I want to search for...
Permit #2007110084
Permit Details
Status: COED
| Parcel Id: 14-11-30-5538-00000-0080 |
| COMMERCIAL SQUARE FOOTAGE: 5000 sqft |
| Total Square Footage: 5000 sqft |
| Block: 00000 |
| Subdivision: - |
| Job Phone: (386) 445-7945 |
| Location Address: 515 PALM COAST PKWY SW |
| Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION |
| Issue Date: 04/17/2008 |
| NOC: RECORDED |
| Applicant name: RYSZARD A SKLADZIEN |
| Owner: ROMA COURT LLC |
|
Address 650 A HERITAGE HILLS SOMERS, NY 10589 |
| Lot: 0080 |
| Contracted Stated Job Value: ¤250,000.00 |
| Job Description: UNIT 3, 4, & 5 INTERIOR - "AMERICAN RENAL ASSOCIATES" --KIDNEY DIALYSIS CARE CENTER |
| Type: CN |
Contractor
RYSKCON CONSTRUCTION INC.
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
2 Market Place Unit D Palm Coast, FL 32137 |
CGC037470 (Exp: 08/31/2014) | (386) 445-7945 | (386)446-3871 |
Sub Contractors
PAUL NOEL BIELEFELDT
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
320 Aragon Street Holly Hill, FL 32117 |
EC0001646 (Exp: 08/31/2026) | (386) 677-0447 | 386-673-9868 |
CHARLES WEYANT
| Status | Location Address | State License Number | Phone |
| ACTIVE |
PO BOX 1261 FLAGLER BEACH, FL 32136 |
CAC1815058 (Exp: 08/31/2026) | (386)246-7745 |
GARY WAYNE EVERS
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
PO BOX 740106 ORANGE CITY, FL 32763 |
CFC050566 (Exp: 08/31/2026) | 386-775-0909 | 386-775-0918 |
Inspection History
| Type | Request Date | Result | Inspector |
| FINAL COMPLETE BUILDING INSPECTION | 10/29/2008 | FINAL APPROVED | JHINDMAN |
| Note: requested by Cezar | |||
| ABOVE CEILING | 08/27/2008 | APPROVED | JMCGOWEN |
| Note: THIS IS A REINSPECTION | |||
| H.V.A.C. FINAL | 08/27/2008 | APPROVED | JMCGOWEN |
| FIRE FINAL | 08/14/2008 | APPROVED | JLEWIS |
| Note: THIS IS A REINSPECTION | |||
| UTILITY COMMERCIAL FINAL | 08/14/2008 | APPROVED | KKING |
| UTILITY COMPANY FINAL | 08/14/2008 | APPROVED | KKING |
| H.V.A.C. FINAL | 08/13/2008 | Disapproved -FEE REQUIRED | LWOODROME |
| Note: Fresh air duct not sized correctly plan shows 8" duct 4" duct is installed. | |||
| ABOVE CEILING | 08/13/2008 | Disapproved -FEE REQUIRED | LWOODROME |
| Note: THIS IS A REINSPECTION Defuser not installed as shown on HVAC plan (1 defuser missing from total required) | |||
| FIREWALL FINAL INSPECTION | 08/08/2008 | APPROVED | JPATTEE |
| Note: THIS IS A REINSPECTION | |||
| FIREWALL FINAL INSPECTION | 07/29/2008 | CANCELLED BY APPLICANT | JPATTEE |
| FIRE FINAL | 07/29/2008 | CANCELLED BY APPLICANT | JPATTEE |
| ELECTRICAL FINAL | 07/24/2008 | APPROVED | RMARVEL |
| Note: CALLED BY CONTRACTOR | |||
| ABOVE CEILING | 07/24/2008 | Disapproved -FEE REQUIRED | JMCGOWEN |
| Note: THIS IS A REINSPECTION NEED REVISIONS FOR THE FOLLOWING.........SHOW FRESH AIR MAKE UP ON PLAN.....SHOW SUPPLIES IN PROPER PLACE....SHOW THAT YOU CAN USE MORE THAN 6` FLEX DUCT..... | |||
| ABOVE CEILING | 07/22/2008 | PARTIALLY APPROVED | LHITES |
| Note: electric only THIS ABOVE CEILING WAS FOR ELECTRIC ONLY | |||
| PLUMBING FINAL | 07/21/2008 | FINAL APPROVED | PGALLMANN |
| Note: requested by contractor | |||
| COMMERCIAL POWER INSPECTION | 07/11/2008 | APPROVED | LHITES |
| Note: REQUESTED BY ROBERT THIS WAS APPROVED AND CALLED IN TO FPL BY ROBERT MARVEL ON 7-11-08 | |||
| INSULATION INSPECTION | 05/22/2008 | APPROVED | MMOORE |
| Note: NORTH AND SOUTH WALLS, AREA AT (AGAINST) METAL DECKING TO BE FOAMED AS PER INSTRUCTION TO CONTRACTOR FROM FIRE MARSHAL | |||
| SECOND ROUGH PLUMBING INSPECTION | 05/14/2008 | APPROVED - AS NOTED | JGIBSON |
| Note: THIS IS A REINSPECTION NEED TO HAVE INSULATION ON WATER LINES IN ABOVE CEILING INSPECTION.........MARK | |||
| SECOND ROUGH PLUMBING INSPECTION | 05/13/2008 | Disapproved -FEE REQUIRED | JGIBSON |
| Note: HOT WATER LINES IN CEILING AND IN WALLS NOT INSULATED PER PLANS, MISSING RISER CLAMP ON CONDENSATE 2`` DRAIN LINE ON EAST SIDE OF FIRE WALL,....................MARK 931-2912 | |||
| FRAMING | 05/07/2008 | APPROVED | JLEVRAULT |
| Note: THIS IS A REINSPECTION | |||
| 2ND ROUGH ELECTRICAL | 04/29/2008 | APPROVED - AS NOTED | LHITES |
| Note: MOVE WIRES THAT ARE BEHIND SINK BRACE WILL CHECK AT INSULTION | |||
| H.V.A.C. ROUGH | 04/28/2008 | APPROVED | JLEVRAULT |
| ABOVE CEILING | 04/28/2008 | CANCELLED BY INSPECTOR | JLEVRAULT |
| Note: CALLED IN BY MISTAKE. | |||
| FIRST ROUGH PLUMBING INSPECTION | 04/28/2008 | Disapproved -FEE REQUIRED | JGIBSON |
| Note: NOT READY NO TEST ON SANITARY, NO PRESSUER ON WATER LINES MISSING RISER CLAMPS, INCOMPLETE INSPECTION.........MARK 931-2912 | |||
| ALL ROUGH | 04/28/2008 | CANCELLED BY INSPECTOR | JLEVRAULT |
| Note: INSPECTIONS WILL BE CALLED IN BY TRADE. | |||
| FRAMING | 04/28/2008 | Disapproved -FEE REQUIRED | JLEVRAULT |
| Note: REVISION IS REQUIRED TO SHOW CHANGES MADE IN THE UNIT. |
Review History
| Department | Status | Date In | Date Out |
| MECH | COMPLETE | 08/08/2008 | 08/11/2008 |
| Note: Released By: FREODICA REVISION 1. Added outside air ducts to the AHU's and revised ductwork. | |||
| BLD | COMPLETE | 05/05/2008 | 05/05/2008 |
| Note: Released By: JJOSEPH | |||
| UD1 | COMPLETE | 04/02/2008 | 04/07/2008 |
| Note: Released By: CJOHNSON | |||
| BLD | COMPLETE | 03/11/2008 | 03/12/2008 |
| Note: Released By: JMCGOWEN Correction Responce to comments | |||
| FI1 | HOLD | 02/26/2008 | 02/27/2008 |
| Note: Held By: JPATTEE Infrastructure has not kept pace with building construction. I have requested stabilized access since November 07. As of February 27, 2008 it is still not acceptable. Review for this permit will resume when site is acceptable. | |||
| DSD | COMPLETE | 11/28/2007 | 11/28/2007 |
| Note: Released By: CBENTLEY Held By: JGONZALEZ per Constance and Phong need to submit a request for parking flexability. jgonzalez 11/28/07 | |||
| DSD | HOLD | 11/07/2007 | 11/09/2007 |
| Note: Held By: JGONZALEZ need to determine weither use applied for is allowed on this permit retrieving development order for project jgonzalez | |||
| BLD | HOLD | 02/27/2008 | |
| Note: Held By: JJOSEPH Building Comments 1. According to the Florida Building Code section 410, provide location of drinking fountain as required by that section. 2. Provide dimensions of placed concrete under recessed scale on page A6 detail 9. 3. Provide fire rated detail for through ceiling and floor penetrations. 4.Provide verification of required outdoor ventilation. a. Revise Outdoor calculation b.What occupant load on plan is calling for, would require more outdoor ventilation. Electrical Comments: 1. Sheet E2: a. Room 138 Bicarb/Concentrate circuit A-5 is shown as a duplex. Panel schedule shows this as a 1 pole 25A with # 12 conductors and a 2016VA (16.8A) load. Please review NEC 240.4(D) for conductor size compliance. In addition, a duplex receptacle allows the potential for future loads to be added to this circuit. Please revise. b. Review and revise load calculations for circuits B-1,7,9,11 and A-31,33,35,37. c. In all panel load calculations, estimated demand has been reflecting the connected load value. Please review NEC estimated demand requirements and revise calculations to include continuous loads. 2. Sheet E3: a. Exit lighting at door 105 and door 114 does not appear this sheet, but does appear sheet A4. Coordinate drawings. b. Exit lighting appears at door 117 this sheet, but not on sheet A4. Please coordinate drawings. c. Strip light in room 121 is not identified or switched. d. Type 'AE' fixture in Corridor 120 shows circuit A-42. Panel schedule 'A' shows circuit 42 as "space". Coordinate drawings and revise load calculations. 3. Sheet E4: a. Door swing for door 119 violates working space of Panel B per NEC 110.26. Relocate Panel or reverse door swing. b. Note 10 identifies booster pump circuit as MDP-12 in R.O. room 139. Booster pump motor information does not appear on Mechanical, Plumbing, or Fire Sprinkler drawings. Please provide further motor data information for load calculation verification. c. Note 5 identifies R.O. System as 60A, 208V 3Ph circuit MDP-10. Sheet P4 shows R.O. pump in opposite corner of room. Please provide motor information for R.O. pump for load calculation verification, and coordinate drawings for location of pump and disconnect. d. Provide information as to whether any of the storage tanks in rooms 138 and 139 contain liquid and/or gases which qualify as hazardous under NEC 500 thru 505. 4. Sheet E5: a. Panels 'A' and 'B' location this sheet does not match locations shown E4. Please coordinate drawings. *By definition, this facility is designated as a "Patient Care Area" and as such must meet requirements as outlined in NEC 517. In addition, the dialysis treatment area of this facility appears to qualify as a "Critical Care Area" as defined by NEC 517.2 which states "areas in which patients are intended to be subjected to invasive procedures and connected to line-operated, electro-medical devices." Please review NEC requirements for these areas and revise plans accordingly. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us | |||
| DSD | COMPLETE | 02/20/2008 | |
| Note: Released By: CBENTLEY | |||
| FI1 | COMPLETE | 04/02/2008 | |
| Note: Released By: JPATTEE Fire alarm shall require separate permitting. Automatic fire sprinkler work may require review for possible permitting. | |||
| MECH | COMPLETE | 08/26/2008 | |
| Note: Released By: JMCGOWEN revision to relocate 8"outside air |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 10/28/2008 |
| REINSPECTION FEE | ¤40.00 | 10/28/2008 |
| REINSPECTION FEE | ¤40.00 | 10/28/2008 |
| REINSPECTION FEE | ¤40.00 | 10/28/2008 |
| REINSPECTION FEE | ¤40.00 | 10/28/2008 |
| REINSPECTION FEE | ¤40.00 | 10/28/2008 |
| REVISION | ¤40.00 | 10/28/2008 |
| REVISION | ¤40.00 | 10/28/2008 |
| REVISION | ¤80.00 | 10/28/2008 |
| TRANSPORTATION IMPACT FEE | ¤29,556.55 | 10/28/2008 |
| ADMIN FEE | ¤20.00 | 04/17/2008 |
| ELECTRIC FEE | ¤180.00 | 04/17/2008 |
| FIRE PLANS REVIEW | ¤50.00 | 04/17/2008 |
| MECHANICAL FEE | ¤180.00 | 04/17/2008 |
| PERMIT FEE | ¤1,750.00 | 04/17/2008 |
| PLAN CHECK FEE | ¤287.50 | 04/17/2008 |
| PLUMBING FEE | ¤180.00 | 04/17/2008 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤32,604.05 |