Permit #2007110084

Permit Details

Status: COED

Parcel Id: 14-11-30-5538-00000-0080
COMMERCIAL SQUARE FOOTAGE: 5000 sqft
Total Square Footage: 5000 sqft
Block: 00000
Subdivision: -
Job Phone: (386) 445-7945
Location Address: 515 PALM COAST PKWY SW
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 04/17/2008
NOC: RECORDED
Applicant name: RYSZARD A SKLADZIEN
Owner: ROMA COURT LLC

Address

650 A HERITAGE HILLS

SOMERS, NY 10589

Lot: 0080
Contracted Stated Job Value: ¤250,000.00
Job Description: UNIT 3, 4, & 5 INTERIOR - "AMERICAN RENAL ASSOCIATES" --KIDNEY DIALYSIS CARE CENTER
Type: CN

Contractor

RYSKCON CONSTRUCTION INC.
Status Location Address State License Number Phone Fax
CANCEL

2 Market Place Unit D

Palm Coast, FL 32137

CGC037470 (Exp: 08/31/2014) (386) 445-7945 (386)446-3871

Sub Contractors

PAUL NOEL BIELEFELDT
Status Location Address State License Number Phone Fax
ACTIVE

320 Aragon Street

Holly Hill, FL 32117

EC0001646 (Exp: 08/31/2026) (386) 677-0447 386-673-9868
CHARLES WEYANT
Status Location Address State License Number Phone
ACTIVE

PO BOX 1261

FLAGLER BEACH, FL 32136

CAC1815058 (Exp: 08/31/2026) (386)246-7745
GARY WAYNE EVERS
Status Location Address State License Number Phone Fax
ACTIVE

PO BOX 740106

ORANGE CITY, FL 32763

CFC050566 (Exp: 08/31/2026) 386-775-0909 386-775-0918

Inspection History

Type Request Date Result Inspector
FINAL COMPLETE BUILDING INSPECTION 10/29/2008 FINAL APPROVED JHINDMAN
Note: requested by Cezar
ABOVE CEILING 08/27/2008 APPROVED JMCGOWEN
Note: THIS IS A REINSPECTION
H.V.A.C. FINAL 08/27/2008 APPROVED JMCGOWEN
FIRE FINAL 08/14/2008 APPROVED JLEWIS
Note: THIS IS A REINSPECTION
UTILITY COMMERCIAL FINAL 08/14/2008 APPROVED KKING
UTILITY COMPANY FINAL 08/14/2008 APPROVED KKING
H.V.A.C. FINAL 08/13/2008 Disapproved -FEE REQUIRED LWOODROME
Note: Fresh air duct not sized correctly plan shows 8" duct 4" duct is installed.
ABOVE CEILING 08/13/2008 Disapproved -FEE REQUIRED LWOODROME
Note: THIS IS A REINSPECTION Defuser not installed as shown on HVAC plan (1 defuser missing from total required)
FIREWALL FINAL INSPECTION 08/08/2008 APPROVED JPATTEE
Note: THIS IS A REINSPECTION
FIREWALL FINAL INSPECTION 07/29/2008 CANCELLED BY APPLICANT JPATTEE
FIRE FINAL 07/29/2008 CANCELLED BY APPLICANT JPATTEE
ELECTRICAL FINAL 07/24/2008 APPROVED RMARVEL
Note: CALLED BY CONTRACTOR
ABOVE CEILING 07/24/2008 Disapproved -FEE REQUIRED JMCGOWEN
Note: THIS IS A REINSPECTION NEED REVISIONS FOR THE FOLLOWING.........SHOW FRESH AIR MAKE UP ON PLAN.....SHOW SUPPLIES IN PROPER PLACE....SHOW THAT YOU CAN USE MORE THAN 6` FLEX DUCT.....
ABOVE CEILING 07/22/2008 PARTIALLY APPROVED LHITES
Note: electric only THIS ABOVE CEILING WAS FOR ELECTRIC ONLY
PLUMBING FINAL 07/21/2008 FINAL APPROVED PGALLMANN
Note: requested by contractor
COMMERCIAL POWER INSPECTION 07/11/2008 APPROVED LHITES
Note: REQUESTED BY ROBERT THIS WAS APPROVED AND CALLED IN TO FPL BY ROBERT MARVEL ON 7-11-08
INSULATION INSPECTION 05/22/2008 APPROVED MMOORE
Note: NORTH AND SOUTH WALLS, AREA AT (AGAINST) METAL DECKING TO BE FOAMED AS PER INSTRUCTION TO CONTRACTOR FROM FIRE MARSHAL
SECOND ROUGH PLUMBING INSPECTION 05/14/2008 APPROVED - AS NOTED JGIBSON
Note: THIS IS A REINSPECTION NEED TO HAVE INSULATION ON WATER LINES IN ABOVE CEILING INSPECTION.........MARK
SECOND ROUGH PLUMBING INSPECTION 05/13/2008 Disapproved -FEE REQUIRED JGIBSON
Note: HOT WATER LINES IN CEILING AND IN WALLS NOT INSULATED PER PLANS, MISSING RISER CLAMP ON CONDENSATE 2`` DRAIN LINE ON EAST SIDE OF FIRE WALL,....................MARK 931-2912
FRAMING 05/07/2008 APPROVED JLEVRAULT
Note: THIS IS A REINSPECTION
2ND ROUGH ELECTRICAL 04/29/2008 APPROVED - AS NOTED LHITES
Note: MOVE WIRES THAT ARE BEHIND SINK BRACE WILL CHECK AT INSULTION
H.V.A.C. ROUGH 04/28/2008 APPROVED JLEVRAULT
ABOVE CEILING 04/28/2008 CANCELLED BY INSPECTOR JLEVRAULT
Note: CALLED IN BY MISTAKE.
FIRST ROUGH PLUMBING INSPECTION 04/28/2008 Disapproved -FEE REQUIRED JGIBSON
Note: NOT READY NO TEST ON SANITARY, NO PRESSUER ON WATER LINES MISSING RISER CLAMPS, INCOMPLETE INSPECTION.........MARK 931-2912
ALL ROUGH 04/28/2008 CANCELLED BY INSPECTOR JLEVRAULT
Note: INSPECTIONS WILL BE CALLED IN BY TRADE.
FRAMING 04/28/2008 Disapproved -FEE REQUIRED JLEVRAULT
Note: REVISION IS REQUIRED TO SHOW CHANGES MADE IN THE UNIT.

Review History

Department Status Date In Date Out
MECH COMPLETE 08/08/2008 08/11/2008
Note: Released By: FREODICA REVISION 1. Added outside air ducts to the AHU's and revised ductwork.
BLD COMPLETE 05/05/2008 05/05/2008
Note: Released By: JJOSEPH
UD1 COMPLETE 04/02/2008 04/07/2008
Note: Released By: CJOHNSON
BLD COMPLETE 03/11/2008 03/12/2008
Note: Released By: JMCGOWEN Correction Responce to comments
FI1 HOLD 02/26/2008 02/27/2008
Note: Held By: JPATTEE Infrastructure has not kept pace with building construction. I have requested stabilized access since November 07. As of February 27, 2008 it is still not acceptable. Review for this permit will resume when site is acceptable.
DSD COMPLETE 11/28/2007 11/28/2007
Note: Released By: CBENTLEY Held By: JGONZALEZ per Constance and Phong need to submit a request for parking flexability. jgonzalez 11/28/07
DSD HOLD 11/07/2007 11/09/2007
Note: Held By: JGONZALEZ need to determine weither use applied for is allowed on this permit retrieving development order for project jgonzalez
BLD HOLD 02/27/2008
Note: Held By: JJOSEPH Building Comments 1. According to the Florida Building Code section 410, provide location of drinking fountain as required by that section. 2. Provide dimensions of placed concrete under recessed scale on page A6 detail 9. 3. Provide fire rated detail for through ceiling and floor penetrations. 4.Provide verification of required outdoor ventilation. a. Revise Outdoor calculation b.What occupant load on plan is calling for, would require more outdoor ventilation. Electrical Comments: 1. Sheet E2: a. Room 138 Bicarb/Concentrate circuit A-5 is shown as a duplex. Panel schedule shows this as a 1 pole 25A with # 12 conductors and a 2016VA (16.8A) load. Please review NEC 240.4(D) for conductor size compliance. In addition, a duplex receptacle allows the potential for future loads to be added to this circuit. Please revise. b. Review and revise load calculations for circuits B-1,7,9,11 and A-31,33,35,37. c. In all panel load calculations, estimated demand has been reflecting the connected load value. Please review NEC estimated demand requirements and revise calculations to include continuous loads. 2. Sheet E3: a. Exit lighting at door 105 and door 114 does not appear this sheet, but does appear sheet A4. Coordinate drawings. b. Exit lighting appears at door 117 this sheet, but not on sheet A4. Please coordinate drawings. c. Strip light in room 121 is not identified or switched. d. Type 'AE' fixture in Corridor 120 shows circuit A-42. Panel schedule 'A' shows circuit 42 as "space". Coordinate drawings and revise load calculations. 3. Sheet E4: a. Door swing for door 119 violates working space of Panel B per NEC 110.26. Relocate Panel or reverse door swing. b. Note 10 identifies booster pump circuit as MDP-12 in R.O. room 139. Booster pump motor information does not appear on Mechanical, Plumbing, or Fire Sprinkler drawings. Please provide further motor data information for load calculation verification. c. Note 5 identifies R.O. System as 60A, 208V 3Ph circuit MDP-10. Sheet P4 shows R.O. pump in opposite corner of room. Please provide motor information for R.O. pump for load calculation verification, and coordinate drawings for location of pump and disconnect. d. Provide information as to whether any of the storage tanks in rooms 138 and 139 contain liquid and/or gases which qualify as hazardous under NEC 500 thru 505. 4. Sheet E5: a. Panels 'A' and 'B' location this sheet does not match locations shown E4. Please coordinate drawings. *By definition, this facility is designated as a "Patient Care Area" and as such must meet requirements as outlined in NEC 517. In addition, the dialysis treatment area of this facility appears to qualify as a "Critical Care Area" as defined by NEC 517.2 which states "areas in which patients are intended to be subjected to invasive procedures and connected to line-operated, electro-medical devices." Please review NEC requirements for these areas and revise plans accordingly. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us
DSD COMPLETE 02/20/2008
Note: Released By: CBENTLEY
FI1 COMPLETE 04/02/2008
Note: Released By: JPATTEE Fire alarm shall require separate permitting. Automatic fire sprinkler work may require review for possible permitting.
MECH COMPLETE 08/26/2008
Note: Released By: JMCGOWEN revision to relocate 8"outside air

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION FEE ¤40.00 10/28/2008
REINSPECTION FEE ¤40.00 10/28/2008
REINSPECTION FEE ¤40.00 10/28/2008
REINSPECTION FEE ¤40.00 10/28/2008
REINSPECTION FEE ¤40.00 10/28/2008
REINSPECTION FEE ¤40.00 10/28/2008
REVISION ¤40.00 10/28/2008
REVISION ¤40.00 10/28/2008
REVISION ¤80.00 10/28/2008
TRANSPORTATION IMPACT FEE ¤29,556.55 10/28/2008
ADMIN FEE ¤20.00 04/17/2008
ELECTRIC FEE ¤180.00 04/17/2008
FIRE PLANS REVIEW ¤50.00 04/17/2008
MECHANICAL FEE ¤180.00 04/17/2008
PERMIT FEE ¤1,750.00 04/17/2008
PLAN CHECK FEE ¤287.50 04/17/2008
PLUMBING FEE ¤180.00 04/17/2008
Fees Total Due: ¤0.00 Total Paid: ¤32,604.05