I want to search for...
Permit #2008060552
Permit Details
Status: COED
| Parcel Id: 13-11-30-3020-00000-0022 |
| COMMERCIAL SQUARE FOOTAGE: 935 sqft |
| Total Square Footage: 935 sqft |
| Block: 00000 |
| Subdivision: 2151 - Home Depot Center Plaza |
| Job Phone: (386)931-4741 |
| Location Address: 55 PLAZA DR |
| Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION |
| Issue Date: 08/19/2008 |
| NOC: RECORDED |
| Applicant name: FOSTER H COLEMAN |
| Owner: PALM COAST INVESTMENT PROPERTIES |
|
Address 1 FLORIDA PARK DRIVE PALM COAST, FL 32137 |
| Lot: 0060 |
| Contracted Stated Job Value: ¤4,150.00 |
| Job Description: UNIT D-1 - COMPUTER REPAIR SHOP - INTERIOR BUILD-OUT |
| Type: CN |
Contractor
Fantastic Homes Const.Inc. (Foster Coleman)
| Status | Location Address | State License Number | Phone |
| CANCEL |
132 N PENINSULA DR DAYTONA BEACH, FL 32118 |
CGC003579 (Exp: 08/31/2016) | 386-307-1666 |
Sub Contractors
GLEN STEWART COLE
| Status | Location Address | State License Number | Phone | Fax |
| HOLD |
P. O. Box 1677 Palm Coast, FL 32136 |
EC0002522 (Exp: 08/31/2010) | (386) 437-4364 | (386)437-0412 |
MICHAEL G MORELLO JR
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
2 HARGROVE GRADE PALM COAST, FL 32137 |
CAC014293 (Exp: 08/31/2014) | (386)447-3950 | (386)446-4614 |
GLEN WILLIAM KEHLE
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
P. O. Box 353511 BUNNELL, FL 32110 |
CFC057241 (Exp: 08/31/2026) | (386) 447-4249 | (386) 437-8488 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRICAL FINAL | 09/19/2008 | FINAL APPROVED | RMARVEL |
| Note: THIS IS A REINSPECTION requested by contractor | |||
| COMMERCIAL BUILDING FINAL | 09/19/2008 | APPROVED | JMCGOWEN |
| Note: THIS IS A REINSPECTION requested by contractor | |||
| COMMERCIAL BUILDING FINAL | 09/18/2008 | CANCELLED BY APPLICANT | JMCGOWEN |
| Note: Requested by Foster | |||
| FIRE FINAL | 09/18/2008 | APPROVED | JPATTEE |
| ELECTRICAL FINAL | 09/18/2008 | Disapproved -FEE REQUIRED | RMARVEL |
| Note: Inspection Resulted at 9/18/2008 2:52:33 PM NEED TO MAINTAIN CLEARNCES ON DISCONNECTS FOR AC UNITS. | |||
| H.V.A.C. FINAL | 09/18/2008 | APPROVED | JMCGOWEN |
| PLUMBING FINAL | 09/17/2008 | APPROVED | PGALLMANN |
| Note: THIS IS A REINSPECTION | |||
| PLUMBING FINAL | 09/15/2008 | CANCELLED BY APPLICANT | PGALLMANN |
| Note: requested by Foster | |||
| ABOVE CEILING | 09/15/2008 | APPROVED | JMCGOWEN |
| Note: requested by Foster | |||
| COMMERCIAL POWER INSPECTION | 09/15/2008 | APPROVED | LHITES |
| Note: requested by Foster | |||
| UTILITY COMMERCIAL FINAL | 09/15/2008 | APPROVED | KKING |
| Note: requested by Foster | |||
| UTILITY COMPANY FINAL | 09/15/2008 | APPROVED | KKING |
| Note: requested by Foster | |||
| FRAMING | 09/02/2008 | APPROVED | DROCKWELL |
| FIREWALL INSPECTION | 08/27/2008 | APPROVED | JPATTEE |
| SECOND ROUGH PLUMBING INSPECTION | 08/26/2008 | APPROVED | PGALLMANN |
| H.V.A.C. ROUGH | 08/26/2008 | APPROVED | JMCGOWEN |
| 2ND ROUGH ELECTRICAL | 08/26/2008 | APPROVED | RMARVEL |
Review History
| Department | Status | Date In | Date Out |
| BLD | COMPLETE | 09/18/2008 | 09/18/2008 |
| Note: Released By: JMCGOWEN revision - back door frame opening - moved disconnects | |||
| BLD | CANCEL | 09/16/2008 | |
| FI1 | COMPLETE | 09/15/2008 | 09/16/2008 |
| Note: Released By: JPATTEE revison to add exit light | |||
| UD1 | COMPLETE | 09/15/2008 | 07/16/2008 |
| Note: Released By: CJOHNSON | |||
| FI1 | HOLD | 09/08/2008 | 09/08/2008 |
| Note: Held By: JPATTEE 1) Exit light not indicated on plans for unit D-1. 2) Door swing, bathroom, will impede exit access. | |||
| FI1 | COMPLETE | 08/07/2008 | 08/08/2008 |
| Note: Released By: JPATTEE | |||
| ELEC | COMPLETE | 07/15/2008 | 07/15/2008 |
| Note: Released By: SKNOPF Approved for Release. | |||
| MECH | COMPLETE | 07/15/2008 | 07/15/2008 |
| Note: Released By: JMCGOWEN | |||
| ELEC | HOLD | 07/03/2008 | 07/03/2008 |
| Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application #2008060552 (Unit D1 Bridal/Tuxedo Shop @ 55 Plaza Dr.) 7/3/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. Sheet 1: a. Provide updated Panel Schedule showing all circuit breaker sizes, circuit identification, circuit loads (VA), and Panel Demand Load Calculation per NEC. Include all existing AC, AHU, water heating, and sign loads. b. Identify circuits on plans for all receptacles, fixtures, equipment, HVAC, and appliances. c. Identify electrical panel location. d. Identify Keynotes A & B shown on Reflected Ceiling, Electric, A/C Plan. e. Provide disconnect location for AC, water heating equipment, and any other identified equipment requiring disconnecting means per the NEC. f. Identify ceiling mounted light fixture load for fixture shown in (2) small booth areas. g. Identify ceiling fan load. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us | |||
| BLD | COMPLETE | 07/02/2008 | 07/03/2008 |
| Note: Released By: JMCGOWEN | |||
| ZON | COMPLETE | 07/02/2008 | 07/02/2008 |
| Note: Released By: ECOYNE | |||
| ZON | HOLD | 06/30/2008 | 07/01/2008 |
| Note: Held By: BBARTON approved construction plans for the build out have this unit labeled as unit D1 not unit 3, please revise plans to indicate unit D1 faxed contractor hold comments 07/01/08 @ 9:21am use and parking verified | |||
| FI1 | HOLD | 07/17/2008 | |
| Note: Held By: JPATTEE Sheet 1 reflected ceiling plans shows an exit/emergency light for the optional rear door, will this door be installed, if not, remove exit light and leave emergency light. | |||
| MECH | HOLD | 07/03/2008 | |
| Note: Held By: JMCGOWEN provide exhaust fan size in cfm's and exhaust duct size and location to the outside, provide hvac duct material and sizes and duct support, hangers and straps. | |||
| PLUM | COMPLETE | 07/03/2008 | |
| Note: Released By: JMCGOWEN existing | |||
| BLD | HOLD | 09/15/2008 | |
| Note: Held By: JMCGOWEN provide structural detail of opening for door |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 09/18/2008 |
| REVISION | ¤80.00 | 09/18/2008 |
| ELECTRIC FEE | ¤33.00 | 08/19/2008 |
| FIRE PLANS REVIEW | ¤25.00 | 08/19/2008 |
| MECHANICAL FEE | ¤33.00 | 08/19/2008 |
| PERMIT FEE | ¤70.00 | 08/19/2008 |
| PLAN CHECK FEE | ¤100.00 | 08/19/2008 |
| PLUMBING FEE | ¤33.00 | 08/19/2008 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤414.00 |