Permit #2008040661
Permit Details
Status: FINAL
| Subdivision: 2119 - HAMMOCK AT PALM HARBOR |
| Job Phone: (407)328-3000 |
| Location Address: 200 CEDAR COVE |
| Type: FS - FIRE SPRINKLER WET COMMERCIAL |
| Issue Date: 06/18/2008 |
| NOC: RECORDED |
| Applicant name: CHARLES MONTGOMERY |
| Owner: THE HAMMOCK AT PALM HARBOR, LLC |
|
Address 500 COUNTY ROAD 115 N BUNNELL, FL 32110 |
| Contracted Stated Job Value: ¤40,000.00 |
| Job Description: NEW FIRE SPRINKLER SYSTEM W/UNDERGROUND |
| Type: CN |
Contractor
DELTA FIRE SPRINKLERS, INC.
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
111 TECH DRIVE SANFORD, FL 32771 |
74974000011990 (Exp: 06/30/2012) | (407)328-3000 | (407)328-3001 |
Inspection History
| Type | Request Date | Result | Inspector |
| FIRE SPRINKLER FINAL INSPECTION | 03/08/2010 | FINAL APPROVED | JPATTEE |
| FIRE SYSTEM FLUSH | 10/28/2009 | APPROVED | JPATTEE |
| Note: Inspection Requested at 10/27/2009 5:16:03 PM SPIGOT AND FDC | |||
| FIRE SPRINKLER HYDROSTATIC TEST | 10/28/2009 | APPROVED | JPATTEE |
| Note: Inspection Requested at 10/27/2009 5:17:42 PM 1ST FLOOR OH HYDROSTATIC TEST | |||
| FIRE SPRINKLER HYDROSTATIC TEST | 06/12/2009 | APPROVED | JLEWIS |
| Note: 2nd 3rd and 4th floor only | |||
| FIRE MAIN PLACEMENT, SIZE, THRUST BLOCKING UNCOVERED INSPECTION | 07/22/2008 | APPROVED | JPATTEE |
| FIRE MAIN-HYDROSTATIC / BACKFLOW PREVENTERS | 07/22/2008 | APPROVED | JPATTEE |
Review History
| Department | Status | Date In | Date Out |
| FD1 | COMPLETE | 04/30/2009 | 05/01/2009 |
| Note: Released By: JPATTEE forwarded an email | |||
| FD1 | HOLD | 04/14/2009 | 04/20/2009 |
| Note: Held By: JPATTEE Plans indicate omission of heads in electrical room and elevator machine room. The electrical room is notorius for storage and normally require protection.. What type of equipment is in the elevator room? | |||
| FI1 | COMPLETE | 01/15/2009 | 01/15/2009 |
| Note: Released By: JPATTEE | |||
| FI1 | HOLD | 12/23/2008 | 01/10/2009 |
| Note: Held By: JPATTEE Control valve 2nd through 4th floor stairwell does not maintain minimum clearance, blocked by stairwell door. | |||
| FI1 | COMPLETE | 06/12/2008 | 06/13/2008 |
| Note: Released By: JPATTEE | |||
| FI1 | HOLD | 04/30/2008 | 05/07/2008 |
| Note: Held By: JPATTEE 1) Calculations 1,2 do not provide adequate PSI margin of safety, # 3 is very close. 2) FP-O Does not indicate heads in machine room, elevator shaft, A/C room, electric room.OK JDP 3) Sheet FP-O, 2, indicates NFPA 13R 2007 Edition, This has not been adopted by the State Fire Marshal, redesign to the 2002 Edition. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REVISION | ¤40.00 | 06/11/2009 |
| EXTENSION | ¤40.00 | 03/31/2009 |
| FIRE PLANS REVIEW | ¤25.00 | 01/20/2009 |
| CONTRACTOR CHANGE | ¤40.00 | 01/08/2009 |
| FIRE PLANS REVIEW | ¤25.00 | 06/18/2008 |
| PERMIT FEE | ¤50.00 | 06/18/2008 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤220.00 |