Permit #2008100098
Permit Details
Status: COED
| Parcel Id: 18-11-31-0000-02010-0070 |
| Block: 02010 |
| Subdivision: - |
| Job Phone: (386) 445-4350 |
| Location Address: 5 UTILITY DR |
| Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION |
| Issue Date: 10/29/2008 |
| NOC: RECORDED |
| Applicant name: MICHAEL GLEN MACHIN |
| Owner: M MACHIN ENTERPRISES INC |
|
Address P O BOX 353460 PALM COAST, FL 32135 |
| Lot: 0070 |
| Contracted Stated Job Value: ¤20,000.00 |
| Job Description: UNIT 22-- ADDING WALLS & PLUMBING "EUROPEAN BEAUTY SALON" |
| Type: CN |
Contractor
MACHIN CONSTRUCTION CO
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
3 HARGROVE GRADE SUITE 1 Palm Coast, FL 32137 |
CGC058789 (Exp: 08/31/2024) | (386) 445-4350 | (386)446-5459 |
Sub Contractors
DANIEL P HUCKS
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
400 N. U.S. 1 Ormond Beach, FL 32174 |
CAC029376 (Exp: 08/31/2024) | 386-672-8494 | 386-673-7856 |
JONATHAN M PEARSON
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
209 N FORSYTH ST BUNNELL, FL 32110 |
CFC1425941 (Exp: 08/31/2026) | 386-597-0944 | 386-437-4996 |
ROBERT J CATES
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
1750 RIDGEWOOD AVE HOLLY HILL, FL 32117 |
EC13002452 (Exp: 08/31/2014) | 386-677-4757 | 386-677-8686 |
Inspection History
| Type | Request Date | Result | Inspector |
| COMMERCIAL BUILDING FINAL | 12/23/2008 | FINAL APPROVED | CMINI |
| ELECTRICAL FINAL | 12/22/2008 | APPROVED | RMARVEL |
| H.V.A.C. FINAL | 12/22/2008 | APPROVED | LWOODROME |
| PLUMBING FINAL | 12/22/2008 | APPROVED | JHINDMAN |
| FIRE FINAL | 12/19/2008 | APPROVED | JPATTEE |
| UTILITY COMMERCIAL FINAL | 12/16/2008 | APPROVED | KKING |
| UTILITY COMPANY FINAL | 12/16/2008 | APPROVED | KKING |
| H.V.A.C. ROUGH | 12/12/2008 | APPROVED | JMCGOWEN |
| Note: THIS IS A REINSPECTION | |||
| ABOVE CEILING | 12/12/2008 | APPROVED | RMARVEL |
| Note: THIS IS A REINSPECTION | |||
| SECOND ROUGH PLUMBING INSPECTION | 12/04/2008 | APPROVED | JHINDMAN |
| Note: THIS IS A REINSPECTION | |||
| 2ND ROUGH ELECTRICAL | 12/03/2008 | APPROVED | RMARVEL |
| H.V.A.C. ROUGH | 12/03/2008 | Disapproved -FEE REQUIRED | JMCGOWEN |
| Note: Inspection Resulted at 12/3/2008 3:01:13 PM HVAC NOT TO PLAN. | |||
| FRAMING | 12/03/2008 | APPROVED | CMINI |
| ABOVE CEILING | 12/03/2008 | Disapproved -FEE REQUIRED | RMARVEL |
| Note: Inspection Resulted at 12/3/2008 3:58:39 PM NEED TO STRAP MC INDIVIDUALLY FROM GRID. | |||
| SECOND ROUGH PLUMBING INSPECTION | 12/03/2008 | Disapproved -FEE REQUIRED | JHINDMAN |
| Note: THIS IS A REINSPECTION Inspection Resulted at 12/3/2008 3:38:44 PM STRAP AND SUPPORT ALL PIPING, TIE IN REVENT. | |||
| SECOND ROUGH PLUMBING INSPECTION | 11/12/2008 | PARTIALLY APPROVED | JHINDMAN |
| Note: THIS IS A REINSPECTION Inspection Resulted at 11/12/2008 3:59:51 PM 1ST ROUGH OK | |||
| SECOND ROUGH PLUMBING INSPECTION | 11/06/2008 | Disapproved -FEE REQUIRED | JHINDMAN |
| Note: THIS IS A REINSPECTION Inspection Resulted at 11/6/2008 3:13:00 PM NEED REVISION UNDER SLAB DOES NOT MATCH PLANS | |||
| SECOND ROUGH PLUMBING INSPECTION | 11/04/2008 | CANCELLED BY APPLICANT | JHINDMAN |
Review History
| Department | Status | Date In | Date Out |
| MECH | COMPLETE | 12/09/2008 | 12/09/2008 |
| Note: Released By: FREODICA revision REROUTING OF DUCT WORK DRYER VENT 2 EXHAUST FANS 3 FRESH AIR INTAKES | |||
| MECH | HOLD | 12/03/2008 | 12/04/2008 |
| Note: Held By: FREODICA 1. Revision submitted shall be signed and sealed by the FL Registered Design Professional. | |||
| PLUM | COMPLETE | 11/10/2008 | 11/10/2008 |
| Note: Released By: FREODICA | |||
| PLUM | HOLD | 11/07/2008 | 11/07/2008 |
| Note: Held By: FREODICA Revision: Revise sanitary riser diagram to match the changes made to sanitary plan. | |||
| FI1 | COMPLETE | 10/27/2008 | 10/29/2008 |
| Note: Released By: JPATTEE Provide fire sprinkler head in bathroom and storage room | |||
| MECH | COMPLETE | 10/27/2008 | 10/27/2008 |
| Note: Released By: FREODICA Correction Responce to comments | |||
| ELEC | COMPLETE | 10/24/2008 | 10/24/2008 |
| Note: Released By: SKNOPF Approved for Release. Signed & sealed copies. | |||
| MECH | HOLD | 10/24/2008 | 10/24/2008 |
| Note: TRHeld By: FREODICA 1. Provide information on the space between the reception and shampoo where the six (6) seating are located. Are these for nail salon or hair only. If there is a nail salon in the area, the return air is prohibited per FMC 2004 Section 403.2.1 and Table 403.3. 2. Provide clothes dryer exhaust per FMC 2004 Section 504. | |||
| PLUM | COMPLETE | 10/24/2008 | 10/24/2008 |
| Note: Released By: FREODICA Revision: Re-routed sanitary lines. | |||
| UD1 | COMPLETE | 10/24/2008 | 10/24/2008 |
| Note: Released By: CJOHNSON | |||
| ENGIN1 | COMPLETE | 10/23/2008 | 10/23/2008 |
| Note: Released By: AWEBB Engineering comments not necessary. | |||
| MECH | COMPLETE | 10/22/2008 | 10/23/2008 |
| Note: Released By: JJOSEPH | |||
| ELEC | HOLD | 10/22/2008 | 10/23/2008 |
| Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application #2008100098 (Unit 22 Interior Alterations European Beauty Salon @ 5 Utility Dr.) 10/23/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. A-1: Revise the Demand Load Calculation per NEC 220 and the following: a. Appliances and equipment loads (such as pedicure chairs, washers, dryers, water coolers, coffee makers, water heaters, exhaust fans, and steamers) cannot be included using the demand factors from NEC Table 220.44. See NEC 220.14(A) and NEC 422. b. Include items such as lighting and signs as continuous load (taken at 125% where minimum 3 hours continuous), as applicable. c. Include additional 25% of largest motor per NEC 220 and 430.24. d. Include continuous storage water heater as continuous load at 125% where 120 gallons or less per NEC 422.13. e. Delete reference to NEC 220.2 in panel schedule load calculation. NEC 2005 does not include 220.2. f. Please note NEC 220.60 for noncoincidental loads, such as A/C and heat. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us | |||
| FI1 | HOLD | 10/09/2008 | 10/14/2008 |
| Note: Held By: JPATTEE 1) Door swing for exsisting toilet, facial 1 and facial 2 impede the path of egress. 2) Alterations to AFA or AFS will require permitting. | |||
| MECH | HOLD | 10/09/2008 | 10/09/2008 |
| Note: Held By: FREODICA 1. Provide existing and proposed (new) HVAC system duct layout. 2. Provide location of HVAC unit(s), new and/or existing. 3. Provide supplementary exhaust duct layout including duct size, location of exhaust fan and termination point. 4. Provide energy calculations. 5. Provide HVAC Equipment and Exhaust Fan Schedules. 6. Provide the required outdoor ventilation air per FMC 2004 Table 403.3 or Section 403.4. 7. Provide condensate disposal per FMC 2004 Section 307. 8. Provide HVAC details. | |||
| PLUM | HOLD | 10/09/2008 | 10/09/2008 |
| Note: Held By: FREODICA 1. Provide Plumbing Fixture Schedule. 2. Provide Sanitary and Domestic Water layouts. 3. Provide readable riser diagrams to match the proposed layouts. 4. Provide plumbing details applicable to the job. | |||
| BLD | HOLD | 10/08/2008 | 10/08/2008 |
| Note: Held By: JJOSEPH 1.Provide a life safety plan as required by the code. 2.Provide measurements on life safety plan to verify egress requirements and travel distance. 3. Revise the plan to indicate the occupancy, the occupant load, the area and type of construction. 4. Provide new interior wall details. 5. Other comments may be necessary based on your responses to these comments. | |||
| ELEC | HOLD | 10/08/2008 | 10/08/2008 |
| Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application #2008100098 (European Beauty Salon @ 5 Utility Dr.) 10/8/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. A-1: a. Provide readable panel schedule with amperage, voltage, # phases, and demand load calculations. b. Identify all circuit breaker sizes and individual circuit loads in panel schedule. c. Provide electrical riser showing electrical equipment and feeder sizes. d. Identify circuit locations on Electrical Power plan for all receptacles, appliances, HVAC and equipment. e. Identify circuits for all lighting, both new and existing. f. Identify wattage of new recessed fixtures. g. Additional exit and emergency light will be required in area outside Changing Room per NEC 700 Part IV. h. Identify location and provide required sign circuit and load in panel per NEC 600.5 and 220.14(F). i. Identify loads for all HVAC and appliances including steamers, exhaust fans, water heaters, washer/dryers, hair dryers, etc. j. Provide circuit for bottled water cooler as required. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us | |||
| ZON | COMPLETE | 10/07/2008 | 10/07/2008 |
| Note: Released By: BBARTON use verified-beauty salon permitted in Com-2 |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 12/10/2008 |
| REINSPECTION FEE | ¤40.00 | 12/10/2008 |
| REINSPECTION FEE | ¤40.00 | 12/10/2008 |
| REVISION | ¤40.00 | 12/10/2008 |
| REINSPECTION FEE | ¤40.00 | 11/10/2008 |
| REVISION | ¤40.00 | 11/10/2008 |
| ADMIN COMMERCIAL | ¤60.00 | 10/29/2008 |
| ELECTRIC FEE | ¤72.00 | 10/29/2008 |
| FIRE PLANS REVIEW | ¤25.00 | 10/29/2008 |
| MECHANICAL FEE | ¤72.00 | 10/29/2008 |
| PERMIT FEE | ¤140.00 | 10/29/2008 |
| PLAN CHECK FEE | ¤100.00 | 10/29/2008 |
| PLUMBING FEE | ¤72.00 | 10/29/2008 |
| SITE PLAN 20 | ¤20.00 | 10/29/2008 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤801.00 |