I want to search for...
Permit #2007060090
Permit Details
Status: COED
| Parcel Id: 11-30-3020-00000-0022 |
| COMMERCIAL SQUARE FOOTAGE: 9412 sqft |
| Total Square Footage: 9412 sqft |
| Block: 00000 |
| Subdivision: - |
| Job Phone: (386)931-4741 |
| Location Address: 55 PLAZA DR |
| Type: BC - BUILDING COMMERCIAL |
| Issue Date: 08/15/2007 |
| NOC: RECORDED |
| Applicant name: FOSTER H COLEMAN |
| Owner: PALM COAST INVESTMENT PROPERTIES |
|
Address 1 FLORIDA PARK DRIVE PALM COAST, FL 32137 |
| Lot: 0060 |
| Contracted Stated Job Value: ¤615,000.00 |
| Job Description: 2 STORY OFFICE BUILDING - OUTBACK VILLAGE #SP-WVR-06-20 |
| Type: CN |
Contractor
Fantastic Homes Const.Inc. (Foster Coleman)
| Status | Location Address | State License Number | Phone |
| CANCEL |
132 N PENINSULA DR DAYTONA BEACH, FL 32118 |
CGC003579 (Exp: 08/31/2016) | 386-307-1666 |
Sub Contractors
GLEN STEWART COLE
| Status | Location Address | State License Number | Phone | Fax |
| HOLD |
P. O. Box 1677 Palm Coast, FL 32136 |
EC0002522 (Exp: 08/31/2010) | (386) 437-4364 | (386)437-0412 |
THEODORE BARRON JOHNSON
| Status | Location Address | State License Number | Phone |
| ACTIVE |
PO BOX 479 Flagler Beach, FL 32136 |
CAC057081 (Exp: 08/31/2026) | 386-333-1672 |
GLEN WILLIAM KEHLE
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
P. O. Box 353511 BUNNELL, FL 32110 |
CFC057241 (Exp: 08/31/2026) | (386) 447-4249 | (386) 437-8488 |
FOSTER H COLEMAN
| Status | Location Address | State License Number | Phone |
| CANCEL |
132 N PENINSULA DR DAYTONA BEACH, FL 32118 |
CGC003579 (Exp: 08/31/2016) | 386-307-1666 |
Inspection History
| Type | Request Date | Result | Inspector |
| ENGINEERING FINAL | 08/25/2008 | APPROVED | FTORO |
| FINAL COMPLETE BUILDING INSPECTION | 08/25/2008 | FINAL APPROVED | JMCGOWEN |
| Note: THIS IS A REINSPECTION | |||
| LANDSCAPE FINAL | 08/22/2008 | APPROVED | WBUTLER |
| Note: THIS IS A REINSPECTION | |||
| LANDSCAPE FINAL | 08/21/2008 | PARTIALLY APPROVED | WBUTLER |
| Note: THIS IS A REINSPECTION Punch list items for landscape and irrigaiton were addressed except for receipt of the bonding check for the completion of the fence. Need this and the associated cash bond paperwork to be signed and submitted with the check prior to approval. | |||
| UTILITY COMMERCIAL FINAL | 08/21/2008 | APPROVED | KKING |
| FRAMING | 08/21/2008 | APPROVED | CMINI |
| FIREWALL INSPECTION | 08/20/2008 | APPROVED | JLEWIS |
| Note: THIS IS A REINSPECTION | |||
| TRAFFIC ENGINEER | 08/20/2008 | APPROVED | FTORO |
| Note: Foster called to schedule this inspection | |||
| FIREWALL FINAL INSPECTION | 08/20/2008 | APPROVED | JLEWIS |
| FIRE FINAL | 08/20/2008 | APPROVED - AS NOTED | JLEWIS |
| Note: sheel only | |||
| FINAL COMPLETE BUILDING INSPECTION | 08/20/2008 | Disapproved -FEE REQUIRED | JMCGOWEN |
| Note: THIS IS A REINSPECTION/ requested buy contractor Inspection Resulted at 8/20/2008 10:25:50 AM NEED REVISION FOR AWNING ATTACHMENT. | |||
| FINAL COMPLETE BUILDING INSPECTION | 08/19/2008 | Disapproved -FEE REQUIRED | JMCGOWEN |
| Note: Inspection Resulted at 8/19/2008 12:55:02 PM NEED TO HAVE WEATHER PROOF COVERS ON ELECTRIC CAPS AND DRAWING SHOWING AWNINGS ATTACHMENT. | |||
| LANDSCAPE FINAL | 08/19/2008 | PARTIALLY APPROVED | CBENNETT |
| Note: weIncomplete irrigation. Irrigation heads in between buildings are hitting Outback. Hose bibs in front are not installed. Rise in the back of the building are too high and spraying the door. Some plant material is not properly planted and is not Florida Grade Number One quality. Not all plant material matches plans. | |||
| ENGINEERING FINAL | 08/19/2008 | CANCELLED BY INSPECTOR | LAPTEKAR |
| Note: Tropical storm Fay prep. | |||
| COMMERCIAL POWER INSPECTION | 08/14/2008 | APPROVED | RMARVEL |
| Note: THIS IS A REINSPECTION Inspection Resulted at 8/14/2008 3:27:37 PM COLE | |||
| COMMERCIAL POWER INSPECTION | 08/13/2008 | Disapproved -FEE REQUIRED | JHINDMAN |
| Note: REQUESTED BY CONTRACTOR NOT READY | |||
| UTILITY COMPANY FINAL | 08/08/2008 | APPROVED | KKING |
| Note: requested by contractor | |||
| FIREWALL INSPECTION 2ND ROUGH | 05/16/2008 | APPROVED - AS NOTED | JPATTEE |
| Note: soffit inspection | |||
| FIREWALL INSPECTION 2ND ROUGH | 05/12/2008 | APPROVED - AS NOTED | JPATTEE |
| Note: 1st floor west unit steel truss fire protection | |||
| FRAMING | 05/02/2008 | APPROVED | MMOORE |
| Note: 1. 2ND FLOOR FIRE WALL EXTENSIONS FRAMED INTO SOFFITS AT 4 AREAS (2 ON EACH SIDE OF CENTER 2X6 FIRE WALL ) | |||
| FIREWALL INSPECTION | 05/01/2008 | CANCELLED BY APPLICANT | JPATTEE |
| ROOF IN PROGRESS | 04/15/2008 | APPROVED - AS NOTED | DROCKWELL |
| Note: THIS IS A REINSPECTION UNDERLAYMENT DRIPEDGE AND FLASHINGS O.K | |||
| ROOF SHEATHING/BRACES/TIES/ DOWN CELL | 04/14/2008 | APPROVED | MMOORE |
| Note: THIS IS A REINSPECTION | |||
| LATH /BRICK FLASHING | 04/10/2008 | APPROVED | DROCKWELL |
| EXTERIOR WALL SHEATHING/SHEAR WALL | 04/08/2008 | APPROVED | DROCKWELL |
| Note: THIS IS A REINSPECTION | |||
| EXTERIOR WALL SHEATHING/SHEAR WALL | 04/03/2008 | PARTIALLY APPROVED | JLEVRAULT |
| Note: FIRST AND SECOND FLOOR PLYWOOD CEILING AT PORCH INCLUDING EAST SIDE STAIR CEILING. | |||
| ROOF IN PROGRESS | 03/27/2008 | PARTIALLY APPROVED | DROCKWELL |
| Note: ROOFING FLAT DECK,FLASHING UNDER 30`` OVERHANG, | |||
| ROOF SHEATHING/BRACES/TIES/ DOWN CELL | 03/25/2008 | PARTIALLY APPROVED | JLEVRAULT |
| Note: THIS IS A REINSPECTION ALL BUT FRONT CENTER ROOF SECTION. | |||
| ROOF SHEATHING/BRACES/TIES/ DOWN CELL | 03/13/2008 | PARTIALLY APPROVED | MMOORE |
| Note: 1. OK TO DRY-IN THE MAIN ROOF. ...THE ROOF ABOVE THE ELEVATOR IS NOT COMPLETED (SHEATHED) AND NEEDS TO BE LEFT OPEN FOR LATH AND STUCCO INSTALLATION AND INSPECTION AN ADDITIONAL INSPECTION MAY BE REQUIRED UNDER A SHEATHING INSPECTION 2. AT MAIN BUILDING / BENT TRUSS STRAPS / TAPCON NEW ( 4 TAPCONS PER STRAP) 3. THE DRILLED -IN RED HEAD BOLTS AT THE FRONT ELEVATOR EXTERIOR WALL FRAMED ABOVE THE LINTEL ARE LOSE AND HOLES ARE TOO BIG IN PLACES 4. SHIM / GROUT TRUSSES 5. REMOVE FIREWALL TYPE-X DRYWALL FOR FRAMING INSPECTION (ONE SIDE ONLY) | |||
| SECOND FLOOR SLAB INSPECTION | 03/07/2008 | PARTIALLY APPROVED | DROCKWELL |
| Note: ELEVATOR CAP | |||
| LINTEL | 02/22/2008 | Disapproved -FEE REQUIRED | CMINI |
| Note: LINTEL NOT READY FOR INSPECTION...CONTRACTOR REQUESTED ME TO COME BACK IN AFTERNOON.. | |||
| LINTEL | 02/22/2008 | APPROVED - AS NOTED | CMINI |
| Note: THIS IS A REINSPECTION 2ND FL LINTEL. | |||
| MONOLITHIC SLAB INSPECTION/SLAB | 02/01/2008 | APPROVED - AS NOTED | JLEVRAULT |
| Note: SECOND FLOOR DECK SLAB. | |||
| MONOLITHIC SLAB INSPECTION/SLAB | 01/28/2008 | PARTIALLY APPROVED | CMINI |
| Note: THIS IS A REINSPECTION 2ND FL. HALL WAY SLAB... | |||
| MONOLITHIC SLAB INSPECTION/SLAB | 01/25/2008 | Disapproved -FEE REQUIRED | CMINI |
| Note: PLAN CALLING FOR 2" X12" 16" O.C. ON PAGE A-6 AND OTHER PAGE 2` O.C. NEED CORRECTION....PLAN CALLING FOR CDX PLYWOOD UNDER SLAB NEED CORRECTION...HANGERS NOT NAILED...STEAL NOT COMPLETE... CHARLIE 931-1251 | |||
| LINTEL | 01/25/2008 | PARTIALLY APPROVED | CMINI |
| Note: STAIRWELL LINTELS TO 2ND FL. | |||
| LINTEL | 01/22/2008 | PARTIALLY APPROVED | JHINDMAN |
| Note: BALANCE OF 1ST FLOOR BEAM EXCEPT ABOVE STAIR LANDINGS | |||
| SECOND FLOOR SLAB INSPECTION | 01/22/2008 | PARTIALLY APPROVED | JHINDMAN |
| Note: STAIRS | |||
| LINTEL | 01/15/2008 | PARTIALLY APPROVED | JHINDMAN |
| Note: Foster called to schedule this inspection 1ST FLOOR EXCEPT AT STAIRS AND SMALL WALL SEE PLANS | |||
| LINTEL | 01/14/2008 | CANCELLED BY APPLICANT | JHINDMAN |
| TEMPORARY POLE | 01/03/2008 | APPROVED | RMARVEL |
| Note: THIS IS A REINSPECTION | |||
| MONOLITHIC SLAB INSPECTION/SLAB | 12/18/2007 | APPROVED | JHINDMAN |
| MONOLITHIC SLAB INSPECTION/SLAB | 12/17/2007 | Disapproved -FEE REQUIRED | JHINDMAN |
| Note: SLAB NOT READY, J HINDMAN 931-3396 | |||
| FIRST ROUGH PLUMBING INSPECTION | 12/10/2007 | APPROVED | JGIBSON |
| TIE BEAM | 12/10/2007 | APPROVED - AS NOTED | CMINI |
| Note: ELEVATOR PIT TIE BEAM,REMOVE FORM BOARDS FROM FOOTER BEFORE BACK FILL... | |||
| FOOTER | 12/05/2007 | PARTIALLY APPROVED | JLEVRAULT |
| Note: ELEVATOR PAD. | |||
| TEMPORARY POLE | 12/05/2007 | Disapproved -FEE REQUIRED | RMARVEL |
| Note: NEED TO SEE BURIAL DEPTH OF T-POLE SER CONDUCTORS. | |||
| FIRST ROUGH PLUMBING INSPECTION | 11/28/2007 | APPROVED - AS NOTED | JGIBSON |
| Note: THIS WAS FIRST ROUGH ON STORM DRAIN LINE ONLY |
Review History
| Department | Status | Date In | Date Out |
| PLUM | COMPLETE | 07/29/2008 | 07/29/2008 |
| Note: Released By: JMCGOWEN revise plumbing riser | |||
| BLD | COMPLETE | 07/16/2008 | 07/17/2008 |
| Note: Released By: FREODICA Revision: | |||
| PLUM | HOLD | 07/16/2008 | 07/16/2008 |
| Note: Held By: FREODICA 1. Sheet P-1: The sanitary venting shown on Plumbing Riser Diagram is non-compliant to FPC 2004 Section 908.3. Please revise. | |||
| ELEC | COMPLETE | 07/15/2008 | 07/15/2008 |
| Note: Released By: SKNOPF Approved for Release. Revision - Service increased to 600A. Note Service feeder needs 4th wire for 3 phase service. Quantity of tenants and tenant meters increased to 8. Revised panel schedules for tenants and revised load calculations. Reduced size of AHU/ACU for each tenant. | |||
| MECH | COMPLETE | 06/17/2008 | 06/17/2008 |
| Note: Released By: FREODICA Revision: Changed bldg to shell bldg. | |||
| PLUM | COMPLETE | 06/17/2008 | 06/17/2008 |
| Note: Released By: FREODICA | |||
| ELEC | HOLD | 06/16/2008 | 06/16/2008 |
| Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Revision to Permit #2007060090 (Commercial Shell Bldg @ 47 Plaza Dr.) 6/16/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. E1/A3: a. Sheet E1 does not reflect the new wall between Units 1 and 2 as shown on A3. Please coordinate. b. Meter Center on Sheet E1 only allows for 4 tenant meters. Sheet A3 shows minimum 5 tenants now. Please verify meter requirements. c. In this latest revision going from 4 tenants to the potential for 8 tenants, please verify that the 400A service will be sufficient for 8 separate tenants (which could include 8 HVAC, water heating and sign circuits), plus the House load. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us | |||
| BLD | COMPLETE | 06/13/2008 | 06/17/2008 |
| Note: Released By: FREODICA Rev.- Changed building to shell building. | |||
| ZON | COMPLETE | 02/25/2008 | 02/25/2008 |
| Note: Released By: BBARTON need to review with DSD - change of elevation Jackie completed | |||
| DSD | COMPLETE | 02/25/2008 | 02/25/2008 |
| Note: Released By: JGONZALEZ | |||
| BLD | COMPLETE | 02/07/2008 | 02/07/2008 |
| Note: Released By: FREODICA Rev. - Changed roof system., added exterior doors, kneewalls, new opening between units at first floor & deleted windows. | |||
| ZON | HOLD | 02/07/2008 | 02/08/2008 |
| Note: Held By: BBARTON Need assistance to review | |||
| BLD | COMPLETE | 01/25/2008 | 01/25/2008 |
| Note: Released By: FREODICA Rev. - Changed balcony slab form up from 3/4" T & G, OSB "Gold" board instead of plywood. | |||
| DSD | COMPLETE | 07/03/2007 | 07/09/2007 |
| Note: Released By: JGONZALEZ Sent just for verification building is being located in approved site. Approved site plan was not submitted. per d. Ramirez nothing has changed. | |||
| BLD | COMPLETE | 06/29/2007 | 07/03/2007 |
| Note: Released By: CCOTE Approved for Release. | |||
| BLD | HOLD | 06/04/2007 | 06/11/2007 |
| Note: Held By: CCOTE CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application No. 2007060090 (47 Plaza Drive) 6/11/07 The following items must be submitted/clarified in order to complete the Building Permit plan review. 1. Provide UL Assembly Number and criteria for rated floor assembly. 2. Indicate separation distance from the Outback building. 3. Identify building height and height to peak. 4. Clarify exposure category used for this project. Sheet A-1 indicates exposure B while sheet A-3 indicates exposure C. 5. Sheet A-2 indicates pre-cast concrete panels on the elevations however the wall section show the wall as masonry. Revise drawings as required. 6. Provide elevator pit ladder information. 7. Clarify whether an elevator pit sump is to be provided. If this is to be provided then supply detail and indicate size and location. 8. Indicate bar overlaps, bar strength and information for grout pours. 9. Revise drawings to show 5'-0" clear dimension for elevator lobby. 10. Dimension locations of vertical bar reinforcing. 11. Sheet A-4 has an accessible diagram that does not match that shown for the restroom layout. 12. Show location of water cooler on the drawings and revise plumbing riser to show these fixtures. 13. Sheet A-4 shows the entrance doors to each unit as swinging out. These doors infringe on the required exit width more than the 50% allowed by code. The life safety drawing shows the doors as swinging into units. Revise plan layout to meet code requirements and to show consistent information. 14. Sheet A-6 shows a Det 1 and Det 2 Powers Steel Lintel details however there is no indication as to which detail is to be used. Revise drawings to clearly indicate the specific lintel information to be used. 15. Sheet E-1 shows the 2nd floor ceiling as a lay-in ceiling however the wall sections indicate the ceiling as gypsum wallboard. Revise drawings to show consistent information and if the ceiling is to be gypsum then indicate locations and size of attic access. 16. Sheet P-1 section DS indicates 8" downspout while notes on the drawings indicate 6" downspouts. Revise drawings to show consistent information. 17. Sheet P-1 indicates 12" pvc stormwater drain line exiting the building. Identify this pipe as either new or existing. If this is new then identify where this pipe extends to. 18. The original site development drawings show the water, sewer, sprinkler main lines stubbed-out at the front of the building while these drawings show the entrance lines on the side. Confirm that the drawings show the correct location. 19. The mechanical drawing note 19 references an EF-3 however none could be found on the plans. The plans show EF-1 on the 1st floor restrooms but not exhaust fans on the 2nd floor. Revise drawings to show exhaust fans at all restrooms and update note as required. 20. Provide information for elevator and add notes verify that it meets accessibility requirements. 21. The stair handrails do not appear to meet code requirements for handrail extensions. Revise drawings and add dimensions showing compliance with code. 22. Provide information/notation on the drawins indicating that the door hardware will meet accessibility requirements. 23. The energy calculation forms submitted are residential forms which are not applicable for this project type. Submit new commercial forms and sizing calculations. ------------------------------------------------------------ Carl L. Cote, R.A. Senior Plans Examiner City of Palm Coast - Building Department 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-4753 [fax]: (386) 986-3781 [email]: ccote@ci.palm-coast.fl.us ------------------------------------------------------------ | |||
| FI1 | COMPLETE | 06/18/2007 | |
| Note: Released By: JPATTEE Sheet E-1 second story, exit/emergency lighting appear to be facing the wrong direction at stairwells. | |||
| BLD | COMPLETE | 08/20/2008 | |
| Note: Released By: JMCGOWEN decorating shutters,"awning attachment detail" |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 08/25/2008 |
| REVISION | ¤40.00 | 08/25/2008 |
| REINSPECTION FEE | ¤40.00 | 08/19/2008 |
| REINSPECTION FEE | ¤40.00 | 08/18/2008 |
| REINSPECTION FEE | ¤40.00 | 08/18/2008 |
| REINSPECTION FEE | ¤40.00 | 08/18/2008 |
| REINSPECTION FEE | ¤40.00 | 08/18/2008 |
| REINSPECTION FEE | ¤40.00 | 08/18/2008 |
| REVISION | ¤40.00 | 08/18/2008 |
| REVISION | ¤80.00 | 08/18/2008 |
| REVISION | ¤60.00 | 08/18/2008 |
| REVISION | ¤40.00 | 08/18/2008 |
| REVISION | ¤40.00 | 08/18/2008 |
| REVISION | ¤60.00 | 08/18/2008 |
| TRANSPORTATION IMPACT FEE | ¤44,787.19 | 08/15/2007 |
| ADMIN FEE | ¤20.00 | 08/15/2007 |
| BUILDING CODE ADMIN FUND | ¤47.06 | 08/15/2007 |
| ELECTRIC FEE | ¤399.00 | 08/15/2007 |
| FIRE COMM IMPACT FEE 4/1/07 | ¤482.84 | 08/15/2007 |
| FIRE PLANS REVIEW | ¤94.12 | 08/15/2007 |
| MECHANICAL FEE | ¤399.00 | 08/15/2007 |
| PERMIT FEE | ¤3,382.50 | 08/15/2007 |
| PLAN CHECK FEE | ¤707.25 | 08/15/2007 |
| PLUMBING FEE | ¤399.00 | 08/15/2007 |
| RADON FEE | ¤47.06 | 08/15/2007 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤51,405.02 |