Permit #2008110072

Permit Details

Status: COED

Parcel Id: 13-11-30-3020-00000-0022
Total Square Footage: 944 sqft
Block: 00000
Subdivision: 2151 - Home Depot Center Plaza
Job Phone: (386)931-4741
Location Address: 55 PLAZA DR
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 11/18/2008
NOC: RECORDED
Applicant name: FOSTER H COLEMAN
Owner: PALM COAST INVESTMENT PROPERTIES

Address

1 FLORIDA PARK DRIVE

PALM COAST, FL 32137

Lot: 0060
Contracted Stated Job Value: ¤9,765.00
Job Description: UNIT D-7 WALL, ELECT. OUTLETS & LIGHTS- DRYWALL HEARING AID STORE
Type: CN

Contractor

Fantastic Homes Const.Inc. (Foster Coleman)
Status Location Address State License Number Phone
CANCEL

132 N PENINSULA DR

DAYTONA BEACH, FL 32118

CGC003579 (Exp: 08/31/2016) 386-307-1666

Sub Contractors

GLEN STEWART COLE
Status Location Address State License Number Phone Fax
HOLD

P. O. Box 1677

Palm Coast, FL 32136

EC0002522 (Exp: 08/31/2010) (386) 437-4364 (386)437-0412
MICHAEL G MORELLO JR
Status Location Address State License Number Phone Fax
CANCEL

2 HARGROVE GRADE

PALM COAST, FL 32137

CAC014293 (Exp: 08/31/2014) (386)447-3950 (386)446-4614
GLEN WILLIAM KEHLE
Status Location Address State License Number Phone Fax
ACTIVE

P. O. Box 353511

BUNNELL, FL 32110

CFC057241 (Exp: 08/31/2026) (386) 447-4249 (386) 437-8488

Inspection History

Type Request Date Result Inspector
ELECTRICAL FINAL 12/15/2008 FINAL APPROVED RMARVEL
Note: THIS IS A REINSPECTION
COMMERCIAL BUILDING FINAL 12/05/2008 APPROVED RMARVEL
ELECTRICAL FINAL 12/05/2008 Disapproved - NO FEE RMARVEL
Note: Inspection Resulted at 12/5/2008 3:17:36 PM REVISE PANEL SCHEDULE TO MATCH PLANS.
H.V.A.C. FINAL 12/05/2008 APPROVED JMCGOWEN
FIRE FINAL 12/05/2008 APPROVED JPATTEE
Note: THIS IS A REINSPECTION
FIRE FINAL 12/03/2008 CANCELLED BY APPLICANT JPATTEE
PLUMBING FINAL 12/03/2008 APPROVED JHINDMAN
COMMERCIAL POWER INSPECTION 12/02/2008 APPROVED RMARVEL
Note: THIS IS A REINSPECTION Inspection Resulted at 12/2/2008 3:41:07 PM COLE
COMMERCIAL POWER INSPECTION 12/01/2008 Disapproved -FEE REQUIRED RMARVEL
Note: REQUESTED BY FOSTER Inspection Resulted at 12/1/2008 3:27:34 PM NEED TO TORQUE LUGS ON FEEDERS. ALSO TO CHECK AT FINAL MC AT SCUTTLE NEEDS TO BE PROTECTED WITHIN 6FT OF SCUTTLE HOLE.
UTILITY COMMERCIAL FINAL 12/01/2008 APPROVED KKING
UTILITY COMPANY FINAL 12/01/2008 APPROVED KKING
FIREWALL INSPECTION 11/24/2008 APPROVED JPATTEE
2ND ROUGH ELECTRICAL 11/21/2008 APPROVED RMARVEL
Note: THIS IS A REINSPECTION requested by Foster
INSULATION INSPECTION 11/20/2008 APPROVED CMINI
2ND ROUGH ELECTRICAL 11/20/2008 Disapproved -FEE REQUIRED JMCGOWEN
Note: Inspection Resulted at 11/20/2008 3:16:44 PM STILL NEED PUT WATER COOLER ON SEPERATE CIRCUIT 13 LOOK AT PLANS. UNUSED CONNECTORS ARE NOT KO PLUGS.
SECOND ROUGH PLUMBING INSPECTION 11/19/2008 APPROVED - AS NOTED JHINDMAN
Note: Inspection Resulted at 11/19/2008 3:49:30 PM INSTALLED AT TIME OF SHELL
2ND ROUGH ELECTRICAL 11/19/2008 Disapproved -FEE REQUIRED RMARVEL
Note: Inspection Resulted at 11/19/2008 2:20:54 PM WATER COOLER IS CALLING FOR ITS OWN CIRCUIT. MOVE SWITCH AT FRONT DOOR AS SHOWN ON THE PLANS.
FRAMING 11/19/2008 APPROVED CMINI
ABOVE CEILING 11/19/2008 APPROVED - AS NOTED RMARVEL
Note: Inspection Resulted at 11/19/2008 2:20:54 PM REMOVE STRAPS FROM GUSSETT PLATES. STRAP MC IN LOCATION SHOWN TO SUPER.
H.V.A.C. ROUGH 11/19/2008 APPROVED JMCGOWEN

Review History

Department Status Date In Date Out
ELEC COMPLETE 12/11/2008 12/11/2008
Note: Released By: SKNOPF Revision Response to comments
ELEC HOLD 12/08/2008 12/09/2008
Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Revision to #2008110072 (Hearing Aid Store @ Unit D-7 55 Plaza Dr.) 12/9/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. NEC 600.5 specifically states the required sign circuit supply no other load. Sign circuit #10 is now shown tied into room lighting. Revise. Note circuit #6 is still identified in panel as "sign". 2. Water Heater EEMAX Mod SP2412 on website appears to have a 2.4KW, 20A, 120V load and is shown requiring #10AWG wire. Revise load calculation and circuit breaker size in panel (per NEC 240.4 and 422.11(E)). Identify wire size requirements on plans for this circuit. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 160 Cypress Point Pkwy, Suite B-106 Palm Coast, Florida 32164 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us
MECH COMPLETE 11/18/2008 11/18/2008
Note: Released By: FREODICA
BLD COMPLETE 11/17/2008 11/17/2008
Note: Released By: FREODICA Correction responce to comments
PLUM COMPLETE 11/17/2008 11/17/2008
Note: Released By: FREODICA
UD1 COMPLETE 11/13/2008 11/14/2008
Note: Released By: CJOHNSON
BLD HOLD 11/10/2008 11/10/2008
Note: Held By: JJOSEPH Provide informartion details as for the existing window that is not shown in the office room of your plan.(Unit D-7)
ELEC COMPLETE 11/10/2008 11/10/2008
Note: Released By: SKNOPF Approved for Release.
FI1 COMPLETE 11/10/2008 11/13/2008
Note: Released By: JPATTEE
MECH HOLD 11/10/2008 11/10/2008
Note: Held By: FREODICA 1. Provide Air Handling Unit (AHU-7)/Condender Unit (CU) and Exhaust Fan Schedules. 2. Indicate on plan the distributed supply air in CFM. 3. Transfer grille between toilet and corridor which is used as a retun plenum is not allowed by code. 4. Revise name designation of AHU No.7 on ground floor to CU-7.
PLUM HOLD 11/10/2008 11/10/2008
Note: Held By: FREODICA 1. Provide location of water heater. Energy calculations show 30 gal. capacity. Do you need this much to supply only (1) lavatory? Please clarify.
ZON COMPLETE 11/07/2008 11/10/2008
Note: Released By: BBARTON verified use interior work only

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REVISION ¤80.00 12/12/2008
REINSPECTION FEE ¤40.00 12/02/2008
REINSPECTION FEE ¤40.00 12/02/2008
REINSPECTION FEE ¤40.00 12/02/2008
SITE PLAN 20 ¤20.00 11/18/2008
ADMIN COMMERCIAL ¤60.00 11/18/2008
ELECTRIC FEE ¤65.92 11/18/2008
FIRE PLANS REVIEW ¤25.00 11/18/2008
MECHANICAL FEE ¤65.92 11/18/2008
PERMIT FEE ¤69.13 11/18/2008
PLAN CHECK FEE ¤100.00 11/18/2008
PLUMBING FEE ¤65.92 11/18/2008
Fees Total Due: ¤0.00 Total Paid: ¤671.89