Permit #2008120377
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7030-00140-0120 |
| Block: 00140 |
| Subdivision: - |
| Job Phone: 386-677-3071 |
| Location Address: 12 RAINROCK PL |
| Type: GEN - GENERATOR |
| Issue Date: 01/06/2009 |
| NOC: Unknown |
| Applicant name: ROBERT EVANS OLIN |
| Owner: MCGLOCKING, GERALDINE |
|
Address 12 RAINROCK PLACE PALM COAST, FL 32164 |
| Lot: 0120 |
| Contracted Stated Job Value: ¤2,300.00 |
| Job Description: INSTALL CUSTOM FURNISHED 20KW GENERATOR, ATS & AG GAS TANK |
| Type: CN |
Contractor
A-1 ENTERPRISES INC
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
57 ABACUS AVE ORMOND BEACH, FL 32174 |
EC0002793 (Exp: 08/31/2020) | (386)677-2278 | (386)677-4461 |
Sub Contractors
RONALD E HUBBARD
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
115N ORANGE ST NEW SMYRNA BEACH, FL 32168 |
01240 (Exp: 08/31/2013) | 386-428-9061 | 386-428-9063 |
Inspection History
| Type | Request Date | Result | Inspector |
| GAS ROUGH | 01/27/2009 | APPROVED | LHITES |
| GAS FINAL | 01/27/2009 | APPROVED | LHITES |
| Note: THIS IS A REINSPECTION | |||
| FINAL INSPECTION (MISC) | 01/27/2009 | FINAL APPROVED | LHITES |
| GAS FINAL | 01/15/2009 | Disapproved -FEE REQUIRED | ACOOPER |
| Note: Inspection Resulted at 1/15/2009 3:36:08 PM ADD A BOND WIRE FROM THE TANK END OF THE LINE TO THE GENERATOR END TO COMPLETE BOND. |
Review History
| Department | Status | Date In | Date Out |
| ZON | COMPLETE | 12/31/2008 | 12/31/2008 |
| Note: Released By: ECOYNE Tank changed to underground again by customer. | |||
| BLD | COMPLETE | 12/30/2008 | 12/31/2008 |
| Note: Released By: SKNOPF Approved for Release. | |||
| BLD | HOLD | 12/29/2008 | 12/29/2008 |
| Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application #2008120377 (Install 20KW Generator, ATS and 250 Gal. Above-ground Tank @ 57 Town Ct.) 12/29/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. Provide conduit and wire feeder sizes for all existing and new feeders. 2. Identify existing electrical panel amperage rating. 3. Provide control wiring diagram with wire size requirements. 4. Identify grounding and bonding requirements per NEC 250. 5. Gas Comment: Provide gas riser diagram showing the total gas consumption in BTU/Hr, approximate total pipe length from gas tank to generator, and delivery pressure. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us | |||
| ZON | COMPLETE | 12/22/2008 | 12/29/2008 |
| Note: Released By: ECOYNE | |||
| ZON | HOLD | 12/17/2008 | 12/17/2008 |
| Note: Held By: BBARTON -there is not an existing permit for a gas tank, please add to permit showing the location and size of tank, indicate if the tank will be above or below ground emailed and faxed hold comments to contractor 12/16/08 @ 10:29 am |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 01/23/2009 |
| SITE PLAN 20 | ¤20.00 | 01/06/2009 |
| ELECTRIC FEE | ¤61.38 | 01/06/2009 |
| PERMIT FEE | ¤20.00 | 01/06/2009 |
| PLAN REVIEW 25 | ¤25.00 | 01/06/2009 |
| PLUMBING FEE | ¤61.38 | 01/06/2009 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤227.76 |