I want to search for...
Permit #2007090197
Permit Details
Status: FINAL
| Parcel Id: 06-12-31-5815-00000-0010 |
| Block: 00000 |
| Subdivision: - |
| Job Phone: (386)248-0460 |
| Location Address: 800 BELLE TERRE PKWY |
| Type: FCA - COMMERCIAL FIRE ALARM |
| Issue Date: 11/05/2007 |
| NOC: Unknown |
| Applicant name: GARY SMITH |
| Owner: NAP TOWN CENTER LLC |
|
Address 7500 COLLEGE PARKWAY FORT MYERS, FL 33907 |
| Lot: 0010 |
| Contracted Stated Job Value: ¤2,200.00 |
| Job Description: BLDG. C ---UNITS 214 -216 -- FIRE ALARM FOR "BAMBOO CREEK" |
| Type: CN |
Contractor
CERTIFIED ELECTRONIC SYSTEMS, INC.
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
1120 A ENTERPRISE COURT HOLLY HILL, FL 32117 |
EF0000139 (Exp: 08/31/2026) | (386)248-0460 | (386)248-2003 |
Inspection History
| Type | Request Date | Result | Inspector |
| FIRE ALARM INSPECTION 1ST ROUGH | 11/06/2007 | APPROVED | JPATTEE |
| FIRE ALARM FINAL INSPECTION | 11/06/2007 | FINAL APPROVED | JPATTEE |
Review History
| Department | Status | Date In | Date Out |
| FI1 | HOLD | 10/29/2007 | 10/31/2007 |
| Note: Held By: JPATTEE The pull stations at the front or the north exits are not within 5ft of the doors. | |||
| FI1 | HOLD | 09/21/2007 | 09/21/2007 |
| Note: Held By: JPATTEE Will there be a connection to the fire suppression system, not indicated? | |||
| FI1 | REJECT | 09/19/2007 | 09/20/2007 |
| Note: Rejected By: JPATTEE Provide cut sheets for all devices. No wiring diagram provided. Provide battery calc's | |||
| FI1 | COMPLETE | 11/02/2007 | |
| Note: Released By: JPATTEE |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADDITIONAL FEE | ¤40.00 | 11/05/2007 |
| FIRE ALARM | ¤75.00 | 11/05/2007 |
| PERMIT FEE | ¤40.00 | 11/05/2007 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤155.00 |