Permit #2007110216
Permit Details
Status: FINAL
| Parcel Id: 26-10-30-0000-01020-0010 |
| Block: 01020 |
| Subdivision: - |
| Job Phone: (941)812-9952 |
| Location Address: 2455 OLD KINGS RD N |
| Type: TA - TELECOMMUNICATION TOWER ALTERATION |
| Issue Date: 03/04/2008 |
| NOC: RECORDED |
| Applicant name: JOHN DAVID MANN |
| Owner: FLAGLER COUNTY C/O JEFFERY C SWEET ESQ. |
|
Address SUITE A ORMOND BEACH, FL 32174 |
|
Address 595 WEST GRANADA BLVD ORMOND BEACH, FL 32174 |
| Lot: 0010 |
| Contracted Stated Job Value: ¤40,000.00 |
| Job Description: COLLOCATION OF ANTENNA & EQUIPMENT ON EXISTING COMMUNICATION TOWER |
| Type: CN |
Contractor
ATLAS SOLUTIONS INC
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
2071 58TH AVE CIRCLE EAST BRADENTON, FL 34203 |
CGC060425 (Exp: 08/31/2026) | (941)812-9952 | (941)821-2994 |
Sub Contractors
PAUL JOHN FAGAN
| Status | Location Address | State License Number | Phone |
| ACTIVE |
2071 58TH AVE CIRCLE BRADENTON , FL 34203 |
EC0002520 (Exp: 08/31/2026) | 941-809-1229 |
Inspection History
| Type | Request Date | Result | Inspector |
| UNDERGROUND ELECTRICAL | 04/24/2008 | APPROVED | RMARVEL |
| ELECTRICAL FINAL | 04/24/2008 | FINAL APPROVED | RMARVEL |
| Note: THIS IS A REINSPECTION | |||
| LANDSCAPE FINAL | 04/24/2008 | APPROVED | WBUTLER |
| FINAL COMPLETE BUILDING INSPECTION | 04/10/2008 | FINAL APPROVED | JMCGOWEN |
| ELECTRICAL FINAL | 04/10/2008 | CANCELLED BY APPLICANT | LHITES |
| Note: CONTRACTOR CALLED TO CANCEL 8:20 A.M. | |||
| UNDERGROUND ELECTRICAL | 04/04/2008 | APPROVED | RMARVEL |
| MONOLITHIC SLAB INSPECTION/SLAB | 04/01/2008 | APPROVED | JLEVRAULT |
| Note: called by contractor |
Review History
| Department | Status | Date In | Date Out |
| ITC | COMPLETE | 01/23/2008 | 01/25/2008 |
| Note: Released By: BBEMBRY to determine if the project is exempt or non exempt IT - (Kathy) has package | |||
| BLD | COMPLETE | 01/22/2008 | 01/22/2008 |
| Note: Released By: SKNOPF Approved for Release | |||
| BLD | HOLD | 01/08/2008 | 01/09/2008 |
| Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Resubmission of Permit Application #2007110216 (Communications Tower Additions @ 2455 Old Kings Rd N) 1/8/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. Sheet E-1 One Line Diagram: a. Provide information on how generator sourced conductors are tapped into Panelboard A feeder. Power cabinet information was not previously submitted. b. Appleton Technical Support states that the 200A 4W4P Generator receptacle #ADR20044RS Style 1 is not designed for 1PH3W service. They state that for Style 1 receptacles, the receptacle shell is the ground. They recommend that with a 120/240V, 1PH3W service, if it is desired to have the equipment ground wire connected to one of the 4 poles, their Style 2, 3W4P, #ADR20034RS which is designed for this purpose and service type be used. Provide the proper receptacle listed for this use. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us | |||
| BLD | HOLD | 11/14/2007 | 12/04/2007 |
| Note: Held By: SKNOPF Electrical Comments: 1. Sheet E-1: a. On One-Line Diagram Power Cabinet shows (2) 2P 200A circuit breakers, one is normal utility source power and the other for temporary power from a portable generator. Provide further information regarding: 1) "MI" tie between circuit breakers 2) How generator sourced conductors are tapped into Panelboard A feeder b. On One-Line Diagram Appleton generator receptacle identification given is for a 4W4P receptacle. Note at generator receptacle states that "1 pole not connected". Please explain how this receptacle is going to work with a standard 120/240V delta (high leg) mated plug which has 3 phases, a neutral, and a ground. How is the generator high leg going to be prevented from being one of the two phases feeding the panel? Susan Knopf (386) 986-2463 |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADDITIONAL FEE | ¤80.00 | 03/04/2008 |
| PERMIT FEE | ¤40.00 | 03/04/2008 |
| TELECOM ANTENNA PERMIT | ¤40.00 | 03/04/2008 |
| TELECOM TOWER ANTENNA PLAN | ¤40.00 | 03/04/2008 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤200.00 |