270: a. Provide condensate drain and tie-in information for AHU-2-7-A. b. Provide reference information on condensate drain tie-in to existing of RTU. 4. Dwg. Nos. E102-270: a. Clarify whether individual exhaust fan will be used for each toilet/soiled utility as shown on plan or ONLY One (1) exhaust fan, EF-2-7-A on roof will be used for all toilets/soiled utility as shown on mechanical drawing. Revise drawing accordingly. 5. Dwg. No. E103-270: a. Exhaust fans, EF-2-7-A/B located on roof and their power supply were missing. | |||
| DSD | COMPLETE | 01/30/2007 | |
| Note: Released By: DCHAUDOIN | |||
| UD1 | COMPLETE | 01/25/2007 | |
| Note: Released By: CJOHNSON | |||
| FI1 | COMPLETE | 02/23/2007 | |
| Note: Released By: BBEMBRY per Jeff Pattee |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADDITIONAL FEE | ¤40.00 | 04/04/2008 |
| ADDITIONAL FEE | ¤40.00 | 04/04/2008 |
| REINSPECTION FEE | ¤40.00 | 04/04/2008 |
| REINSPECTION FEE | ¤40.00 | 04/04/2008 |
| REINSPECTION FEE | ¤40.00 | 04/04/2008 |
| RENEW PERMIT FEES | ¤40.00 | 04/04/2008 |
| REVISION | ¤40.00 | 04/04/2008 |
| REVISION | ¤40.00 | 04/04/2008 |
| REVISION | ¤40.00 | 04/04/2008 |
| ADMIN FEE | ¤20.00 | 02/27/2007 |
| ELECTRIC FEE | ¤206.99 | 02/27/2007 |
| FIRE PLANS REVIEW | ¤28.41 | 02/27/2007 |
| MECHANICAL FEE | ¤206.99 | 02/27/2007 |
| PERMIT FEE | ¤2,064.90 | 02/27/2007 |
| PLAN CHECK FEE | ¤339.24 | 02/27/2007 |
| PLUMBING FEE | ¤206.99 | 02/27/2007 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤3,433.52 |