Permit #2008100098

Permit Details

Status: COED

Parcel Id: 18-11-31-0000-02010-0070
Block: 02010
Subdivision: -
Job Phone: (386) 445-4350
Location Address: 5 UTILITY DR
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 10/29/2008
NOC: RECORDED
Applicant name: MICHAEL GLEN MACHIN
Owner: M MACHIN ENTERPRISES INC

Address

P O BOX 353460

PALM COAST, FL 32135

Lot: 0070
Contracted Stated Job Value: ¤20,000.00
Job Description: UNIT 22-- ADDING WALLS & PLUMBING "EUROPEAN BEAUTY SALON"
Type: CN

Contractor

MACHIN CONSTRUCTION CO
Status Location Address State License Number Phone Fax
INACTIVE

3 HARGROVE GRADE SUITE 1

Palm Coast, FL 32137

CGC058789 (Exp: 08/31/2024) (386) 445-4350 (386)446-5459

Sub Contractors

DANIEL P HUCKS
Status Location Address State License Number Phone Fax
CANCEL

400 N. U.S. 1

Ormond Beach, FL 32174

CAC029376 (Exp: 08/31/2024) 386-672-8494 386-673-7856
JONATHAN M PEARSON
Status Location Address State License Number Phone Fax
ACTIVE

209 N FORSYTH ST

BUNNELL, FL 32110

CFC1425941 (Exp: 08/31/2026) 386-597-0944 386-437-4996
ROBERT J CATES
Status Location Address State License Number Phone Fax
CANCEL

1750 RIDGEWOOD AVE

HOLLY HILL, FL 32117

EC13002452 (Exp: 08/31/2014) 386-677-4757 386-677-8686

Inspection History

Type Request Date Result Inspector
COMMERCIAL BUILDING FINAL 12/23/2008 FINAL APPROVED CMINI
ELECTRICAL FINAL 12/22/2008 APPROVED RMARVEL
H.V.A.C. FINAL 12/22/2008 APPROVED LWOODROME
PLUMBING FINAL 12/22/2008 APPROVED JHINDMAN
FIRE FINAL 12/19/2008 APPROVED JPATTEE
UTILITY COMMERCIAL FINAL 12/16/2008 APPROVED KKING
UTILITY COMPANY FINAL 12/16/2008 APPROVED KKING
H.V.A.C. ROUGH 12/12/2008 APPROVED JMCGOWEN
Note: THIS IS A REINSPECTION
ABOVE CEILING 12/12/2008 APPROVED RMARVEL
Note: THIS IS A REINSPECTION
SECOND ROUGH PLUMBING INSPECTION 12/04/2008 APPROVED JHINDMAN
Note: THIS IS A REINSPECTION
2ND ROUGH ELECTRICAL 12/03/2008 APPROVED RMARVEL
H.V.A.C. ROUGH 12/03/2008 Disapproved -FEE REQUIRED JMCGOWEN
Note: Inspection Resulted at 12/3/2008 3:01:13 PM HVAC NOT TO PLAN.
FRAMING 12/03/2008 APPROVED CMINI
ABOVE CEILING 12/03/2008 Disapproved -FEE REQUIRED RMARVEL
Note: Inspection Resulted at 12/3/2008 3:58:39 PM NEED TO STRAP MC INDIVIDUALLY FROM GRID.
SECOND ROUGH PLUMBING INSPECTION 12/03/2008 Disapproved -FEE REQUIRED JHINDMAN
Note: THIS IS A REINSPECTION Inspection Resulted at 12/3/2008 3:38:44 PM STRAP AND SUPPORT ALL PIPING, TIE IN REVENT.
SECOND ROUGH PLUMBING INSPECTION 11/12/2008 PARTIALLY APPROVED JHINDMAN
Note: THIS IS A REINSPECTION Inspection Resulted at 11/12/2008 3:59:51 PM 1ST ROUGH OK
SECOND ROUGH PLUMBING INSPECTION 11/06/2008 Disapproved -FEE REQUIRED JHINDMAN
Note: THIS IS A REINSPECTION Inspection Resulted at 11/6/2008 3:13:00 PM NEED REVISION UNDER SLAB DOES NOT MATCH PLANS
SECOND ROUGH PLUMBING INSPECTION 11/04/2008 CANCELLED BY APPLICANT JHINDMAN

Review History

Department Status Date In Date Out
MECH COMPLETE 12/09/2008 12/09/2008
Note: Released By: FREODICA revision REROUTING OF DUCT WORK DRYER VENT 2 EXHAUST FANS 3 FRESH AIR INTAKES
MECH HOLD 12/03/2008 12/04/2008
Note: Held By: FREODICA 1. Revision submitted shall be signed and sealed by the FL Registered Design Professional.
PLUM COMPLETE 11/10/2008 11/10/2008
Note: Released By: FREODICA
PLUM HOLD 11/07/2008 11/07/2008
Note: Held By: FREODICA Revision: Revise sanitary riser diagram to match the changes made to sanitary plan.
FI1 COMPLETE 10/27/2008 10/29/2008
Note: Released By: JPATTEE Provide fire sprinkler head in bathroom and storage room
MECH COMPLETE 10/27/2008 10/27/2008
Note: Released By: FREODICA Correction Responce to comments
ELEC COMPLETE 10/24/2008 10/24/2008
Note: Released By: SKNOPF Approved for Release. Signed & sealed copies.
MECH HOLD 10/24/2008 10/24/2008
Note: TRHeld By: FREODICA 1. Provide information on the space between the reception and shampoo where the six (6) seating are located. Are these for nail salon or hair only. If there is a nail salon in the area, the return air is prohibited per FMC 2004 Section 403.2.1 and Table 403.3. 2. Provide clothes dryer exhaust per FMC 2004 Section 504.
PLUM COMPLETE 10/24/2008 10/24/2008
Note: Released By: FREODICA Revision: Re-routed sanitary lines.
UD1 COMPLETE 10/24/2008 10/24/2008
Note: Released By: CJOHNSON
ENGIN1 COMPLETE 10/23/2008 10/23/2008
Note: Released By: AWEBB Engineering comments not necessary.
MECH COMPLETE 10/22/2008 10/23/2008
Note: Released By: JJOSEPH
ELEC HOLD 10/22/2008 10/23/2008
Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application #2008100098 (Unit 22 Interior Alterations European Beauty Salon @ 5 Utility Dr.) 10/23/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. A-1: Revise the Demand Load Calculation per NEC 220 and the following: a. Appliances and equipment loads (such as pedicure chairs, washers, dryers, water coolers, coffee makers, water heaters, exhaust fans, and steamers) cannot be included using the demand factors from NEC Table 220.44. See NEC 220.14(A) and NEC 422. b. Include items such as lighting and signs as continuous load (taken at 125% where minimum 3 hours continuous), as applicable. c. Include additional 25% of largest motor per NEC 220 and 430.24. d. Include continuous storage water heater as continuous load at 125% where 120 gallons or less per NEC 422.13. e. Delete reference to NEC 220.2 in panel schedule load calculation. NEC 2005 does not include 220.2. f. Please note NEC 220.60 for noncoincidental loads, such as A/C and heat. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us
FI1 HOLD 10/09/2008 10/14/2008
Note: Held By: JPATTEE 1) Door swing for exsisting toilet, facial 1 and facial 2 impede the path of egress. 2) Alterations to AFA or AFS will require permitting.
MECH HOLD 10/09/2008 10/09/2008
Note: Held By: FREODICA 1. Provide existing and proposed (new) HVAC system duct layout. 2. Provide location of HVAC unit(s), new and/or existing. 3. Provide supplementary exhaust duct layout including duct size, location of exhaust fan and termination point. 4. Provide energy calculations. 5. Provide HVAC Equipment and Exhaust Fan Schedules. 6. Provide the required outdoor ventilation air per FMC 2004 Table 403.3 or Section 403.4. 7. Provide condensate disposal per FMC 2004 Section 307. 8. Provide HVAC details.
PLUM HOLD 10/09/2008 10/09/2008
Note: Held By: FREODICA 1. Provide Plumbing Fixture Schedule. 2. Provide Sanitary and Domestic Water layouts. 3. Provide readable riser diagrams to match the proposed layouts. 4. Provide plumbing details applicable to the job.
BLD HOLD 10/08/2008 10/08/2008
Note: Held By: JJOSEPH 1.Provide a life safety plan as required by the code. 2.Provide measurements on life safety plan to verify egress requirements and travel distance. 3. Revise the plan to indicate the occupancy, the occupant load, the area and type of construction. 4. Provide new interior wall details. 5. Other comments may be necessary based on your responses to these comments.
ELEC HOLD 10/08/2008 10/08/2008
Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application #2008100098 (European Beauty Salon @ 5 Utility Dr.) 10/8/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. A-1: a. Provide readable panel schedule with amperage, voltage, # phases, and demand load calculations. b. Identify all circuit breaker sizes and individual circuit loads in panel schedule. c. Provide electrical riser showing electrical equipment and feeder sizes. d. Identify circuit locations on Electrical Power plan for all receptacles, appliances, HVAC and equipment. e. Identify circuits for all lighting, both new and existing. f. Identify wattage of new recessed fixtures. g. Additional exit and emergency light will be required in area outside Changing Room per NEC 700 Part IV. h. Identify location and provide required sign circuit and load in panel per NEC 600.5 and 220.14(F). i. Identify loads for all HVAC and appliances including steamers, exhaust fans, water heaters, washer/dryers, hair dryers, etc. j. Provide circuit for bottled water cooler as required. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us
ZON COMPLETE 10/07/2008 10/07/2008
Note: Released By: BBARTON use verified-beauty salon permitted in Com-2

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION FEE ¤40.00 12/10/2008
REINSPECTION FEE ¤40.00 12/10/2008
REINSPECTION FEE ¤40.00 12/10/2008
REVISION ¤40.00 12/10/2008
REINSPECTION FEE ¤40.00 11/10/2008
REVISION ¤40.00 11/10/2008
ADMIN COMMERCIAL ¤60.00 10/29/2008
ELECTRIC FEE ¤72.00 10/29/2008
FIRE PLANS REVIEW ¤25.00 10/29/2008
MECHANICAL FEE ¤72.00 10/29/2008
PERMIT FEE ¤140.00 10/29/2008
PLAN CHECK FEE ¤100.00 10/29/2008
PLUMBING FEE ¤72.00 10/29/2008
SITE PLAN 20 ¤20.00 10/29/2008
Fees Total Due: ¤0.00 Total Paid: ¤801.00