Permit #2007040059
Permit Details
Status: COED
| Parcel Id: 07-11-31-7025-000G0-0190 |
| COMMERCIAL SQUARE FOOTAGE: 4200 sqft |
| Total Square Footage: 4200 sqft |
| Block: 000G0 |
| Subdivision: 1228 - SOUTHWEST QUADRANT |
| Job Phone: (386) 445-5239 |
| Location Address: 1000 PALM COAST PKWY SW |
| Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION |
| Issue Date: 06/05/2007 |
| NOC: RECORDED |
| Applicant name: KEITH M PARKER |
| Owner: PALM COAST PROPERTIES LLC & |
|
Address GERALD C NIELSEN & CA BRADENTON, FL 34210 |
|
Address 3639 CORTEZ RD W STE. 220 BRADENTON, FL 34210 |
| Lot: 0190 |
| Contracted Stated Job Value: ¤48,000.00 |
| Job Description: SUITES 101-104-- INTERIOR BUILDOUT FOR STRATHMORE BAGELS & DELI |
| Type: CN |
Contractor
DILLARD CONSTRUCTION LLC.
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
PO BOX 355007 PALM COAST, FL 32137 |
CGC1510399 (Exp: 09/30/2010) | 386-864-1320 | (386)986-3054 |
Sub Contractors
BRIAN ALLEN MOLL
| Status | Location Address | Mailing Address | State License Number | Phone |
| ACTIVE |
1 ENTERPRISE DRIVE BUNNELL, FL 32110 |
SUITE 8 BUNNELL, FL 32110 |
CAC1815106 (Exp: 08/31/2026) | 386-447-3782 |
ISAAC WALTER JOHNSTON
| Status | Location Address | State License Number | Phone |
| ACTIVE |
887 BRENTWOOD DRIVE Daytona Beach, FL 32117 |
CFC023634 (Exp: 08/31/2026) | (386) 252-7047 |
DAVID CASH
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
605 S. STATE STREET BUNNELL, FL 32110 |
01613 (Exp: 08/31/2008) | (386)437-3433 | (904)829-1844 |
KENNETH HOLMES
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
4904 GREENLAND HIDEAWAY DR N JAX , FL 32258 |
EC0001799 (Exp: 08/31/2010) | (904)619-4525 | (904)619-4525 |
Inspection History
| Type | Request Date | Result | Inspector |
| FINAL COMPLETE BUILDING INSPECTION | 10/17/2007 | FINAL APPROVED | JLEVRAULT |
| FIRE FINAL | 10/16/2007 | APPROVED | JPATTEE |
| Note: THIS IS A REINSPECTION | |||
| UTILITY COMMERCIAL FINAL | 10/16/2007 | APPROVED | KKING |
| Note: THIS IS A REINSPECTION | |||
| FIRE FINAL | 10/15/2007 | CANCELLED BY APPLICANT | JPATTEE |
| ABOVE CEILING | 10/08/2007 | APPROVED | JLEVRAULT |
| H.V.A.C. ROUGH | 10/08/2007 | CANCELLED BY APPLICANT | AIRS WEB |
| 2ND ROUGH ELECTRICAL | 10/08/2007 | CANCELLED BY APPLICANT | AIRS WEB |
| H.V.A.C. ROUGH | 10/01/2007 | APPROVED | JMCGOWEN |
| 2ND ROUGH ELECTRICAL | 10/01/2007 | APPROVED | LHITES |
| Note: THIS WAS APPROVED BY ROBERT MARVEL | |||
| UTILITY COMMERCIAL FINAL | 09/20/2007 | Disapproved - NO FEE | KKING |
| Note: The plumbing system needs to be finished and the utility scheduled to dye test the system to verify the grease lines are going to the out side interseptor. | |||
| UTILITY COMPANY FINAL | 09/20/2007 | APPROVED | TSCHWEERS |
| ABOVE CEILING | 09/18/2007 | Disapproved - NO FEE | JLEVRAULT |
| Note: INSPECTION CANCELLED BY CONTRACTOR | |||
| ABOVE CEILING | 09/18/2007 | PARTIALLY APPROVED | JLEVRAULT |
| Note: THIS IS A REINSPECTION FRONT HALF IS APPROVED WITH THE EXCEPTION OF A FEW SMALL AREAS THAT NEED TO HAVE SPRAY ON FIRE PROOFING REAPPLYED TO STEEL. CEILING TILES WILL BE LEFT OUT FOR INSPECTION OF THESE AREAS ON NEXT INSPECTION. | |||
| 2ND ROUGH ELECTRICAL | 09/14/2007 | PARTIALLY APPROVED | LHITES |
| Note: CHECK DISCONNECT AT NEXT INSPECTION. AREA INSPECTED IS HIGHLITED ON PLANS | |||
| GAS ROUGH | 08/24/2007 | APPROVED | JGIBSON |
| Note: THIS IS A REINSPECTION | |||
| H.V.A.C. ROUGH | 08/23/2007 | APPROVED - AS NOTED | JLEVRAULT |
| Note: THREE BATHROOMS AND OFFICE WITH HARD CEILINGS ONLY. | |||
| GAS ROUGH | 08/13/2007 | Disapproved -FEE REQUIRED | JGIBSON |
| Note: RELIEF VENT FOR WATER HEATER NEEDS TO HAVE 5' CLERENCE FROM IGNITION SOURCE {MIN} MISSING BOND WIRE @ GAS CONNECTION 2 INDEPENDENT GAS LINES FEEDING SEPERATE AREAS OF KITCHEN, NEED TO SUBMIT GAS RISER DIAGRAM TO PLAN REVIEW FOR APPROVAL BEFORE GAS ROUGH CAN BE GIVEN. | |||
| FRAMING | 07/23/2007 | APPROVED | JLEVRAULT |
| Note: per request of Larry W | |||
| MONOLITHIC SLAB INSPECTION/SLAB | 07/20/2007 | APPROVED | PPROVIDER |
| Note: Letter from R> Johnson eng. Re: slab inspectiion | |||
| SECOND ROUGH PLUMBING INSPECTION | 07/19/2007 | APPROVED | PGALLMANN |
| Note: Keith from Dillard called to schedule this inspection for 7/19/07 | |||
| FIRST ROUGH PLUMBING INSPECTION | 06/22/2007 | APPROVED | PGALLMANN |
| DEMOLITION INSPECTION | 06/13/2007 | Disapproved -FEE REQUIRED | JLEVRAULT |
| Note: PROVIDE REVISION FOR SIX FOOT PARTY WALL LEFT ABOVE CEILING. this is for an other permit that was issued for this same job site. J.R.M. |
Review History
| Department | Status | Date In | Date Out |
| BLD | COMPLETE | 10/01/2007 | 10/04/2007 |
| Note: Released By: FREODICA Rev.- revised HVAC & electrical dwgs.-as built. | |||
| BLD | COMPLETE | 08/14/2007 | 08/17/2007 |
| Note: Released By: CCOTE Approved for Release. Review by Fred R. REVISION: Add gas riser. | |||
| BLD | COMPLETE | 07/19/2007 | 07/20/2007 |
| Note: Released By: FREODICA Released per LW. | |||
| BLD | HOLD | 05/22/2007 | 05/24/2007 |
| Note: Held By: CCOTE CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application No. 2007040059 (1000 Palm Coast Pkwy SW) 5/24/07 The following items must be resolved in order to complete the Building Permit plan review. Previous items that were addressed and completed that need no further action have been removed. Comments made to previous items that need to be addressed are shown as Bold Italic. 16. Provide additional emergency egress illumination for the restroom corridor and the food service area. 18. Provide a minimum of a heat capture hood at the rack oven #15. 19. Indicate location(s) of exhaust(s) and make-up air intakes for existing and new exhaust hood(s), restroom exhaust ducts and fresh air intakes. 21. Provide outside air for HVAC units. 22. Provide installation detail(s) for air handler(s) which are suspended and which are installed above the restrooms and office. 23. Indicate a primary method of condensate disposal and provide an auxiliary pan with a secondary drain or a float switch. 24. Provide energy calculations. The forms submitted are for residential structures. Submit commercial forms. ------------------------------------------------------------ Carl L. Cote, R.A. Senior Plans Examiner City of Palm Coast - Building Department 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-4753 [fax]: (386) 986-3781 [email]: ccote@ci.palm-coast.fl.us ------------------------------------------------------------ | |||
| UD1 | COMPLETE | 04/20/2007 | 04/20/2007 |
| Note: Released By: CJOHNSON | |||
| FI1 | COMPLETE | 04/10/2007 | 04/23/2007 |
| Note: Released By: JPATTEE Fire sprinkler alteration to be done by licensed FS contractor. Hood, duct and fire suppression system will require separate permitting | |||
| UD1 | HOLD | 04/10/2007 | 04/12/2007 |
| Note: Held By: CJOHNSON Provide a plumbing plan. Additional capacity fees will need to be paid prior to the issuance of the CO | |||
| BLD | HOLD | 04/04/2007 | 04/10/2007 |
| Note: Held By: LWOODROME PLAN REVIEW COMMENTS: " Clarify the use of the small space, which is located at the left front of the building and is entered from the exterior. " Clarify whether the door marked "Fire Exit" is, existing or new construction. If it is new construction, provide structural details of the rough opening, in the exterior wall. " Provide threshold detail(s) per the Florida Building Code, section 11-4.13.8. " Specify door hardware, which complies with FBC, section 11-4.13.9 for H.C. accessibility. " Provide a minimum of 12" maneuvering space, on the push side of the door marked as "out". " Provide maneuvering space in front of the "Men's" restroom door per FBC. Figure 11-25, as applicable. " Provide, at least minimum width H.C. accessible route, at the entrance to the corridor, in front of the restrooms. " Provide H.C. accessibility at the P.O.S. cash register counter, per FBC, section 11-7.2, as applicable. " Revise calculation of required H.C. accessible seating, (88)(5%)= 4.4, this figure must be rounded up to 5 required H.C. accessible seating positions. Also, revise layout of H.C. accessible seating positions to comply with FBC, section 11-5.1 for seat distribution throughout the space or facility. " Indicate location(s) of existing and/or new electrical panels. " Provide electrical load calculations to verify that existing service(s) are adequate for any added electrical loads or indicate any up-grades to be made to the existing service(s). " Provide an electrical power plan, which shows all existing and new receptacle outlets. " Provide electrical disconnects for air handlers, condensing units and water heaters, which are not with-in sight and 50' of originating power supply panel. " Provide receptacle outlet(s) at show windows, at least equal to one receptacle outlet for each twelve linear feet of glazing or portion thereof. " Provide a lighting plan, which clearly identifies all, existing and new lighting fixtures and switches, and which resolves the conflicts between 2 X 4 light location(s), in the kitchen on sheet A-5 and kitchen air supply and return grilles on sheet M-1. " Provide additional emergency egress illumination for the restroom corridor and the food service area. " Item # 45 is indicated to be an existing exhaust hood with fire protection, verify if this is correct. " Provide a minimum of a heat capture hood at the rack oven #15. " Indicate location(s) of exhaust(s) and make-up air intakes for existing and new exhaust hood(s), restroom exhaust ducts and fresh air intakes. " Provide or verify exhaust fans, in all restrooms. " Provide outside air for HVAC units. " Provide installation detail(s) for air handler(s) which are suspended and which are installed above the restrooms and office. " Indicate a primary method of condensate disposal and provide an auxiliary pan with a secondary drain or a float switch. " Provide energy calculations. FYI: If Mechanical, Electrical and Plumbing drawings are to be provided by the contractors of record, each drawing must bear the signature and license number of the person responsible for the design. All revised and/or additional drawings must be assembled together and resubmitted as a complete package. Larry Woodrome, CBO Chief Plans Examiner City of Palm Coast 386-986-3786 | |||
| DSD | COMPLETE | 04/04/2007 | 04/04/2007 |
| Note: Released By: DCHAUDOIN | |||
| BLD | COMPLETE | 06/04/2007 | |
| Note: Released By: LWOODROME |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADDITIONAL FEE | ¤40.00 | 10/24/2007 |
| MISCELLANEOUS | ¤40.00 | 10/24/2007 |
| REINSPECTION FEE | ¤40.00 | 10/24/2007 |
| REINSPECTION FEE | ¤40.00 | 10/24/2007 |
| REVISION | ¤40.00 | 10/24/2007 |
| REVISION | ¤40.00 | 10/24/2007 |
| PERMIT FEE | ¤336.00 | 06/05/2007 |
| PLAN CHECK FEE | ¤100.00 | 06/05/2007 |
| PLUMBING FEE | ¤58.80 | 06/05/2007 |
| ADMIN FEE | ¤20.00 | 06/05/2007 |
| ELECTRIC FEE | ¤58.80 | 06/05/2007 |
| FIRE PLANS REVIEW | ¤42.00 | 06/05/2007 |
| GAS PIPING | ¤40.00 | 06/05/2007 |
| MECHANICAL FEE | ¤58.80 | 06/05/2007 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤954.40 |