Permit #2008040661

Permit Details

Status: FINAL

Subdivision: 2119 - HAMMOCK AT PALM HARBOR
Job Phone: (407)328-3000
Location Address: 200 CEDAR COVE
Type: FS - FIRE SPRINKLER WET COMMERCIAL
Issue Date: 06/18/2008
NOC: RECORDED
Applicant name: CHARLES MONTGOMERY
Owner: THE HAMMOCK AT PALM HARBOR, LLC

Address

500 COUNTY ROAD 115 N

BUNNELL, FL 32110

Contracted Stated Job Value: ¤40,000.00
Job Description: NEW FIRE SPRINKLER SYSTEM W/UNDERGROUND
Type: CN

Contractor

DELTA FIRE SPRINKLERS, INC.
Status Location Address State License Number Phone Fax
CANCEL

111 TECH DRIVE

SANFORD, FL 32771

74974000011990 (Exp: 06/30/2012) (407)328-3000 (407)328-3001

Inspection History

Type Request Date Result Inspector
FIRE SPRINKLER FINAL INSPECTION 03/08/2010 FINAL APPROVED JPATTEE
FIRE SYSTEM FLUSH 10/28/2009 APPROVED JPATTEE
Note: Inspection Requested at 10/27/2009 5:16:03 PM SPIGOT AND FDC
FIRE SPRINKLER HYDROSTATIC TEST 10/28/2009 APPROVED JPATTEE
Note: Inspection Requested at 10/27/2009 5:17:42 PM 1ST FLOOR OH HYDROSTATIC TEST
FIRE SPRINKLER HYDROSTATIC TEST 06/12/2009 APPROVED JLEWIS
Note: 2nd 3rd and 4th floor only
FIRE MAIN PLACEMENT, SIZE, THRUST BLOCKING UNCOVERED INSPECTION 07/22/2008 APPROVED JPATTEE
FIRE MAIN-HYDROSTATIC / BACKFLOW PREVENTERS 07/22/2008 APPROVED JPATTEE

Review History

Department Status Date In Date Out
FD1 COMPLETE 04/30/2009 05/01/2009
Note: Released By: JPATTEE forwarded an email
FD1 HOLD 04/14/2009 04/20/2009
Note: Held By: JPATTEE Plans indicate omission of heads in electrical room and elevator machine room. The electrical room is notorius for storage and normally require protection.. What type of equipment is in the elevator room?
FI1 COMPLETE 01/15/2009 01/15/2009
Note: Released By: JPATTEE
FI1 HOLD 12/23/2008 01/10/2009
Note: Held By: JPATTEE Control valve 2nd through 4th floor stairwell does not maintain minimum clearance, blocked by stairwell door.
FI1 COMPLETE 06/12/2008 06/13/2008
Note: Released By: JPATTEE
FI1 HOLD 04/30/2008 05/07/2008
Note: Held By: JPATTEE 1) Calculations 1,2 do not provide adequate PSI margin of safety, # 3 is very close. 2) FP-O Does not indicate heads in machine room, elevator shaft, A/C room, electric room.OK JDP 3) Sheet FP-O, 2, indicates NFPA 13R 2007 Edition, This has not been adopted by the State Fire Marshal, redesign to the 2002 Edition.

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REVISION ¤40.00 06/11/2009
EXTENSION ¤40.00 03/31/2009
FIRE PLANS REVIEW ¤25.00 01/20/2009
CONTRACTOR CHANGE ¤40.00 01/08/2009
FIRE PLANS REVIEW ¤25.00 06/18/2008
PERMIT FEE ¤50.00 06/18/2008
Fees Total Due: ¤0.00 Total Paid: ¤220.00