I want to search for...
Permit #2008020012
Permit Details
Status: COED
| Parcel Id: 07-11-31-1090-00000-00B0 |
| Subdivision: 1228 - SOUTHWEST QUADRANT |
| Job Phone: (386)437-3323 |
| Location Address: 160 CYPRESS POINT PKWY |
| Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION |
| Issue Date: 07/17/2008 |
| NOC: RECORDED |
| Applicant name: PETER JOSEPH LYDEN |
| Owner: ASNACO LLC |
|
Address C/O INTERSTATE HOLDINGS INC LAKE MARY, FL 32746 |
|
Address 1307 S INTERNATIONAL PKWY 2051 LAKE MARY, FL 32746 |
| Contracted Stated Job Value: ¤50,000.00 |
| Job Description: BLDG. B - UNITS 101 & 102 BUILDOUT OF SANDWICH SHOP - |
| Type: CN |
Contractor
DEL CONSTRUCTION INC.
| Status | Location Address | State License Number | Phone |
| INACTIVE |
PO BOX 1009 BUNNELL, FL 32110 |
CBC1253392 (Exp: 08/31/2024) | 386-931-2568 |
Sub Contractors
PETER JOSEPH LYDEN
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
PO BOX 1009 BUNNELL, FL 32110 |
EC0002436 (Exp: 08/31/2014) | (386) 931-2568 | 386-313-3445 |
ISAAC WALTER JOHNSTON
| Status | Location Address | State License Number | Phone |
| ACTIVE |
887 BRENTWOOD DRIVE Daytona Beach, FL 32117 |
CFC023634 (Exp: 08/31/2026) | (386) 252-7047 |
Inspection History
| Type | Request Date | Result | Inspector |
| COMMERCIAL BUILDING FINAL | 09/26/2008 | FINAL APPROVED | JMCGOWEN |
| ELECTRICAL FINAL | 09/25/2008 | APPROVED | RMARVEL |
| PLUMBING FINAL | 09/25/2008 | APPROVED | PGALLMANN |
| Note: THIS IS A REINSPECTION | |||
| PLUMBING FINAL | 09/23/2008 | CANCELLED BY APPLICANT | PGALLMANN |
| FIRE FINAL | 09/23/2008 | APPROVED | JPATTEE |
| Note: THIS IS A REINSPECTION | |||
| UTILITY COMPANY FINAL | 09/23/2008 | APPROVED | KKING |
| UTILITY COMMERCIAL FINAL | 09/23/2008 | APPROVED | KKING |
| UTILITY COMPANY FINAL | 09/22/2008 | APPROVED | KKING |
| UTILITY COMMERCIAL FINAL | 09/22/2008 | APPROVED | KKING |
| FIRE FINAL | 09/22/2008 | PARTIALLY APPROVED | JPATTEE |
| Note: Repair emergency light east wall | |||
| SECOND ROUGH PLUMBING INSPECTION | 09/02/2008 | APPROVED | PGALLMANN |
| H.V.A.C. FINAL | 09/02/2008 | APPROVED | JMCGOWEN |
| 2ND ROUGH ELECTRICAL | 09/02/2008 | CANCELLED BY APPLICANT | RMARVEL |
| Note: Inspection Resulted at 9/2/2008 2:52:07 PM NOT READY. | |||
| 2ND ROUGH ELECTRICAL | 08/04/2008 | APPROVED - AS NOTED | RMARVEL |
| Note: Pete called to schedule this inspection WALLS ONLY. | |||
| COMMERCIAL POWER INSPECTION | 08/01/2008 | APPROVED | RMARVEL |
| Note: requested by contractor | |||
| FRAMING | 07/28/2008 | APPROVED | DROCKWELL |
| Note: called by contractor |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 09/23/2008 | 09/23/2008 |
| Note: Released By: SKNOPF Approved for Release. Revision: Revised circuits and load calculations. | |||
| ELEC | HOLD | 09/12/2008 | 09/12/2008 |
| Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Revision to Permit #2008020012 (Sandwich Shop @ 160 Cypress Point Pkwy) 9/12/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. E-1: a. Location of circuits A-9 (Sign) and B-15 (Telephone) are not shown on plan, but circuit identification appears in panel schedule. Coordinate. b. Circuit A-13, Insta-Hot, is shown in panel schedule, but location is not shown on plan. c. The following appliances do not appear in the load calculations: 1) A-13 Insta-Hot 2) B-1 Prep Refrigerator d. Load Calculation shows both Deli Case (1500VA) and Pastry Case (1500VA), but the Pastry Case circuit is not shown in panel schedule, nor is location of Pastry Case shown on plans. Coordinate. e. Identify the size (amps) of all circuit breakers greater than 20A. These should include the following items: 1) A-29:31:33 Sub-panel B 2) A-15:17, A-19:21, A-23:25 Air Handlers (3) 3) A-16:18, A-20,22, A-24:26 Cond. Units (3) 4) A-32 Refrigerator (2200VA, 120V) 5) A-34 Refrigerator (2200VA, 120V) 6) A-42 Ice Machine (2000VA, 120V) 7) B-5 Dishwasher (3300VA, 120V) 8) A-36:38:40 Oven (8000VA, 208V 3Ph) f. Load shown in Load calculation for Soft Drink Machine on circuit B-3, is shown as 1920VA, but 2 additional duplex receptacles are shown on same circuit. Either revise load of Soft Drink Machine to reflect actual nameplate load, or separate the 2 duplex receptacles onto a different circuit so that circuit complies with NEC 422. g. Identify feeder conductor size to Sub-panel B. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us | |||
| ELEC | COMPLETE | 07/16/2008 | 07/16/2008 |
| Note: Released By: SKNOPF Approved for Release. | |||
| ZON | COMPLETE | 07/16/2008 | 07/16/2008 |
| Note: Released By: BBARTON modification approved 07/16/08 allowing restaurant use inthis building routed to Building Department | |||
| ELEC | HOLD | 04/16/2008 | 04/16/2008 |
| Note: Called left message about permit on hold -6/17/08 Lmusgrove also - emailed comments again Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application #2008020012 (Sandwich Shop Units B101 & B102 @ 160 Cypress Point Pkwy) 4/16/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: a. Original plans are signed and sealed, so all corrections and any future revisions must be signed and sealed. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us | |||
| ELEC | HOLD | 03/03/2008 | 03/04/2008 |
| Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application #2008020012 (Buildout of Sandwich Shop-Bldg B @ 160 Cypress Point Pkwy) 3/4/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. Sheet E-1: a. 2P circuit 21,23 is shown in (2) different locations for Hot Food Wells. Hot Food Wells are shown as having a load of 14.4A each set. Both sets of Hot Food Wells cannot be on the same 2P20A circuit breaker, since the combined load exceeds the limitations of the circuit breaker. Review and revise. b. Ice Machine listed in 120V dedicated equipment list is not shown for location on plan sheet, and it's circuit breaker is not listed in the panel schedule. Identify location of Ice Machine and add Ice Machine circuit breaker to panel. c. (3) Prep Tables, (1) @ 4.6A, (1) @ 10.5A, and (1) @ 8.6A (total 23.7A) are listed in the 120V Dedicated Equipment list but none are shown on the floor plan, and only (1) 20A circuit breaker is allotted in the panel schedule. Identify location of all (3) Prep Tables and revise panel circuiting to within limits of circuit breaker. d. Circuit 17 and 18 are shown in panel schedule as Deli Case, but are not listed in 120V Dedicated Equipment list. Sheet H-1 shows these same locations as Sandwich Prep Tables. Confirm whether circuits 17 and 18 are for "Deli Case" or "Sandwich Prep Table", and coordinate and revise Equipment List and Panel Schedule to match. e. Existing plans on file under Permit #2005060988 show that there are (4) existing circuits dedicated for show windows which do not appear on the panel schedule. Floor plan on E-1 shows there are 40', not 30' of show windows. Revise load calculation to reflect correct show window length and add circuits to panel schedule. f. 120V Dedicated Equipment loads shown under Design Information calculate to more than the load shown in Load Calculation. Please review and revise 120V Dedicated Equipment load shown in Load Calculations. g. 208V Dedicated Equipment loads shown under Design Information calculate to more than the load shown in Load Calculation. Please review and revise 208V Dedicated Equipment load shown in Load Calculations. h. Existing plans on file under Permit #2005060988 show that existing Condensing Units are all 3P circuit breakers fed with 3 phase circuits. Your panel schedule has all (3) Condensing Units as 2P circuit breakers. Please confirm # poles of condensing units and revise panel schedule as required. i. Riser does not reflect relocation of Panelboard or extension of feeder. Revise Riser to show how existing feeder is to be extended or replaced, and relocation of existing panel. j. Total Demand Load still appears to exceed the 200A maximum limitation of the existing panel size. Please review existing panel schedule on plans filed under permit #2005060988 for panel size. Revise panel and panel feeders as required to meet minimum demand shown in revised load calculations. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us | |||
| PLUM | HOLD | 03/03/2008 | 03/03/2008 |
| Note: Held By: JJOSEPH plum. revision 1. Provide domestic water distribution layout and riser diagram including pipe sizes and connection to existing domestic water system. 2. Provide specifications of electric water heater. | |||
| MECH | COMPLETE | 03/03/2008 | 03/03/2008 |
| Note: Released By: JJOSEPH a/c revisions | |||
| BLD | COMPLETE | 02/29/2008 | 03/03/2008 |
| Note: Released By: JJOSEPH | |||
| FI1 | REJECT | 02/20/2008 | 02/26/2008 |
| Note: Rejected By: JPATTEE No plans will be reviewed until automatic fire sprinkler system issue is resolved JDP | |||
| MECH | HOLD | 02/19/2008 | 02/19/2008 |
| Note: Held By: FREODICA 1. Provide duct layout of exhaust air from the new bathroom showing duct size and cfm.. 2. Provide exhaust fan specifications. | |||
| PLUM | HOLD | 02/19/2008 | 02/19/2008 |
| Note: 1. Provide sanitary and vent layout and riser diagram for the new bathroom including the pipe sizes and conection to the existing sanitary system. 2. Provide domestic water distribution layout and riser diagram including pipe sizes and connection to existing domestic water system. 3. Provide specifications of electric water heater. 4. Provide complete grease line layout including but not limited to location of floor sinks serving food service equipments, all fixtures shown on plan and pipe sizes up to grease trap and show how it is tied-in to the existing sanitary line. | |||
| UD1 | HOLD | 02/19/2008 | 02/25/2008 |
| Note: Held By: CJOHNSON The restroom toilet and sink should not be connected to the grease line. sent to Chris Johnson 02/19/08 ecoyne | |||
| BLD | HOLD | 02/18/2008 | 02/19/2008 |
| Note: Held By: FREODICA Sheet A-1: 1. Door No.3 does not match with the detail shown on sheet A-2. 2. Dining area shall be provided with at least five (5) percent of dining table for accessibility per FBC 2006 supplements, Section 11-5.1. 3. Provide detail elevations of salad bar, beverage counter and sandwitch preparation table to comply with FBC 2006 supplements, Section 11-5.5. 4. Provide HVAC subcontactor name, address and license number. 5. Please be reminded that the permit application can not be released until the shell building is completely issued with certificate of occupancy. | |||
| ELEC | HOLD | 02/18/2008 | 02/18/2008 |
| Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application #2008020012 (New Construction & Buildout for Sandwich Shop Tenant B101/B102 @ 160 Cypress Point Pkwy) 2/18/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. Sheet E-1: a. Furnish circuit numbers and identify whether receptacles are new or existing on Electrical Floor Plan for all receptacles and appliances shown. b. Revise lighting loads in Panel Schedule to reflect new recessed fixtures shown Sheet A-2. Identify Load (VA) for all new fixtures. c. Revise Panel Schedule to reflect all circuit breaker poles, amps, and load (VA) on each phase for both existing and new circuits. d. Existing documentation shows that existing panel is a 200A panel, not a 225A panel as shown on E-1. Review and revise. e. Sheet H-1 shows a convection oven, (2) hot food wells, and an ice maker that are not listed on the appliances list, or on the Panel Schedule. Review and revise. f. Please refer to existing Permit #2005060988 for Shell Building available on our website at "www.ci.palm-coast.fl.us". To access this permit on our site go to "Public Records Search"…"Launch Records Search"…enter "2005060988". View scanned document dated 6-20-2006. These existing plans show a significantly higher existing load and quantity of circuits in this unit than what is depicted in the panel schedule and load calculation submitted. For instance, the plans on file indicate that there is a third AHU and CU for Unit B101/B102. Revise load calculations to reflect both existing and new actual loads. Recommend use of either NEC 220.88 or NEC 220.56 for your revised load calculations. g. Proposed location of water heater violates NEC 110.26 for area in front of and above electrical panel. Review and revise. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us | |||
| ZON | HOLD | 02/13/2008 | 02/13/2008 |
| Note: Held By: ECOYNE restaurants allowed on 2nd floor 2,446 sq ft restaurant (l,168 sq ft eating area) | |||
| UD1 | HOLD | 02/13/2008 | 02/15/2008 |
| Note: Held By: CJOHNSON All hand sinks in the food prep areas and the dishwasher should connect to the grease line. Label the slope and pipe size on the grease line | |||
| ZON | HOLD | 02/01/2008 | 02/04/2008 |
| Note: Held By: ECOYNE Need sq ft of seating area to determine parking requirements | |||
| UD1 | COMPLETE | 04/04/2008 | |
| Note: Released By: CJOHNSON Held By: CJOHNSON Held By: CJOHNSON Held By: CJOHNSON The hand sink in the food prep area is still not connected to the grease line | |||
| UD1 | COMPLETE | 04/15/2008 | |
| Note: Released By: CJOHNSON | |||
| FI1 | COMPLETE | 04/03/2008 | |
| Note: Released By: JPATTEE | |||
| PLUM | COMPLETE | 03/11/2008 | |
| Note: Released By: JMCGOWEN |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REVISION | ¤80.00 | 09/29/2008 |
| TRANSPORTATION IMPACT FEE | ¤28,790.17 | 07/17/2008 |
| ADMIN FEE | ¤20.00 | 07/17/2008 |
| ELECTRIC FEE | ¤60.00 | 07/17/2008 |
| FIRE PLANS REVIEW | ¤25.00 | 07/17/2008 |
| PERMIT FEE | ¤370.00 | 07/17/2008 |
| PLAN CHECK FEE | ¤100.00 | 07/17/2008 |
| PLUMBING FEE | ¤60.00 | 07/17/2008 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤29,505.17 |