Permit #2008040158
Permit Details
Status: COED
| Parcel Id: 07-11-31-7009-RP A -0000 |
| COMMERCIAL SQUARE FOOTAGE: 5222 sqft |
| Total Square Footage: 5222 sqft |
| Block: RP A |
| Subdivision: - |
| Job Phone: (321)723-5661 |
| Location Address: 1755 PALM HARBOR PKWY |
| Type: BC - BUILDING COMMERCIAL |
| Issue Date: 06/25/2008 |
| NOC: RECORDED |
| Applicant name: LUKE MIORELLI |
| Owner: PALM COAST PETRO INC |
|
Address 4900 ST ROAD 524 COCOA, FL 32926 |
| Lot: 0000 |
| Contracted Stated Job Value: ¤550,000.00 |
| Job Description: CONVENIENCE STORE - GAS STATION W/ 2 RETAIL STORES- SP-WVR-07-26 |
| Type: CN |
Contractor
ME CONSTRUCTION INC.
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
7607 CORAL DRIVE WEST MELBOURNE, FL 32904 |
CGC019528 (Exp: 08/31/2020) | 321-723-5661 | (321)951-1952 |
Sub Contractors
MORGAN W RAYMOND
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
996 CAROLINA CIRCLE TITUSVILLE, FL 32796 |
EC13001231 (Exp: 08/31/2010) | (321)269-7240 | (321)269-7421 |
JACK DOUGLAS LANIER
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
485 COMMERCE WAY LONGWOOD , FL 32750 |
CCC058022 (Exp: 08/31/2026) | (321)441-2300 | (321)441-2313 |
JONATHAN M PEARSON
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
209 N FORSYTH ST BUNNELL, FL 32110 |
CFC1425941 (Exp: 08/31/2026) | 386-597-0944 | 386-437-4996 |
WALTER CLAY DAVIS JR
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
2762 TURNBULL BAY RD NEW SMYRNA BEACH, FL 32158 |
CAC1813339 (Exp: 08/31/2016) | 386-428-3700 | 385-428-2400 |
Inspection History
| Type | Request Date | Result | Inspector |
| UTILITY COMMERCIAL FINAL | 01/14/2009 | APPROVED | KKING |
| Note: THIS IS A REINSPECTION | |||
| ELECTRICAL FINAL | 01/13/2009 | APPROVED | RMARVEL |
| LANDSCAPE FINAL | 01/12/2009 | APPROVED | WBUTLER |
| Note: THIS IS A REINSPECTION | |||
| COMMERCIAL BUILDING FINAL | 01/09/2009 | FINAL APPROVED | CMINI |
| Note: THIS IS A REINSPECTION | |||
| UTILITY COMMERCIAL FINAL | 01/07/2009 | Disapproved - NO FEE | KKING |
| Note: All condisions of the Utility Developer agreement have not been met | |||
| UTILITY COMPANY FINAL | 01/07/2009 | APPROVED | KKING |
| ENGINEERING FINAL | 01/07/2009 | APPROVED | KHOWELL |
| TRAFFIC ENGINEER | 01/07/2009 | APPROVED | KHOWELL |
| COMMERCIAL BUILDING FINAL | 01/07/2009 | Disapproved -FEE REQUIRED | JMCGOWEN |
| Note: Inspection Resulted at 1/7/2009 3:14:49 PM NEED CHECK VALVE ON COLD WATER SIDE OF WATER HEATER.RAISE ICE MACHINE DRIAN GAP. | |||
| FIRE FINAL | 01/07/2009 | APPROVED | JLEWIS |
| INSULATION INSPECTION | 01/07/2009 | APPROVED | JMCGOWEN |
| ELECTRICAL FINAL | 01/07/2009 | APPROVED | RMARVEL |
| H.V.A.C. FINAL | 01/07/2009 | APPROVED | JMCGOWEN |
| Note: THIS IS A REINSPECTION | |||
| ELECTRICAL FINAL | 12/23/2008 | Disapproved -FEE REQUIRED | RMARVEL |
| Note: A few punchlist items need to be addressed concerning the landscape and irrigation of the site. Also, two sets of signed and sealed as-built drawings need to be provided at the time of the next inspection. Bill Butler 12/23/08 Inspection Resulted at 12/23/2008 3:13:06 PM REVISE DRAWINGS TO SHOW CURRENT CIRCUIT DIRECTORY, NEUTRAL SHUNT, RECEPTACLE LOCATIONS. DISCONNECTS NEED TO MEET 36IN CLEARANCE IN FRONT. | |||
| H.V.A.C. FINAL | 12/23/2008 | Disapproved -FEE REQUIRED | LWOODROME |
| Note: THIS IS A REINSPECTION Inspection Resulted at 12/23/2008 2:59:40 PM 1.. REVISE LOCATION OF FAI AND EXHAUST...10`` SEPARATION REQUIRED... 2... PROVIDE WORKING CLEARANCE ON SERVICE SIDE OF A/H UNIT IN ATTIC AREA.... | |||
| LANDSCAPE FINAL | 12/23/2008 | PARTIALLY APPROVED | WBUTLER |
| Note: Several punch list items remain concerning landscaping and irrigation. Also two signed and sealed sets of as-built drawings for same must be submitted prior to the reinspection. Bill Butler 12/23/08 | |||
| TRAFFIC ENGINEER | 12/08/2008 | APPROVED | KHOWELL |
| PLUMBING FINAL | 12/08/2008 | APPROVED | JHINDMAN |
| Note: THIS IS A REINSPECTION | |||
| COMMERCIAL POWER INSPECTION | 12/05/2008 | APPROVED | LHITES |
| Note: THIS IS A REINSPECTION | |||
| ELECTRIC FEEDER | 12/05/2008 | APPROVED | LHITES |
| Note: THIS IS A REINSPECTION Approved per Larry Hites | |||
| ELECTRIC FEEDER | 12/04/2008 | Disapproved -FEE REQUIRED | LHITES |
| Note: THIS IS A REINSPECTION Inspection Resulted at 12/4/2008 1:53:11 PM GROUND MUST BE THROUGH BOLTED NOT SELF TAPPED SCREW. MUST HAVE TORQUE WRENCH FOR NEXT INSPECTION. | |||
| COMMERCIAL POWER INSPECTION | 12/04/2008 | Disapproved -FEE REQUIRED | LHITES |
| Note: THIS IS A REINSPECTION Inspection Resulted at 12/4/2008 1:53:11 PM NOT READY | |||
| ELECTRIC FEEDER | 12/02/2008 | Disapproved -FEE REQUIRED | RMARVEL |
| Note: Inspection Resulted at 12/2/2008 3:41:09 PM NEED ELECTRICIAN WITH A TORQUE WRENCH. | |||
| COMMERCIAL POWER INSPECTION | 12/02/2008 | Disapproved -FEE REQUIRED | RMARVEL |
| Note: Inspection Resulted at 12/2/2008 3:41:09 PM NEED AN ELECTRICIAN WITH A TORQUE WRENCH. | |||
| PLUMBING FINAL | 11/25/2008 | Disapproved -FEE REQUIRED | JMCGOWEN |
| Note: Inspection Resulted at 11/25/2008 3:51:27 PM NEED REVISION FOR LOCATION OF WATER HEATER. | |||
| H.V.A.C. FINAL | 11/25/2008 | CANCELLED BY APPLICANT | JMCGOWEN |
| ABOVE CEILING | 11/25/2008 | APPROVED | RMARVEL |
| Note: THIS IS A REINSPECTION | |||
| ABOVE CEILING | 11/06/2008 | Disapproved -FEE REQUIRED | JMCGOWEN |
| Note: Inspection Resulted at 11/6/2008 11:21:44 AM 1. NEED REVISION FOR DUCT AND AIR HANDLER LOCATIONS 2. RESTRAP MC INDEPENDANTLY FROM GRID SUPPORTS. 3. STRAP MC INDEPENDANTLY FROM OTHER CABLES OR RACEWAYS. | |||
| 2ND ROUGH ELECTRICAL | 10/01/2008 | APPROVED | LHITES |
| Note: THIS IS A REINSPECTION | |||
| FIREWALL INSPECTION | 10/01/2008 | APPROVED - AS NOTED | JPATTEE |
| Note: Remud wall to cover tape (east wall) | |||
| ROOF IN PROGRESS | 09/29/2008 | APPROVED | DROCKWELL |
| Note: THIS IS A REINSPECTION | |||
| ROOF IN PROGRESS | 09/25/2008 | Disapproved -FEE REQUIRED | DROCKWELL |
| Note: Inspection Resulted at 9/25/2008 3:09:11 PM NOT READY FOR INSPECTION | |||
| 2ND ROUGH ELECTRICAL | 09/25/2008 | Disapproved -FEE REQUIRED | LHITES |
| Note: Inspection Resulted at 9/25/2008 3:10:58 PM REPLACE DAMAGED WIRE NUTS. THE WIRE NUTS WERE OVER TIGHTENED. MOVE A/H WIRE FROM BEHIND UNITS. MOVE SERVICE OUTLET FROM BEHIND DUCT WORK | |||
| FRAMING | 09/25/2008 | APPROVED | DROCKWELL |
| Note: THIS IS A REINSPECTION | |||
| H.V.A.C. ROUGH | 09/25/2008 | APPROVED - AS NOTED | JMCGOWEN |
| Note: Inspection Resulted at 9/25/2008 1:02:53 PM NEED REVISION ON CHANGE OF RETURN AIR AND AHU-2 AND MASTIC EXPOSED TAPE ON JOINTS..HAVE BY ABOVE CEILING INSPECTION. | |||
| SECOND ROUGH PLUMBING INSPECTION | 09/25/2008 | APPROVED | PGALLMANN |
| FRAMING | 09/10/2008 | PARTIALLY APPROVED | DROCKWELL |
| Note: Inspection Resulted at 9/10/2008 11:36:28 AM DRAFT STOP ABOVE CEILING | |||
| ROOF SHEATHING/BRACES/TIES/ DOWN CELL | 08/27/2008 | APPROVED | DROCKWELL |
| FOUNDATION SURVEY APPROVED BY ZONING | 08/08/2008 | APPROVED | DRAMIREZ |
| Note: Reviewed with Project Manager, Larry Torino. As per Larry Foundation Survey is approved. | |||
| LINTEL | 08/05/2008 | APPROVED | CMINI |
| Note: THIS IS A REINSPECTION | |||
| LINTEL | 08/04/2008 | CANCELLED BY APPLICANT | JEANNE |
| Note: Bo called to schedule this inspection | |||
| MONOLITHIC SLAB INSPECTION/SLAB | 07/30/2008 | APPROVED | CMINI |
| FIRST ROUGH PLUMBING INSPECTION | 07/28/2008 | APPROVED | PGALLMANN |
| FOOTER | 07/23/2008 | CANCELLED BY APPLICANT | DROCKWELL |
| TEMPORARY POLE | 07/22/2008 | APPROVED | RMARVEL |
| Note: requested by contractor MORGAN AND LYNCH ELECTRICAL |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 01/06/2009 | 01/06/2009 |
| Note: Released By: SKNOPF Approved for Release. Revision: Added shunted disconnect to kill neutral & 1Ph 240V circuits Changed ice maker to 120 volt | |||
| MECH | COMPLETE | 11/24/2008 | 11/24/2008 |
| Note: Released By: FREODICA 1. Revision: Relocated AHU'S and changed ductwork. | |||
| MECH | HOLD | 10/15/2008 | 10/15/2008 |
| Note: Held By: FREODICA Revision hold: 1. Plan shows (2) CFM's for each supply diffuser and (2) sizes for each flexible duct. Please clarify. | |||
| ELEC | COMPLETE | 10/03/2008 | 10/06/2008 |
| Note: Released By: SKNOPF Approved for Release. Revision: Changed Electrical Service. Updated Load Calculations. Added receptacles. Added 600A Manual Transfer Switch. | |||
| ELEC | HOLD | 09/26/2008 | 09/26/2008 |
| Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Revision to Permit #2008040158 (Convenience Store-Gas Station @ 1755 Palm Harbor Pkwy.) 9/26/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. E-2: a. Identify circuits and loads for 3 new receptacles located on wall behind service counter. b. Identify circuit for new receptacle located at phone board. c. Revised Electrical Riser Diagram now shows trough feeding new 100A Panel 'D'. Provide Panel Schedule and Electrical Load Summary for this Panel 'D'. d. Identify size of grounding electrode conductor per NEC Table 250.66. e. Identify Transfer Switch as Automatic or Manual. Provide manufacturer specifications for Transfer Switch. f. Feeder from 600A Service Disconnect to new 600A Transfer Switch shows only 1 set of #500 (380A). Revise feeder size to meet total demand of Panels A, B, C and D. g. Equipment grounding conductor is undersized for the feeders between the 600A Disconnect and the Transfer Switch, and the Transfer Switch and the trough per NEC 250.122(F). …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us | |||
| UD1 | COMPLETE | 04/30/2008 | 05/01/2008 |
| Note: Released By: CJOHNSON | |||
| MECH | COMPLETE | 04/29/2008 | 04/29/2008 |
| Note: Released By: FREODICA | |||
| PLUM | COMPLETE | 04/29/2008 | 04/29/2008 |
| Note: Released By: FREODICA | |||
| ELEC | COMPLETE | 04/29/2008 | 04/29/2008 |
| Note: Released By: SKNOPF Approved for Release. | |||
| BLD | COMPLETE | 04/28/2008 | 04/29/2008 |
| Note: Released By: JJOSEPH correction | |||
| UD1 | HOLD | 04/22/2008 | 04/22/2008 |
| Note: Held By: CJOHNSON Remove the future grease line connection to the proposed retail unit. If the future retail unit requires a grease interceptor it shall have it's own interceptor. | |||
| FI1 | COMPLETE | 04/18/2008 | 04/22/2008 |
| Note: Released By: JPATTEE | |||
| MECH | HOLD | 04/18/2008 | 04/18/2008 |
| Note: Held By: FREODICA 1. Revise the amount of air supplied (CFM) from each supply diffuser as almost all of them show (2) CFM values. 2. Provide specifications of toilet exhaust fans. 3. Provide duct size, CFM and louver size of toilet exhaust air. 4. Provide duct sizes and louver size of fresh air intake to the AHU(s). 5. Indicate on Horizontal Air Handler Detail how it is supported. | |||
| PLUM | HOLD | 04/18/2008 | 04/18/2008 |
| Note: Held By: FREODICA 1. Floor drain for Men's Toilet is missing on Sanitary Riser Diagram. 2. Water heater and janitor sink are both marked as P7 on Plumbing Fixture Schedule. Please Clarify. 3. The plan shows both water heater and janitor sink are located in the same location but the Water Heater Detail does not show where the janitor sink is. Please clarify. 3. The Water Heater Detail indicates referenced code section 504.8.2 for drain discharge but that reference code can not be found in the Florida Plumbing Code 2004. Please clarify. 4. The water heater capacity on Energy Calculations shows 40 gallon but on Equipment Schedule (sheet A-1) shows 6 gallon only. Please clarify. 5. Provide Domestic Water Riser Diagram. | |||
| ELEC | HOLD | 04/16/2008 | 04/16/2008 |
| Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application #2008040158 (Palm Coast C Store & Retail @ 1755 Palm Harbor Pkwy) 4/16/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. E-1: a. Identify circuit(s) on Lighting plan for canopy. b. No Emergency lighting shown in Public areas. Provide emergency lighting per NEC Art 700. 2. E-2: a. (3) receptacles in Cashier area need circuit identified. Identify circuit and add load into panel. b. (1) receptacle in Stockroom for telephone board needs a circuit identified. c. Electrical Panels are not identified. d. Provide Demand Load Calculations per NEC Art 220 for all 3 electrical panels. e. Panel 'A' schedule shows panel is 225A. Electrical Riser shows panel is 300A. Please coordinate. f. Panel 'C' schedule shows panel is 150A. Electrical Riser shows panel is 200A. Please coordinate. g. Circuit B-40, 42 Water Heater shown on M-1 as a Rheem EGSP20 which is listed with a maximum wattage of 6000W. Panel schedule shows load of 4500W. Please review and revise. h. Receptacle in Stockroom on circuit A-2 for Box/Bag. Circuit A-2 is listed as soffit lights in panel schedule. i. Circuit B-26 and B-28 Hand Dryers have no load shown in panel. j. Receptacle on circuit A-6 is located as service receptacle for AHU-2 above ceiling. Panel schedule lists A-6 as Bill changer. k. Receptacle on circuit A-13 is located as service receptacle for AHU-1 above ceiling. Panel schedule lists A-13 as charcoal filter. l. Circuits B-10 and B-12 for coffee receptacle each show a duplex receptacle on 20A 1P circuit breakers, but with 3200W which yields 27A. m. Power Plan shows 5 sets of Door Heaters and Lights for the 3 Coolers, but only 4 pairs of circuits are shown in Panel 'B' for these loads. n. Electrical Riser Diagram shows Panel B feeding Panel C, but no circuit breaker is shown for Panel C in Panel B. o. Provide Wiring Trough and Meter/CT location on Power Plan. p. Circuit A-38, 40 is shown for a duplex receptacle and identified in the panel as reclaim control, but there is no circuit breaker or load identified for these circuits. q. The following circuits have undersized loads: A-3, 5, 7, and 11. r. The following circuits are shown in the panel schedule but are not located on the Electrical plans: 1) A-5, 9, 13, 14, 16, 17, 18, 19:21, 24, 30, 35, 37 2) B-3, 5 s. Circuits A-15, B-31, and B-33 show loads in their respective panels but have no description listed, nor are found on the Electrical plan sheets. Please review and revise. t. Electrical Riser shows the grounding electrode conductor and the grounding electrode located ahead of the CT/Meter. Please review and revise. u. Provide grounding electrode conductor size per NEC Table 250.66. v. Identify individual feeder conductor and conduit sizes for Panels A, B and C on Electrical Riser. 3. E-3: a. Identify Site circuit locations on Site Electrical Plan for all electrical loads. b. Identify Site Fixtures including maximum wattage for load calculation verification. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us | |||
| BLD | HOLD | 04/15/2008 | 04/18/2008 |
| Note: Held By: JJOSEPH 1. Provide wall sections details. 2. Identify the space reserved (both side) for future use. 3 Provide opening protection. 4. Please revise the orientation and fixe the elevation to comply with our hour. 5. Revise the electrical code NEC 2002 to NEC2005. | |||
| ZON | COMPLETE | 04/15/2008 | 04/15/2008 |
| Note: Released By: BBARTON recieved site plan via mail and approved | |||
| ZON | HOLD | 04/08/2008 | 04/08/2008 |
| Note: Held By: BBARTON please provide site plan for review emailed and faxed contractor hold comment 04/08/08 @ 3:51pm |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 01/15/2009 |
| REINSPECTION FEE | ¤40.00 | 01/07/2009 |
| REINSPECTION FEE | ¤40.00 | 01/07/2009 |
| REINSPECTION FEE | ¤40.00 | 01/07/2009 |
| REVISION | ¤80.00 | 01/07/2009 |
| REVISION | ¤40.00 | 01/07/2009 |
| REVISION | ¤40.00 | 01/07/2009 |
| ADDITIONAL FEE | ¤40.00 | 01/07/2009 |
| ADDITIONAL FEE | ¤40.00 | 01/07/2009 |
| REINSPECTION FEE | ¤40.00 | 01/07/2009 |
| REINSPECTION FEE | ¤40.00 | 01/07/2009 |
| REINSPECTION FEE | ¤40.00 | 01/07/2009 |
| REINSPECTION FEE | ¤40.00 | 01/07/2009 |
| REINSPECTION FEE | ¤40.00 | 01/07/2009 |
| REINSPECTION FEE | ¤40.00 | 01/07/2009 |
| REINSPECTION FEE | ¤40.00 | 01/07/2009 |
| ADMIN FEE | ¤20.00 | 06/25/2008 |
| BUILDING CODE ADMIN FUND | ¤26.11 | 06/25/2008 |
| ELECTRIC FEE | ¤360.00 | 06/25/2008 |
| FIRE COMM IMPACT FEE 4/1/07 | ¤267.89 | 06/25/2008 |
| FIRE PLANS REVIEW | ¤52.22 | 06/25/2008 |
| MECHANICAL FEE | ¤360.00 | 06/25/2008 |
| PERMIT FEE | ¤3,025.00 | 06/25/2008 |
| PLAN CHECK FEE | ¤632.50 | 06/25/2008 |
| PLUMBING FEE | ¤360.00 | 06/25/2008 |
| RADON FEE | ¤26.11 | 06/25/2008 |
| TRANSPORTATION IMPACT FEE | ¤71,537.64 | 06/25/2008 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤77,347.47 |