Permit Details

Status: COED

Parcel Id: 06-12-31-5815-00000-0200
Total Square Footage: 1649 sqft
Block: 00000
Subdivision: 2118 - Town Center Phase I
Job Phone: (904)260-2900
Location Address: 21 HOSPITAL DR
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 02/27/2007
NOC: RECORDED
Applicant name: RONALD H FOSTER
Owner: PALM COAST MEDICAL SPECIALISTS LTD

Address

21 HOSPITAL DR STE 200

PALM COAST, FL 32164

Lot: 0200
Contracted Stated Job Value: ¤176,449.00
Job Description: WILLIAMS FAMILY PRACTICE BUILD-OUT SUITE 290
Type: CN

Contractor

STELLAR GROUP INC
Status Location Address State License Number Phone
INACTIVE

2900 HARTLEY ROAD

JACKSONVILLE, FL 32257

CGC052029 (Exp: 08/31/2024) 904-899-9214

Sub Contractors

RONALD A AUTREY
Status Location Address State License Number Phone
CANCEL

PO Box 1799

Jacksonville, Fl., 32201

ECOOOO388 (Exp: 08/31/2018) (904) 388-8000
ERIC TIMOTHY HOLCOMB
Status Location Address State License Number Phone Fax
CANCEL

101 MUNDY MEMORIAL

MT JULIET, TN 37122

CMC1249492 (Exp: 09/30/2008) (800)222-1819 (615)773-8108
GARY S WELBORN
Status Location Address State License Number Phone Fax
CANCEL

1709 North Nova Road

Holly Hill, FL 32117

CFC037140 (Exp: 08/31/2018) (386) 257-1172 (386)252-5979
ANTHONY JAMES PARETE
Status Location Address State License Number Phone Fax
INACTIVE

6900 PHILLIPS INDUSTRIAL BLVD.

JACKSONVILLE, FL 32256

CCC044057 (Exp: 08/31/2026) (904)880-6005 (904)880-3377
WILLIAM W GAY
Status Location Address State License Number Phone Fax
DECEASED

524 STOCKTON STREET

JACKSONVILLE, FL 32204

CMC008140 (Exp: 08/31/2020) (904)388-2696 904-394-7944
JOHN W BARBER JR
Status Location Address State License Number Phone Fax
INACTIVE

1514 BERNITA STREET

JACKSONVILLE, FL 32211

CCC057141 (Exp: 08/31/2020) (904)744-4067 (904)744-4209

Inspection History

Type Request Date Result Inspector
UTILITY COMMERCIAL FINAL 04/08/2008 APPROVED DSPENCER
FINAL COMPLETE BUILDING INSPECTION 04/08/2008 FINAL APPROVED JLEVRAULT
FIRE FINAL 04/04/2008 APPROVED JPATTEE
H.V.A.C. FINAL 04/02/2008 FINAL APPROVED JLEVRAULT
Note: THIS IS A REINSPECTION
ELECTRICAL FINAL 04/02/2008 APPROVED RMARVEL
Note: THIS IS A REINSPECTION
ELECTRICAL FINAL 03/24/2008 Disapproved -FEE REQUIRED RMARVEL
Note: NEED REVISIONS WHERE RECEPTACLES ARE ADDED
PLUMBING FINAL 03/19/2008 FINAL APPROVED PGALLMANN
Note: THIS IS A REINSPECTION
PLUMBING FINAL 03/18/2008 Disapproved - NO FEE PGALLMANN
Note: THIS IS A REINSPECTION
H.V.A.C. FINAL 03/18/2008 Disapproved -FEE REQUIRED JLEVRAULT
Note: THIS IS A REINSPECTION BATH EXHAUST NOT OPERATING.
H.V.A.C. FINAL 03/14/2008 Disapproved -FEE REQUIRED JLEVRAULT
Note: BATH EXHAUST FANS NOT OPERATING.
PLUMBING FINAL 03/14/2008 Disapproved - NO FEE PGALLMANN
Note: 1) NO HOT WATER. 2) NON ADA WATER CLOSET NOT GROUTED IN.
ABOVE CEILING 01/02/2008 PARTIALLY APPROVED RMARVEL
Note: LOBBY AREA AT FRONT ENTRANCE.
FIREWALL FINAL INSPECTION 12/14/2007 APPROVED JPATTEE
FIREWALL INSPECTION 12/10/2007 Disapproved -FEE REQUIRED JPATTEE
Note: penetrations not sealed, spray application not heavy enough
COMMERCIAL POWER INSPECTION 12/07/2007 APPROVED JHINDMAN
INSULATION INSPECTION 10/16/2007 APPROVED JHINDMAN
2ND ROUGH ELECTRICAL 10/04/2007 APPROVED LHITES
Note: WALLS ONLY
FIREWALL INSPECTION 09/21/2007 APPROVED - AS NOTED JPATTEE
Note: floor penetrations
SECOND ROUGH PLUMBING INSPECTION 09/10/2007 APPROVED JGIBSON
H.V.A.C. ROUGH 09/04/2007 APPROVED JMCGOWEN
FRAMING 08/22/2007 APPROVED JHINDMAN

Review History

Department Status Date In Date Out
ELEC COMPLETE 03/31/2008 03/31/2008
Note: Released By: SKNOPF Approved for Release. Revision - Added duplex receptacle room 2900 - telephone removed rooms 2907, 2912, 2913 - revised telephone room 2908 - Fire Alarm strobe added room 2915 - Fire Alarm strobe removed room 2901
ELEC COMPLETE 03/20/2008 03/20/2008
Note: Released By: SKNOPF Approved for Release. Revision: Various electrical changes (see electrical comments 3-19-2008). Released by L.W.
ELEC HOLD 03/18/2008 03/19/2008
Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Revision to Permit #2006120184 (Suite 290 Williams Family Practice @ 21 Hospital Dr) 3/19/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. E001-290: a. Provide circuit breaker size for circuit 25. b. Circuit 39,41 Water Heater is listed in panel as 12KW with a 70A circuit breaker. Plumbing schedule lists this equipment as 6KW. Please revise load and circuit breaker size. c. Provide actual nameplate load for copier (15), and refrigerator (17) for load calculation verification. d. Provide revised Demand Load Calculation which conforms to NEC 220 using actual lighting, receptacle, equipment, HVAC and largest motor loads. 2. E101-290 - Identify circuit for Corridor 2915/2905 fluorescent 2'x4' lighting. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us
FI1 COMPLETE 01/24/2007 02/16/2007
Note: Released By: JPATTEE 1. Sent one (1) set of drawings to FD on 1/16/07. 2. Sent one (1) set of revised drawings on 2/24/07.
BLD COMPLETE 01/16/2007 02/23/2007
Note: Released By: LWOODROME
BLD HOLD 12/14/2006 01/16/2007
Note: Held By: FREODICA CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application No. 2006120184 - Williams Family Practice - Suite 290: 1. Dwg. No. P801-290: a. Sanitary riser for toilet 2906 did not matched with plan layout. 2. Dwg. No. E102-290: a. Coordinate toilet exhaust fan location with mechanical.
DSD COMPLETE 01/30/2007
Note: Released By: DCHAUDOIN
UD1 COMPLETE 01/25/2007
Note: Released By: CJOHNSON
BLD COMPLETE 03/27/2008
Note: Released By: JJOSEPH Revision: paper towel dispenser flooring changed in reception area room 2901 1/2 cabinet door removed from corridor 2915 to reception area sheet E102-290 shows a receptacle above exam table. outlets listed at above exam table to be elevated

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADDITIONAL FEE ¤40.00 04/04/2008
ADDITIONAL FEE ¤40.00 04/04/2008
REINSPECTION FEE ¤40.00 04/04/2008
REINSPECTION FEE ¤40.00 04/04/2008
REINSPECTION FEE ¤40.00 04/04/2008
REINSPECTION FEE ¤40.00 04/04/2008
RENEW PERMIT FEES ¤40.00 04/04/2008
REVISION ¤40.00 04/04/2008
REVISION ¤40.00 04/04/2008
REVISION ¤40.00 04/04/2008
ADMIN FEE ¤20.00 02/27/2007
ELECTRIC FEE ¤135.87 02/27/2007
FIRE PLANS REVIEW ¤25.00 02/27/2007
MECHANICAL FEE ¤135.87 02/27/2007
PERMIT FEE ¤1,235.14 02/27/2007
PLAN CHECK FEE ¤202.92 02/27/2007
PLUMBING FEE ¤135.87 02/27/2007
Fees Total Due: ¤0.00 Total Paid: ¤2,290.67