I want to search for...
Permit #2008070421
Permit Details
Status: COED
| Parcel Id: 13-11-30-3020-00000-0022 |
| Total Square Footage: 935 sqft |
| Block: 00000 |
| Subdivision: 2151 - Home Depot Center Plaza |
| Job Phone: (386)931-4741 |
| Location Address: 55 PLAZA DR |
| Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION |
| Issue Date: 08/18/2008 |
| NOC: RECORDED |
| Applicant name: FOSTER H COLEMAN |
| Owner: PALM COAST INVESTMENT PROPERTIES |
|
Address 1 FLORIDA PARK DRIVE PALM COAST, FL 32137 |
| Lot: 0060 |
| Contracted Stated Job Value: ¤3,475.00 |
| Job Description: UNIT D-3 GIFT SHOP - INTERIOR BUILDOUT |
| Type: CN |
Contractor
Fantastic Homes Const.Inc. (Foster Coleman)
| Status | Location Address | State License Number | Phone |
| CANCEL |
132 N PENINSULA DR DAYTONA BEACH, FL 32118 |
CGC003579 (Exp: 08/31/2016) | 386-307-1666 |
Sub Contractors
GLEN STEWART COLE
| Status | Location Address | State License Number | Phone | Fax |
| HOLD |
P. O. Box 1677 Palm Coast, FL 32136 |
EC0002522 (Exp: 08/31/2010) | (386) 437-4364 | (386)437-0412 |
MICHAEL G MORELLO JR
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
2 HARGROVE GRADE PALM COAST, FL 32137 |
CAC014293 (Exp: 08/31/2014) | (386)447-3950 | (386)446-4614 |
GLEN WILLIAM KEHLE
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
P. O. Box 353511 BUNNELL, FL 32110 |
CFC057241 (Exp: 08/31/2026) | (386) 447-4249 | (386) 437-8488 |
Inspection History
| Type | Request Date | Result | Inspector |
| COMMERCIAL BUILDING FINAL | 09/11/2008 | FINAL APPROVED | JMCGOWEN |
| Note: REQUESTED BY FOSTER | |||
| UTILITY COMMERCIAL FINAL | 09/10/2008 | APPROVED | KKING |
| UTILITY COMPANY FINAL | 09/10/2008 | APPROVED | KKING |
| FIRE FINAL | 09/10/2008 | APPROVED | JPATTEE |
| Note: THIS IS A REINSPECTION | |||
| PLUMBING FINAL | 09/10/2008 | FINAL APPROVED | PGALLMANN |
| H.V.A.C. FINAL | 09/10/2008 | APPROVED | JMCGOWEN |
| ELECTRICAL FINAL | 09/10/2008 | APPROVED | RMARVEL |
| FIRE FINAL | 09/08/2008 | Disapproved - NO FEE | JPATTEE |
| Note: no fire extinguisher | |||
| COMMERCIAL POWER INSPECTION | 09/05/2008 | APPROVED | RMARVEL |
| Note: THIS IS A REINSPECTION Inspection Resulted at 9/5/2008 1:38:17 PM COLE ELECTRIC | |||
| COMMERCIAL POWER INSPECTION | 09/04/2008 | CANCELLED BY APPLICANT | RMARVEL |
| Note: Requested by Foster | |||
| ABOVE CEILING | 09/04/2008 | APPROVED | JMCGOWEN |
| Note: THIS IS A REINSPECTION | |||
| FIREWALL INSPECTION | 08/27/2008 | APPROVED | JPATTEE |
| 2ND ROUGH ELECTRICAL | 08/25/2008 | APPROVED | RMARVEL |
| Note: THIS IS A REINSPECTION Inspection Resulted at 8/25/2008 12:35:37 PM WALLS ONLY | |||
| H.V.A.C. ROUGH | 08/25/2008 | APPROVED | JMCGOWEN |
| Note: THIS IS A REINSPECTION | |||
| FRAMING | 08/25/2008 | APPROVED | JHINDMAN |
| Note: THIS IS A REINSPECTION | |||
| FIREWALL FRAMING (DUPLEX) | 08/20/2008 | CANCELLED BY INSPECTOR | JMCGOWEN |
| Note: commercial buildings do not need a residental inspection | |||
| ABOVE CEILING | 08/20/2008 | Disapproved -FEE REQUIRED | JMCGOWEN |
| Note: Inspection Resulted at 8/20/2008 10:25:49 AM NOT READY FOR ABOVE CEILING INSPECTION | |||
| FRAMING | 08/20/2008 | Disapproved -FEE REQUIRED | DROCKWELL |
| Note: Inspection Resulted at 8/20/2008 10:41:46 AM RESTROOM FLOOR TO CEILING HEIGHT NOT TO PLAN/FIREBLOCKING MISSING/A/C DECK CALLS FOR 5/8 PLYWOOD | |||
| SECOND ROUGH PLUMBING INSPECTION | 08/20/2008 | APPROVED | PGALLMANN |
| H.V.A.C. ROUGH | 08/20/2008 | Disapproved -FEE REQUIRED | JMCGOWEN |
| Note: Inspection Resulted at 8/20/2008 10:25:49 AM NEED TO CORRECT RESTRICTION OF FLOW ON RETURN AIR DUCT. | |||
| 2ND ROUGH ELECTRICAL | 08/20/2008 | Disapproved -FEE REQUIRED | RMARVEL |
| Note: THIS IS A REINSPECTION Inspection Resulted at 8/20/2008 10:08:28 AM NEED A REVISION ON ADDED RECEPTACLES AND SWITCH. CIRCLED AREAS ON PLANS. | |||
| FIREWALL INSPECTION | 08/20/2008 | APPROVED | JLEWIS |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 08/22/2008 | 08/22/2008 |
| Note: Released By: SKNOPF Approved for Release. Revision: added 2 new convenience duplex receptacles, and added switch for exterior rear light. | |||
| UD1 | COMPLETE | 08/11/2008 | 08/18/2008 |
| Note: Released By: CJOHNSON Released By: CJOHNSON | |||
| FI1 | COMPLETE | 08/08/2008 | 08/11/2008 |
| Note: Released By: JPATTEE | |||
| MECH | COMPLETE | 08/08/2008 | 08/08/2008 |
| Note: Released By: FREODICA | |||
| BLD | COMPLETE | 08/07/2008 | 08/07/2008 |
| Note: Released By: JJOSEPH | |||
| MECH | HOLD | 08/04/2008 | 08/05/2008 |
| Note: Held By: FREODICA 1. Revise the energy calculations to refflect the change in square footage of the space. 2. Provide supporting detail of AHU above the existing toilet. 3. The condensate drain disposal as shown on detail is not acceptable. The discharge shall be at least 1 ft away from the building and shall not cause nuisance. Revise to comply with code. See previous comment. | |||
| PLUM | COMPLETE | 08/04/2008 | 08/04/2008 |
| Note: Released By: FREODICA | |||
| BLD | HOLD | 08/04/2008 | 08/05/2008 |
| Note: Held By: JJOSEPH 1. Revise the occupancy group from business(B) to Mercantile(M) 2. Revise the occupant load and Egress width to reflect the change in occupancy group. 3. The note regarding Floor Covering needs to be updated from SBC to FBC and reflect proper chapter number and section. | |||
| MECH | HOLD | 07/29/2008 | 07/29/2008 |
| Note: Held By: FREODICA 1. Indicate on plan the supply air in CFM for each supply diffuser. 2. Indicate the use of room adjacent to the restroom. 3. Return air from the main room shall be ducted from the return grille up to the Air Handling Unit (AHU) and show outside air duct layout. 4. Provide AHU/CU schedule or specifications and instalattion details. 5. Indicate how condensate would be disposed to comply with FBC/mechanical 2004 Section 307. | |||
| PLUM | HOLD | 07/29/2008 | 07/29/2008 |
| Note: Held By: FREODICA 1. Provide drinking fountain per FBC/Plumbing 2004 Table 403.1 and Section 410. | |||
| BLD | HOLD | 07/29/2008 | 07/29/2008 |
| Note: Held By: JJOSEPH The gypsum board indicated for the interior wall does not match to U305, please clarify. | |||
| ELEC | COMPLETE | 07/29/2008 | 07/29/2008 |
| Note: Released By: SKNOPF Approved for Release. | |||
| ZON | HOLD | 07/25/2008 | 07/25/2008 |
| Note: Held By: BBARTON please verify use of unit plans need to reflect the correct address of 55 Plaza Drive faxed contractor 07/25/08 @ 2:20pm | |||
| ZON | COMPLETE | 07/29/2008 | |
| Note: Released By: ECOYNE Gift Shop - Retail |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 09/10/2008 |
| REINSPECTION FEE | ¤40.00 | 09/10/2008 |
| REINSPECTION FEE | ¤40.00 | 09/10/2008 |
| REINSPECTION FEE | ¤40.00 | 09/10/2008 |
| REVISION | ¤40.00 | 09/10/2008 |
| SITE PLAN 20 | ¤20.00 | 08/18/2008 |
| ADMIN COMMERCIAL | ¤60.00 | 08/18/2008 |
| ELECTRIC FEE | ¤63.00 | 08/18/2008 |
| FIRE PLANS REVIEW | ¤25.00 | 08/18/2008 |
| MECHANICAL FEE | ¤63.00 | 08/18/2008 |
| PERMIT FEE | ¤50.00 | 08/18/2008 |
| PLAN CHECK FEE | ¤100.00 | 08/18/2008 |
| PLUMBING FEE | ¤63.00 | 08/18/2008 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤644.00 |