I want to search for...
Permit #2006120184
Permit Details
Status: COED
| Parcel Id: 06-12-31-5815-00000-0200 |
| Total Square Footage: 1649 sqft |
| Block: 00000 |
| Subdivision: 2118 - Town Center Phase I |
| Job Phone: (904)260-2900 |
| Location Address: 21 HOSPITAL DR |
| Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION |
| Issue Date: 02/27/2007 |
| NOC: RECORDED |
| Applicant name: RONALD H FOSTER |
| Owner: PALM COAST MEDICAL SPECIALISTS LTD |
|
Address 21 HOSPITAL DR STE 200 PALM COAST, FL 32164 |
| Lot: 0200 |
| Contracted Stated Job Value: ¤176,449.00 |
| Job Description: WILLIAMS FAMILY PRACTICE BUILD-OUT SUITE 290 |
| Type: CN |
Contractor
STELLAR GROUP INC
| Status | Location Address | State License Number | Phone |
| INACTIVE |
2900 HARTLEY ROAD JACKSONVILLE, FL 32257 |
CGC052029 (Exp: 08/31/2024) | 904-899-9214 |
Sub Contractors
RONALD A AUTREY
| Status | Location Address | State License Number | Phone |
| CANCEL |
PO Box 1799 Jacksonville, Fl., 32201 |
ECOOOO388 (Exp: 08/31/2018) | (904) 388-8000 |
ERIC TIMOTHY HOLCOMB
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
101 MUNDY MEMORIAL MT JULIET, TN 37122 |
CMC1249492 (Exp: 09/30/2008) | (800)222-1819 | (615)773-8108 |
GARY S WELBORN
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
1709 North Nova Road Holly Hill, FL 32117 |
CFC037140 (Exp: 08/31/2018) | (386) 257-1172 | (386)252-5979 |
ANTHONY JAMES PARETE
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
6900 PHILLIPS INDUSTRIAL BLVD. JACKSONVILLE, FL 32256 |
CCC044057 (Exp: 08/31/2026) | (904)880-6005 | (904)880-3377 |
WILLIAM W GAY
| Status | Location Address | State License Number | Phone | Fax |
| DECEASED |
524 STOCKTON STREET JACKSONVILLE, FL 32204 |
CMC008140 (Exp: 08/31/2020) | (904)388-2696 | 904-394-7944 |
JOHN W BARBER JR
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
1514 BERNITA STREET JACKSONVILLE, FL 32211 |
CCC057141 (Exp: 08/31/2020) | (904)744-4067 | (904)744-4209 |
Inspection History
| Type | Request Date | Result | Inspector |
| UTILITY COMMERCIAL FINAL | 04/08/2008 | APPROVED | DSPENCER |
| FINAL COMPLETE BUILDING INSPECTION | 04/08/2008 | FINAL APPROVED | JLEVRAULT |
| FIRE FINAL | 04/04/2008 | APPROVED | JPATTEE |
| H.V.A.C. FINAL | 04/02/2008 | FINAL APPROVED | JLEVRAULT |
| Note: THIS IS A REINSPECTION | |||
| ELECTRICAL FINAL | 04/02/2008 | APPROVED | RMARVEL |
| Note: THIS IS A REINSPECTION | |||
| ELECTRICAL FINAL | 03/24/2008 | Disapproved -FEE REQUIRED | RMARVEL |
| Note: NEED REVISIONS WHERE RECEPTACLES ARE ADDED | |||
| PLUMBING FINAL | 03/19/2008 | FINAL APPROVED | PGALLMANN |
| Note: THIS IS A REINSPECTION | |||
| PLUMBING FINAL | 03/18/2008 | Disapproved - NO FEE | PGALLMANN |
| Note: THIS IS A REINSPECTION | |||
| H.V.A.C. FINAL | 03/18/2008 | Disapproved -FEE REQUIRED | JLEVRAULT |
| Note: THIS IS A REINSPECTION BATH EXHAUST NOT OPERATING. | |||
| H.V.A.C. FINAL | 03/14/2008 | Disapproved -FEE REQUIRED | JLEVRAULT |
| Note: BATH EXHAUST FANS NOT OPERATING. | |||
| PLUMBING FINAL | 03/14/2008 | Disapproved - NO FEE | PGALLMANN |
| Note: 1) NO HOT WATER. 2) NON ADA WATER CLOSET NOT GROUTED IN. | |||
| ABOVE CEILING | 01/02/2008 | PARTIALLY APPROVED | RMARVEL |
| Note: LOBBY AREA AT FRONT ENTRANCE. | |||
| FIREWALL FINAL INSPECTION | 12/14/2007 | APPROVED | JPATTEE |
| FIREWALL INSPECTION | 12/10/2007 | Disapproved -FEE REQUIRED | JPATTEE |
| Note: penetrations not sealed, spray application not heavy enough | |||
| COMMERCIAL POWER INSPECTION | 12/07/2007 | APPROVED | JHINDMAN |
| INSULATION INSPECTION | 10/16/2007 | APPROVED | JHINDMAN |
| 2ND ROUGH ELECTRICAL | 10/04/2007 | APPROVED | LHITES |
| Note: WALLS ONLY | |||
| FIREWALL INSPECTION | 09/21/2007 | APPROVED - AS NOTED | JPATTEE |
| Note: floor penetrations | |||
| SECOND ROUGH PLUMBING INSPECTION | 09/10/2007 | APPROVED | JGIBSON |
| H.V.A.C. ROUGH | 09/04/2007 | APPROVED | JMCGOWEN |
| FRAMING | 08/22/2007 | APPROVED | JHINDMAN |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 03/31/2008 | 03/31/2008 |
| Note: Released By: SKNOPF Approved for Release. Revision - Added duplex receptacle room 2900 - telephone removed rooms 2907, 2912, 2913 - revised telephone room 2908 - Fire Alarm strobe added room 2915 - Fire Alarm strobe removed room 2901 | |||
| ELEC | COMPLETE | 03/20/2008 | 03/20/2008 |
| Note: Released By: SKNOPF Approved for Release. Revision: Various electrical changes (see electrical comments 3-19-2008). Released by L.W. | |||
| ELEC | HOLD | 03/18/2008 | 03/19/2008 |
| Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Revision to Permit #2006120184 (Suite 290 Williams Family Practice @ 21 Hospital Dr) 3/19/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. E001-290: a. Provide circuit breaker size for circuit 25. b. Circuit 39,41 Water Heater is listed in panel as 12KW with a 70A circuit breaker. Plumbing schedule lists this equipment as 6KW. Please revise load and circuit breaker size. c. Provide actual nameplate load for copier (15), and refrigerator (17) for load calculation verification. d. Provide revised Demand Load Calculation which conforms to NEC 220 using actual lighting, receptacle, equipment, HVAC and largest motor loads. 2. E101-290 - Identify circuit for Corridor 2915/2905 fluorescent 2'x4' lighting. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us | |||
| FI1 | COMPLETE | 01/24/2007 | 02/16/2007 |
| Note: Released By: JPATTEE 1. Sent one (1) set of drawings to FD on 1/16/07. 2. Sent one (1) set of revised drawings on 2/24/07. | |||
| BLD | COMPLETE | 01/16/2007 | 02/23/2007 |
| Note: Released By: LWOODROME | |||
| BLD | HOLD | 12/14/2006 | 01/16/2007 |
| Note: Held By: FREODICA CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application No. 2006120184 - Williams Family Practice - Suite 290: 1. Dwg. No. P801-290: a. Sanitary riser for toilet 2906 did not matched with plan layout. 2. Dwg. No. E102-290: a. Coordinate toilet exhaust fan location with mechanical. | |||
| DSD | COMPLETE | 01/30/2007 | |
| Note: Released By: DCHAUDOIN | |||
| UD1 | COMPLETE | 01/25/2007 | |
| Note: Released By: CJOHNSON | |||
| BLD | COMPLETE | 03/27/2008 | |
| Note: Released By: JJOSEPH Revision: paper towel dispenser flooring changed in reception area room 2901 1/2 cabinet door removed from corridor 2915 to reception area sheet E102-290 shows a receptacle above exam table. outlets listed at above exam table to be elevated |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADDITIONAL FEE | ¤40.00 | 04/04/2008 |
| ADDITIONAL FEE | ¤40.00 | 04/04/2008 |
| REINSPECTION FEE | ¤40.00 | 04/04/2008 |
| REINSPECTION FEE | ¤40.00 | 04/04/2008 |
| REINSPECTION FEE | ¤40.00 | 04/04/2008 |
| REINSPECTION FEE | ¤40.00 | 04/04/2008 |
| RENEW PERMIT FEES | ¤40.00 | 04/04/2008 |
| REVISION | ¤40.00 | 04/04/2008 |
| REVISION | ¤40.00 | 04/04/2008 |
| REVISION | ¤40.00 | 04/04/2008 |
| ADMIN FEE | ¤20.00 | 02/27/2007 |
| ELECTRIC FEE | ¤135.87 | 02/27/2007 |
| FIRE PLANS REVIEW | ¤25.00 | 02/27/2007 |
| MECHANICAL FEE | ¤135.87 | 02/27/2007 |
| PERMIT FEE | ¤1,235.14 | 02/27/2007 |
| PLAN CHECK FEE | ¤202.92 | 02/27/2007 |
| PLUMBING FEE | ¤135.87 | 02/27/2007 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤2,290.67 |