Permit #2008040158

Permit Details

Status: COED

Parcel Id: 07-11-31-7009-RP A -0000
COMMERCIAL SQUARE FOOTAGE: 5222 sqft
Total Square Footage: 5222 sqft
Block: RP A
Subdivision: -
Job Phone: (321)723-5661
Location Address: 1755 PALM HARBOR PKWY
Type: BC - BUILDING COMMERCIAL
Issue Date: 06/25/2008
NOC: RECORDED
Applicant name: LUKE MIORELLI
Owner: PALM COAST PETRO INC

Address

4900 ST ROAD 524

COCOA, FL 32926

Lot: 0000
Contracted Stated Job Value: ¤550,000.00
Job Description: CONVENIENCE STORE - GAS STATION W/ 2 RETAIL STORES- SP-WVR-07-26
Type: CN

Contractor

ME CONSTRUCTION INC.
Status Location Address State License Number Phone Fax
INACTIVE

7607 CORAL DRIVE

WEST MELBOURNE, FL 32904

CGC019528 (Exp: 08/31/2020) 321-723-5661 (321)951-1952

Sub Contractors

MORGAN W RAYMOND
Status Location Address State License Number Phone Fax
CANCEL

996 CAROLINA CIRCLE

TITUSVILLE, FL 32796

EC13001231 (Exp: 08/31/2010) (321)269-7240 (321)269-7421
JACK DOUGLAS LANIER
Status Location Address State License Number Phone Fax
ACTIVE

485 COMMERCE WAY

LONGWOOD , FL 32750

CCC058022 (Exp: 08/31/2026) (321)441-2300 (321)441-2313
JONATHAN M PEARSON
Status Location Address State License Number Phone Fax
ACTIVE

209 N FORSYTH ST

BUNNELL, FL 32110

CFC1425941 (Exp: 08/31/2026) 386-597-0944 386-437-4996
WALTER CLAY DAVIS JR
Status Location Address State License Number Phone Fax
CANCEL

2762 TURNBULL BAY RD

NEW SMYRNA BEACH, FL 32158

CAC1813339 (Exp: 08/31/2016) 386-428-3700 385-428-2400

Inspection History

Type Request Date Result Inspector
UTILITY COMMERCIAL FINAL 01/14/2009 APPROVED KKING
Note: THIS IS A REINSPECTION
ELECTRICAL FINAL 01/13/2009 APPROVED RMARVEL
LANDSCAPE FINAL 01/12/2009 APPROVED WBUTLER
Note: THIS IS A REINSPECTION
COMMERCIAL BUILDING FINAL 01/09/2009 FINAL APPROVED CMINI
Note: THIS IS A REINSPECTION
UTILITY COMMERCIAL FINAL 01/07/2009 Disapproved - NO FEE KKING
Note: All condisions of the Utility Developer agreement have not been met
UTILITY COMPANY FINAL 01/07/2009 APPROVED KKING
ENGINEERING FINAL 01/07/2009 APPROVED KHOWELL
TRAFFIC ENGINEER 01/07/2009 APPROVED KHOWELL
COMMERCIAL BUILDING FINAL 01/07/2009 Disapproved -FEE REQUIRED JMCGOWEN
Note: Inspection Resulted at 1/7/2009 3:14:49 PM NEED CHECK VALVE ON COLD WATER SIDE OF WATER HEATER.RAISE ICE MACHINE DRIAN GAP.
FIRE FINAL 01/07/2009 APPROVED JLEWIS
INSULATION INSPECTION 01/07/2009 APPROVED JMCGOWEN
ELECTRICAL FINAL 01/07/2009 APPROVED RMARVEL
H.V.A.C. FINAL 01/07/2009 APPROVED JMCGOWEN
Note: THIS IS A REINSPECTION
ELECTRICAL FINAL 12/23/2008 Disapproved -FEE REQUIRED RMARVEL
Note: A few punchlist items need to be addressed concerning the landscape and irrigation of the site. Also, two sets of signed and sealed as-built drawings need to be provided at the time of the next inspection. Bill Butler 12/23/08 Inspection Resulted at 12/23/2008 3:13:06 PM REVISE DRAWINGS TO SHOW CURRENT CIRCUIT DIRECTORY, NEUTRAL SHUNT, RECEPTACLE LOCATIONS. DISCONNECTS NEED TO MEET 36IN CLEARANCE IN FRONT.
H.V.A.C. FINAL 12/23/2008 Disapproved -FEE REQUIRED LWOODROME
Note: THIS IS A REINSPECTION Inspection Resulted at 12/23/2008 2:59:40 PM 1.. REVISE LOCATION OF FAI AND EXHAUST...10`` SEPARATION REQUIRED... 2... PROVIDE WORKING CLEARANCE ON SERVICE SIDE OF A/H UNIT IN ATTIC AREA....
LANDSCAPE FINAL 12/23/2008 PARTIALLY APPROVED WBUTLER
Note: Several punch list items remain concerning landscaping and irrigation. Also two signed and sealed sets of as-built drawings for same must be submitted prior to the reinspection. Bill Butler 12/23/08
TRAFFIC ENGINEER 12/08/2008 APPROVED KHOWELL
PLUMBING FINAL 12/08/2008 APPROVED JHINDMAN
Note: THIS IS A REINSPECTION
COMMERCIAL POWER INSPECTION 12/05/2008 APPROVED LHITES
Note: THIS IS A REINSPECTION
ELECTRIC FEEDER 12/05/2008 APPROVED LHITES
Note: THIS IS A REINSPECTION Approved per Larry Hites
ELECTRIC FEEDER 12/04/2008 Disapproved -FEE REQUIRED LHITES
Note: THIS IS A REINSPECTION Inspection Resulted at 12/4/2008 1:53:11 PM GROUND MUST BE THROUGH BOLTED NOT SELF TAPPED SCREW. MUST HAVE TORQUE WRENCH FOR NEXT INSPECTION.
COMMERCIAL POWER INSPECTION 12/04/2008 Disapproved -FEE REQUIRED LHITES
Note: THIS IS A REINSPECTION Inspection Resulted at 12/4/2008 1:53:11 PM NOT READY
ELECTRIC FEEDER 12/02/2008 Disapproved -FEE REQUIRED RMARVEL
Note: Inspection Resulted at 12/2/2008 3:41:09 PM NEED ELECTRICIAN WITH A TORQUE WRENCH.
COMMERCIAL POWER INSPECTION 12/02/2008 Disapproved -FEE REQUIRED RMARVEL
Note: Inspection Resulted at 12/2/2008 3:41:09 PM NEED AN ELECTRICIAN WITH A TORQUE WRENCH.
PLUMBING FINAL 11/25/2008 Disapproved -FEE REQUIRED JMCGOWEN
Note: Inspection Resulted at 11/25/2008 3:51:27 PM NEED REVISION FOR LOCATION OF WATER HEATER.
H.V.A.C. FINAL 11/25/2008 CANCELLED BY APPLICANT JMCGOWEN
ABOVE CEILING 11/25/2008 APPROVED RMARVEL
Note: THIS IS A REINSPECTION
ABOVE CEILING 11/06/2008 Disapproved -FEE REQUIRED JMCGOWEN
Note: Inspection Resulted at 11/6/2008 11:21:44 AM 1. NEED REVISION FOR DUCT AND AIR HANDLER LOCATIONS 2. RESTRAP MC INDEPENDANTLY FROM GRID SUPPORTS. 3. STRAP MC INDEPENDANTLY FROM OTHER CABLES OR RACEWAYS.
2ND ROUGH ELECTRICAL 10/01/2008 APPROVED LHITES
Note: THIS IS A REINSPECTION
FIREWALL INSPECTION 10/01/2008 APPROVED - AS NOTED JPATTEE
Note: Remud wall to cover tape (east wall)
ROOF IN PROGRESS 09/29/2008 APPROVED DROCKWELL
Note: THIS IS A REINSPECTION
ROOF IN PROGRESS 09/25/2008 Disapproved -FEE REQUIRED DROCKWELL
Note: Inspection Resulted at 9/25/2008 3:09:11 PM NOT READY FOR INSPECTION
2ND ROUGH ELECTRICAL 09/25/2008 Disapproved -FEE REQUIRED LHITES
Note: Inspection Resulted at 9/25/2008 3:10:58 PM REPLACE DAMAGED WIRE NUTS. THE WIRE NUTS WERE OVER TIGHTENED. MOVE A/H WIRE FROM BEHIND UNITS. MOVE SERVICE OUTLET FROM BEHIND DUCT WORK
FRAMING 09/25/2008 APPROVED DROCKWELL
Note: THIS IS A REINSPECTION
H.V.A.C. ROUGH 09/25/2008 APPROVED - AS NOTED JMCGOWEN
Note: Inspection Resulted at 9/25/2008 1:02:53 PM NEED REVISION ON CHANGE OF RETURN AIR AND AHU-2 AND MASTIC EXPOSED TAPE ON JOINTS..HAVE BY ABOVE CEILING INSPECTION.
SECOND ROUGH PLUMBING INSPECTION 09/25/2008 APPROVED PGALLMANN
FRAMING 09/10/2008 PARTIALLY APPROVED DROCKWELL
Note: Inspection Resulted at 9/10/2008 11:36:28 AM DRAFT STOP ABOVE CEILING
ROOF SHEATHING/BRACES/TIES/ DOWN CELL 08/27/2008 APPROVED DROCKWELL
FOUNDATION SURVEY APPROVED BY ZONING 08/08/2008 APPROVED DRAMIREZ
Note: Reviewed with Project Manager, Larry Torino. As per Larry Foundation Survey is approved.
LINTEL 08/05/2008 APPROVED CMINI
Note: THIS IS A REINSPECTION
LINTEL 08/04/2008 CANCELLED BY APPLICANT JEANNE
Note: Bo called to schedule this inspection
MONOLITHIC SLAB INSPECTION/SLAB 07/30/2008 APPROVED CMINI
FIRST ROUGH PLUMBING INSPECTION 07/28/2008 APPROVED PGALLMANN
FOOTER 07/23/2008 CANCELLED BY APPLICANT DROCKWELL
TEMPORARY POLE 07/22/2008 APPROVED RMARVEL
Note: requested by contractor MORGAN AND LYNCH ELECTRICAL

Review History

Department Status Date In Date Out
ELEC COMPLETE 01/06/2009 01/06/2009
Note: Released By: SKNOPF Approved for Release. Revision: Added shunted disconnect to kill neutral & 1Ph 240V circuits Changed ice maker to 120 volt
MECH COMPLETE 11/24/2008 11/24/2008
Note: Released By: FREODICA 1. Revision: Relocated AHU'S and changed ductwork.
MECH HOLD 10/15/2008 10/15/2008
Note: Held By: FREODICA Revision hold: 1. Plan shows (2) CFM's for each supply diffuser and (2) sizes for each flexible duct. Please clarify.
ELEC COMPLETE 10/03/2008 10/06/2008
Note: Released By: SKNOPF Approved for Release. Revision: Changed Electrical Service. Updated Load Calculations. Added receptacles. Added 600A Manual Transfer Switch.
ELEC HOLD 09/26/2008 09/26/2008
Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Revision to Permit #2008040158 (Convenience Store-Gas Station @ 1755 Palm Harbor Pkwy.) 9/26/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. E-2: a. Identify circuits and loads for 3 new receptacles located on wall behind service counter. b. Identify circuit for new receptacle located at phone board. c. Revised Electrical Riser Diagram now shows trough feeding new 100A Panel 'D'. Provide Panel Schedule and Electrical Load Summary for this Panel 'D'. d. Identify size of grounding electrode conductor per NEC Table 250.66. e. Identify Transfer Switch as Automatic or Manual. Provide manufacturer specifications for Transfer Switch. f. Feeder from 600A Service Disconnect to new 600A Transfer Switch shows only 1 set of #500 (380A). Revise feeder size to meet total demand of Panels A, B, C and D. g. Equipment grounding conductor is undersized for the feeders between the 600A Disconnect and the Transfer Switch, and the Transfer Switch and the trough per NEC 250.122(F). …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us
UD1 COMPLETE 04/30/2008 05/01/2008
Note: Released By: CJOHNSON
MECH COMPLETE 04/29/2008 04/29/2008
Note: Released By: FREODICA
PLUM COMPLETE 04/29/2008 04/29/2008
Note: Released By: FREODICA
ELEC COMPLETE 04/29/2008 04/29/2008
Note: Released By: SKNOPF Approved for Release.
BLD COMPLETE 04/28/2008 04/29/2008
Note: Released By: JJOSEPH correction
UD1 HOLD 04/22/2008 04/22/2008
Note: Held By: CJOHNSON Remove the future grease line connection to the proposed retail unit. If the future retail unit requires a grease interceptor it shall have it's own interceptor.
FI1 COMPLETE 04/18/2008 04/22/2008
Note: Released By: JPATTEE
MECH HOLD 04/18/2008 04/18/2008
Note: Held By: FREODICA 1. Revise the amount of air supplied (CFM) from each supply diffuser as almost all of them show (2) CFM values. 2. Provide specifications of toilet exhaust fans. 3. Provide duct size, CFM and louver size of toilet exhaust air. 4. Provide duct sizes and louver size of fresh air intake to the AHU(s). 5. Indicate on Horizontal Air Handler Detail how it is supported.
PLUM HOLD 04/18/2008 04/18/2008
Note: Held By: FREODICA 1. Floor drain for Men's Toilet is missing on Sanitary Riser Diagram. 2. Water heater and janitor sink are both marked as P7 on Plumbing Fixture Schedule. Please Clarify. 3. The plan shows both water heater and janitor sink are located in the same location but the Water Heater Detail does not show where the janitor sink is. Please clarify. 3. The Water Heater Detail indicates referenced code section 504.8.2 for drain discharge but that reference code can not be found in the Florida Plumbing Code 2004. Please clarify. 4. The water heater capacity on Energy Calculations shows 40 gallon but on Equipment Schedule (sheet A-1) shows 6 gallon only. Please clarify. 5. Provide Domestic Water Riser Diagram.
ELEC HOLD 04/16/2008 04/16/2008
Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application #2008040158 (Palm Coast C Store & Retail @ 1755 Palm Harbor Pkwy) 4/16/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. E-1: a. Identify circuit(s) on Lighting plan for canopy. b. No Emergency lighting shown in Public areas. Provide emergency lighting per NEC Art 700. 2. E-2: a. (3) receptacles in Cashier area need circuit identified. Identify circuit and add load into panel. b. (1) receptacle in Stockroom for telephone board needs a circuit identified. c. Electrical Panels are not identified. d. Provide Demand Load Calculations per NEC Art 220 for all 3 electrical panels. e. Panel 'A' schedule shows panel is 225A. Electrical Riser shows panel is 300A. Please coordinate. f. Panel 'C' schedule shows panel is 150A. Electrical Riser shows panel is 200A. Please coordinate. g. Circuit B-40, 42 Water Heater shown on M-1 as a Rheem EGSP20 which is listed with a maximum wattage of 6000W. Panel schedule shows load of 4500W. Please review and revise. h. Receptacle in Stockroom on circuit A-2 for Box/Bag. Circuit A-2 is listed as soffit lights in panel schedule. i. Circuit B-26 and B-28 Hand Dryers have no load shown in panel. j. Receptacle on circuit A-6 is located as service receptacle for AHU-2 above ceiling. Panel schedule lists A-6 as Bill changer. k. Receptacle on circuit A-13 is located as service receptacle for AHU-1 above ceiling. Panel schedule lists A-13 as charcoal filter. l. Circuits B-10 and B-12 for coffee receptacle each show a duplex receptacle on 20A 1P circuit breakers, but with 3200W which yields 27A. m. Power Plan shows 5 sets of Door Heaters and Lights for the 3 Coolers, but only 4 pairs of circuits are shown in Panel 'B' for these loads. n. Electrical Riser Diagram shows Panel B feeding Panel C, but no circuit breaker is shown for Panel C in Panel B. o. Provide Wiring Trough and Meter/CT location on Power Plan. p. Circuit A-38, 40 is shown for a duplex receptacle and identified in the panel as reclaim control, but there is no circuit breaker or load identified for these circuits. q. The following circuits have undersized loads: A-3, 5, 7, and 11. r. The following circuits are shown in the panel schedule but are not located on the Electrical plans: 1) A-5, 9, 13, 14, 16, 17, 18, 19:21, 24, 30, 35, 37 2) B-3, 5 s. Circuits A-15, B-31, and B-33 show loads in their respective panels but have no description listed, nor are found on the Electrical plan sheets. Please review and revise. t. Electrical Riser shows the grounding electrode conductor and the grounding electrode located ahead of the CT/Meter. Please review and revise. u. Provide grounding electrode conductor size per NEC Table 250.66. v. Identify individual feeder conductor and conduit sizes for Panels A, B and C on Electrical Riser. 3. E-3: a. Identify Site circuit locations on Site Electrical Plan for all electrical loads. b. Identify Site Fixtures including maximum wattage for load calculation verification. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us
BLD HOLD 04/15/2008 04/18/2008
Note: Held By: JJOSEPH 1. Provide wall sections details. 2. Identify the space reserved (both side) for future use. 3 Provide opening protection. 4. Please revise the orientation and fixe the elevation to comply with our hour. 5. Revise the electrical code NEC 2002 to NEC2005.
ZON COMPLETE 04/15/2008 04/15/2008
Note: Released By: BBARTON recieved site plan via mail and approved
ZON HOLD 04/08/2008 04/08/2008
Note: Held By: BBARTON please provide site plan for review emailed and faxed contractor hold comment 04/08/08 @ 3:51pm

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION FEE ¤40.00 01/15/2009
REINSPECTION FEE ¤40.00 01/07/2009
REINSPECTION FEE ¤40.00 01/07/2009
REINSPECTION FEE ¤40.00 01/07/2009
REVISION ¤80.00 01/07/2009
REVISION ¤40.00 01/07/2009
REVISION ¤40.00 01/07/2009
ADDITIONAL FEE ¤40.00 01/07/2009
ADDITIONAL FEE ¤40.00 01/07/2009
REINSPECTION FEE ¤40.00 01/07/2009
REINSPECTION FEE ¤40.00 01/07/2009
REINSPECTION FEE ¤40.00 01/07/2009
REINSPECTION FEE ¤40.00 01/07/2009
REINSPECTION FEE ¤40.00 01/07/2009
REINSPECTION FEE ¤40.00 01/07/2009
REINSPECTION FEE ¤40.00 01/07/2009
ADMIN FEE ¤20.00 06/25/2008
BUILDING CODE ADMIN FUND ¤26.11 06/25/2008
ELECTRIC FEE ¤360.00 06/25/2008
FIRE COMM IMPACT FEE 4/1/07 ¤267.89 06/25/2008
FIRE PLANS REVIEW ¤52.22 06/25/2008
MECHANICAL FEE ¤360.00 06/25/2008
PERMIT FEE ¤3,025.00 06/25/2008
PLAN CHECK FEE ¤632.50 06/25/2008
PLUMBING FEE ¤360.00 06/25/2008
RADON FEE ¤26.11 06/25/2008
TRANSPORTATION IMPACT FEE ¤71,537.64 06/25/2008
Fees Total Due: ¤0.00 Total Paid: ¤77,347.47