Permit #2007110216

Permit Details

Status: FINAL

Parcel Id: 26-10-30-0000-01020-0010
Block: 01020
Subdivision: -
Job Phone: (941)812-9952
Location Address: 2455 OLD KINGS RD N
Type: TA - TELECOMMUNICATION TOWER ALTERATION
Issue Date: 03/04/2008
NOC: RECORDED
Applicant name: JOHN DAVID MANN
Owner: FLAGLER COUNTY C/O JEFFERY C SWEET ESQ.

Address

SUITE A

ORMOND BEACH, FL 32174

Address

595 WEST GRANADA BLVD

ORMOND BEACH, FL 32174

Lot: 0010
Contracted Stated Job Value: ¤40,000.00
Job Description: COLLOCATION OF ANTENNA & EQUIPMENT ON EXISTING COMMUNICATION TOWER
Type: CN

Contractor

ATLAS SOLUTIONS INC
Status Location Address State License Number Phone Fax
ACTIVE

2071 58TH AVE CIRCLE EAST

BRADENTON, FL 34203

CGC060425 (Exp: 08/31/2026) (941)812-9952 (941)821-2994

Sub Contractors

PAUL JOHN FAGAN
Status Location Address State License Number Phone
ACTIVE

2071 58TH AVE CIRCLE

BRADENTON , FL 34203

EC0002520 (Exp: 08/31/2026) 941-809-1229

Inspection History

Type Request Date Result Inspector
UNDERGROUND ELECTRICAL 04/24/2008 APPROVED RMARVEL
ELECTRICAL FINAL 04/24/2008 FINAL APPROVED RMARVEL
Note: THIS IS A REINSPECTION
LANDSCAPE FINAL 04/24/2008 APPROVED WBUTLER
FINAL COMPLETE BUILDING INSPECTION 04/10/2008 FINAL APPROVED JMCGOWEN
ELECTRICAL FINAL 04/10/2008 CANCELLED BY APPLICANT LHITES
Note: CONTRACTOR CALLED TO CANCEL 8:20 A.M.
UNDERGROUND ELECTRICAL 04/04/2008 APPROVED RMARVEL
MONOLITHIC SLAB INSPECTION/SLAB 04/01/2008 APPROVED JLEVRAULT
Note: called by contractor

Review History

Department Status Date In Date Out
ITC COMPLETE 01/23/2008 01/25/2008
Note: Released By: BBEMBRY to determine if the project is exempt or non exempt IT - (Kathy) has package
BLD COMPLETE 01/22/2008 01/22/2008
Note: Released By: SKNOPF Approved for Release
BLD HOLD 01/08/2008 01/09/2008
Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Resubmission of Permit Application #2007110216 (Communications Tower Additions @ 2455 Old Kings Rd N) 1/8/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. Sheet E-1 One Line Diagram: a. Provide information on how generator sourced conductors are tapped into Panelboard A feeder. Power cabinet information was not previously submitted. b. Appleton Technical Support states that the 200A 4W4P Generator receptacle #ADR20044RS Style 1 is not designed for 1PH3W service. They state that for Style 1 receptacles, the receptacle shell is the ground. They recommend that with a 120/240V, 1PH3W service, if it is desired to have the equipment ground wire connected to one of the 4 poles, their Style 2, 3W4P, #ADR20034RS which is designed for this purpose and service type be used. Provide the proper receptacle listed for this use. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us
BLD HOLD 11/14/2007 12/04/2007
Note: Held By: SKNOPF Electrical Comments: 1. Sheet E-1: a. On One-Line Diagram Power Cabinet shows (2) 2P 200A circuit breakers, one is normal utility source power and the other for temporary power from a portable generator. Provide further information regarding: 1) "MI" tie between circuit breakers 2) How generator sourced conductors are tapped into Panelboard A feeder b. On One-Line Diagram Appleton generator receptacle identification given is for a 4W4P receptacle. Note at generator receptacle states that "1 pole not connected". Please explain how this receptacle is going to work with a standard 120/240V delta (high leg) mated plug which has 3 phases, a neutral, and a ground. How is the generator high leg going to be prevented from being one of the two phases feeding the panel? Susan Knopf (386) 986-2463

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADDITIONAL FEE ¤80.00 03/04/2008
PERMIT FEE ¤40.00 03/04/2008
TELECOM ANTENNA PERMIT ¤40.00 03/04/2008
TELECOM TOWER ANTENNA PLAN ¤40.00 03/04/2008