Permit #2007040642

Permit Details

Status: COED

Parcel Id: 07-11-31-7013-00150-0440
CONDITIONED SPACE: 1908 sqft
GARAGE: 514 sqft
OPENED PORCH (WITH ROOF) : 242 sqft
OPENED PORCH (WITH ROOF) : 79 sqft
Total Square Footage: 2743 sqft
Block: 00150
Subdivision: -
Job Phone: (386)447-0818
Location Address: 139 BRITTANY LN
Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY
Issue Date: 06/25/2007
NOC: RECORDED
Applicant name: GREGORY ALLAN NELSON
Owner: SHIRLEY MONROSE

Address

147-10 230TH PLACE

SPRINGFIELD GARDENS, NY 11413

Lot: 0440
Contracted Stated Job Value: ¤220,000.00
Job Description: SINGLE FAMILY
Type: CN

Contractor

HERITAGE HOMES OF PALM COAST INC.
Status Location Address State License Number Phone Fax
CANCEL

12 PRINCESS KIM LANE

PALM COAST, FL 32137

CBC1251716 (Exp: 09/30/2008) (386)447-0818 (386)447-0359

Sub Contractors

KENNETH J LOEPER
Status Location Address State License Number Phone Fax
CANCEL

PO BOX 353782

PALM COAST, FL 32164

ES12000379 (Exp: 08/31/2010) (386)931-5106 (386)986-2272
THOMAS ALAN MOSE
Status Location Address State License Number Phone Fax
INACTIVE

PO BOX 1894

HOLLY HILL, FL 32117

CAC048082 (Exp: 08/31/2026) 386-255-4545 (386)252-4979
MARTIN JOHN EVANS
Status Location Address State License Number
ACTIVE

14 FORT CAROLINE CT

BUNNELL, FL 32110

CFC057676 (Exp: 08/31/2026)
JEFFREY JAY MITCHELL
Status Location Address State License Number Phone Fax
CANCEL

PO BOX 353178

PALM COAST, FL 32135

CCC1327078 (Exp: 08/31/2010) (386)437-3929 (386)447-2236

Inspection History

Type Request Date Result Inspector
FINAL COMPLETE BUILDING INSPECTION 03/18/2008 Disapproved -FEE REQUIRED ACOOPER
Note: THIS IS A REINSPECTION PUT MASTER BATH AND CLOSETS ON ARC-FAULT BREAKER.
FINAL COMPLETE BUILDING INSPECTION 03/18/2008 FINAL APPROVED ACOOPER
Note: THIS IS A REINSPECTION
FINAL COMPLETE BUILDING INSPECTION 03/17/2008 Disapproved -FEE REQUIRED ACOOPER
Note: ANCHOR A/C UNIT, RE-IDENTIFY WIRING IN DISCONNECT BOX, PUT MASTER BATH AND CLOSETS ON ARC-FAULT BREAKER.
STORMWATER FINAL INSPECTION 03/03/2008 APPROVED GLALIMA
UTILITY COMPANY FINAL 02/25/2008 APPROVED TSCHWEERS
Note: Gravity ok.
STORMWATER FINAL INSPECTION 02/25/2008 Disapproved -FEE REQUIRED DRANDALL
Note: clean out concrete overspill from culvert ends.....remove silt fence from rear of property.....24 sf road damage $292.00
RESIDENTIAL EARLY POWER 02/14/2008 APPROVED RMARVEL
Note: REQUESTED BY CONTRACTOR
PRE DRIVEWAY 01/16/2008 APPROVED DRANDALL
Note: THIS IS A REINSPECTION
PRE DRIVEWAY 01/15/2008 Disapproved -FEE REQUIRED DRANDALL
Note: culvert pipe must have 50% coverage of dirt & 50% coverage of concrete all along length of pipe
LATH /BRICK FLASHING 11/30/2007 APPROVED CMINI
INSULATION INSPECTION 11/09/2007 APPROVED MMOORE
ALL ROUGH 11/07/2007 APPROVED DROCKWELL
Note: THIS IS A REINSPECTION
ALL ROUGH 11/06/2007 Disapproved -FEE REQUIRED DROCKWELL
Note: THIS IS A REINSPECTION STILL NEED TO TIGHTEN BOLTS ON BEARING WALL ATTACHMENT TO CMU WALL.(GARAGE) FRAME OUT FOR DRYER VENT. SUPPORT DRYER VENT USING APPROVED MEANS. FIRE BLOCK NEEDED AT DINING ROOM/GARAGE WALL.
ALL ROUGH 10/31/2007 Disapproved -FEE REQUIRED PGALLMANN
Note: THIS IS A REINSPECTION BOLTS AT BEARING WALL IN GARAGE AT ATTACHMENT TO CMU NEEDS TO BE TORQUED. STILL NEED TO ADD RECEPTACLE AT LEFT OF FRONT DOOR. NO PRESSURE ON PLUMBING. AIR HANDLER PLATFORM STILL DOES NOT CONFORM TO PLANS. INSTALL N AIL PLATES FOR ELECTRICAL WIRING WHERE LESS THAN 1.25IN FROM EDGE OF FRAMING MEMBER TO EDGE OF HOLE. ADD SUPPORT AT RANGE HOOD VENT OFFSET. INSTALL NON COMPRESSIBLE SHIMS AT CIRCLE HEAD WINDOW ATTACHMENT.
ALL ROUGH 10/24/2007 Disapproved -FEE REQUIRED MMOORE
Note: STRAPPING ABOVE GARAGE TO NAIL INTO TRUSS VERTICAL FRAMING. STRAP SER CABLE WITHIN 12IN OF ENCLOSURE. CAP EXTRA RACEWAY. STRAP SER EVERY 4.5FT. MISSING MULTIPLE NAIL PLATES. NO PRESSURE ON PLUMBING. SHEAR WALL LEFT OF GARAGE BOLT IS LOOSE. FRAME PLENUM PER PLAN. ADD REC. AT FRONT DOOR. NOT READY.
ROOF IN PROGRESS 09/21/2007 APPROVED RMARVEL
ROOF SHEATHING/BRACES/TIES/ DOWN CELL 09/13/2007 APPROVED MMOORE
ROOF SHEATHING/BRACES/TIES/ DOWN CELL 09/12/2007 CANCELLED BY APPLICANT AIRS WEB
Note: THIS IS A REINSPECTION
ROOF SHEATHING/BRACES/TIES/ DOWN CELL 09/06/2007 Disapproved -FEE REQUIRED MMOORE
Note: 1. GROUT UNDER TRUSSES 2. TIGHTEN ALL-THREAD 3. AT FRAMED ARCHES: CANNOT SEE TAPCONNED TREATED 2X4 / 2X6 AT 12" O.C. OPEN-UP PLYWOOD AT ARCHES 3. HOLES CUT AT ARCHES ARE TOO SMALL FOR INSULATING AROUND ARCH 4. ALL NON P.T. AT LINTELS TO BE PROTECTED BY VAPOR BARRIER
LINTEL 07/25/2007 APPROVED ACOOPER
FOUNDATION SURVEY APPROVED BY STORMWATER 07/18/2007 APPROVED WKINELL
MONOLITHIC SLAB INSPECTION/SLAB 07/03/2007 APPROVED MMOORE
MONOLITHIC SLAB INSPECTION/SLAB 07/02/2007 Disapproved -FEE REQUIRED CMINI
Note: NEED TO HAVE STAMPED APPROVED SET OF PLANS ON JOB SITE.
FIRST ROUGH PLUMBING INSPECTION 06/27/2007 APPROVED ACOOPER
Note:

Review History

Department Status Date In Date Out
BLD COMPLETE 10/29/2007 10/30/2007
Note: Released By: FREODICA Rev.- Revised Air handling unit base frame detail.
BLD COMPLETE 09/04/2007 09/04/2007
Note: Released By: FREODICA Approved for release. Rev.- connector schedule.
SW1 COMPLETE 08/10/2007 08/10/2007
Note: Released By: WKINELL Received new topo surveys/LGPs.//wk
SW1 HOLD 08/08/2007 08/08/2007
Note: Held By: EBLACKER We cannot complete the swale plan for this property due to a datum elevation discrepancy on the topographic survey. We check the topographic surveys against the city's as-built drawings corrected to the NAVD of 1988. The elevations apear to be referenced to NGVD 1929 because they are high by an average of 1.05ft. Please submit three signed sealed topographic surveys for this property showing corrected elevations. If we can be of help regarding this issue please call (386) 986-4760. NOTE: When topographic survey elevations are changed, all documents that reference or duplicate those elevations must also be revised.
BLD COMPLETE 05/10/2007 05/14/2007
Note: Released By: CCOTE Approved for Release per plan cover sheet. Review by Auba.
SW1 COMPLETE 04/27/2007 04/27/2007
Note: Released By: WKINELL Inspection hold in place until erosion control measures are in installed and approved along the rear property line and front swale.\\wk
ZON COMPLETE 04/25/2007 05/10/2007
Note: Released By: ECOYNE need 5 trees (3) exsisting need plant schedule

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
EARLY POWER INSPECTION ¤40.00 03/19/2008
REINSPECTION FEE ¤40.00 03/19/2008
REINSPECTION FEE ¤40.00 03/19/2008
REINSPECTION FEE ¤40.00 03/19/2008
REINSPECTION FEE ¤40.00 03/19/2008
REINSPECTION FEE ¤40.00 03/19/2008
REINSPECTION FEE ¤40.00 03/19/2008
REVISION ¤40.00 03/19/2008
REVISION ¤40.00 03/19/2008
STORMWATER REINSPECTION FEE ¤35.00 03/19/2008
STORMWATER REINSPECTION FEE ¤35.00 03/19/2008
10/06 TRANS IMPACT FEE/MULTI ¤3,631.83 06/25/2007
ADMIN FEE ¤20.00 06/25/2007
ARC HOUSE REVIEW ¤125.00 06/25/2007
BUILDING CODE ADMIN FUND ¤13.72 06/25/2007
ELECTRIC FEE ¤162.00 06/25/2007
SCHOOL BOARD IMPACT FEE RES ¤3,600.00 06/25/2007
STORM WATER PERMIT FEES ¤80.00 06/25/2007
FIRE IMPACT FEE RES 4/1/07 ¤185.11 06/25/2007
MECHANICAL FEE ¤162.00 06/25/2007
PERMIT FEE ¤858.00 06/25/2007
PARKS IMPACT FEE 4/1/07 ¤1,196.11 06/25/2007
PLAN CHECK FEE ¤88.00 06/25/2007
PLUMBING FEE ¤162.00 06/25/2007
RADON FEE ¤13.72 06/25/2007
Fees Total Due: ¤0.00 Total Paid: ¤10,727.49