I want to search for...

Permit #2008120525

Permit Details

Status: COED

Parcel Id: 06-12-31-5825-00000-0090
COMMERCIAL SQUARE FOOTAGE: 5743 sqft
Total Square Footage: 5743 sqft
Subdivision: 2088 - TOWN CENTER
Job Phone: (386)677-8736
Location Address: 145 CITY PL
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 04/21/2009
NOC: RECORDED
Applicant name: LEONARD MARINACCO
Owner: CITY CENTRE OF PALM COAST, INC.

Address

4B OLD KINGS RD NORTH

PALM COAST, FL 32137

Lot: 9
Contracted Stated Job Value: ¤300,000.00
Job Description: SUITE 301 - INTERIOR BUILDOUT "PALM COAST CITY CENTRE LAW"
Type: CN

Contractor

BOMAR CONSTRUCTION INC
Status Location Address State License Number Phone Fax
INACTIVE

27 S ORCHARD STREET

ORMOND BEACH, FL 32174

CGC015648 (Exp: 08/31/2022) (386)677-8736 (386)677-7726

Sub Contractors

MATTHEW JOHN WITTWER
Status Location Address State License Number Phone Fax
ACTIVE

231 JEAN STREET

DAYTONA BEACH, FL 32114

EC0002058 (Exp: 08/31/2026) (386)255-1418 (386)255-3429
DONALD G MEYER
Status Location Address State License Number Phone
CANCEL

P. O. Drawer 730008

Ormond Beach, FL 32174

CAC039739 (Exp: 08/31/2016) (386) 253-7774
ISAAC WALTER JOHNSTON
Status Location Address State License Number Phone
ACTIVE

887 BRENTWOOD DRIVE

Daytona Beach, FL 32117

CFC023634 (Exp: 08/31/2026) (386) 252-7047

Inspection History

Type Request Date Result Inspector
COMMERCIAL BUILDING FINAL 11/18/2009 FINAL APPROVED CMINI
UTILITY COMMERCIAL FINAL 11/16/2009 APPROVED DSPENCER
UTILITY COMPANY FINAL 11/13/2009 APPROVED TSCHWEERS
FINAL COMPLETE BUILDING INSPECTION 11/13/2009 APPROVED CMINI
ELECTRICAL FINAL 11/12/2009 APPROVED RMARVEL
H.V.A.C. FINAL 10/06/2009 APPROVED JHINDMAN
Note: THIS IS A REINSPECTION
FIRE FINAL 10/02/2009 APPROVED JPATTEE
H.V.A.C. FINAL 09/28/2009 CANCELLED BY APPLICANT JHINDMAN
PLUMBING FINAL 09/09/2009 APPROVED JHINDMAN
FIREWALL FINAL INSPECTION 08/18/2009 APPROVED JPATTEE
ABOVE CEILING 08/14/2009 APPROVED LHITES
Note: Inspection Resulted at 8/14/2009 12:46:20 PM HVAC
ABOVE CEILING 08/13/2009 APPROVED RMARVEL
COMMERCIAL POWER INSPECTION 08/11/2009 APPROVED RMARVEL
H.V.A.C. ROUGH 07/31/2009 APPROVED JHINDMAN
Note: THIS IS A REINSPECTION
H.V.A.C. ROUGH 07/30/2009 PARTIALLY APPROVED JHINDMAN
Note: THIS IS A REINSPECTION Inspection Resulted at 7/30/2009 1:33:20 PM OK TO WRAP DUCTS
H.V.A.C. ROUGH 07/02/2009 PARTIALLY APPROVED JHINDMAN
Note: Inspection Resulted at 7/2/2009 2:53:13 PM DUCTS OK ABOVE HARD CEILINGS ONLY
2ND ROUGH ELECTRICAL 07/02/2009 APPROVED RMARVEL
H.V.A.C. ROUGH 07/01/2009 Disapproved -FEE REQUIRED JHINDMAN
Note: Inspection Resulted at 7/1/2009 2:59:09 PM CANNOT INSPECT THEJOINTS IN METEL DUCTS THAT HAVE BEEN COVERED BY INSULATION. NEED APPROVED PLANS FOR INSPECTION.
INSULATION INSPECTION 06/16/2009 APPROVED CMINI
2ND ROUGH ELECTRICAL 06/09/2009 APPROVED RMARVEL
Note: Inspection Resulted at 6/9/2009 2:56:26 PM WALLS ONLY
FRAMING 06/09/2009 APPROVED CMINI
SECOND ROUGH PLUMBING INSPECTION 05/28/2009 APPROVED JHINDMAN

Review History

Department Status Date In Date Out
ELEC COMPLETE 11/09/2009 11/09/2009
Note: Released By: JJOSEPH
BLD COMPLETE 11/09/2009 11/09/2009
Note: Released By: JJOSEPH Added door in rm 116 (1) in office rm 115 (1) in corridor 128
ELEC HOLD 11/02/2009 11/02/2009
Note: Held By: SKNOPF Electrical as-builts CITY OF PALM COAST BUILDING DIVISION Comments on Revision to Permit #2008120525 (Palm Coast City Centre Law @ 145 City Pl.) 11/2/2009 The following items must be resolved in order to complete the Building Permit plan review. Comments: 1. The wall and door changes shown on the revised Electrical plans do not match the latest Architectural plans on file. Per AHJ, submit revised Architectural plans showing these changes. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us
ELEC COMPLETE 02/19/2009 02/19/2009
Note: Released By: JMCGOWEN
MECH COMPLETE 02/19/2009 02/19/2009
Note: Released By: FREODICA
PLUM COMPLETE 02/19/2009 02/19/2009
Note: Released By: FREODICA
BLD COMPLETE 02/18/2009 02/19/2009
Note: Released By: JJOSEPH comments review comment revisions
UD1 COMPLETE 02/18/2009 02/23/2009
Note: Released By: CJOHNSON
UD1 HOLD 01/13/2009 01/14/2009
Note: Held By: CJOHNSON Employee lounge's water connection is connected to the adjacent unit's water service. All units shall be individually metered. Verify that Unit 301 has an individual water service coming from the meter room.
PLUM HOLD 01/05/2009 01/05/2009
Note: Held By: FREODICA 1. Provide Domestic Water Riser Diagram (hot/cold water). 2. Provide floor- pipe penetration detail.
FI1 COMPLETE 01/02/2009 01/10/2009
Note: Released By: JPATTEE Sheet E-1 detail (2) indicates painted device to match wall. Only devices painted by the manufaturer shall be allowed. Fire alarm shall require separate permitting not inlcluded on this permit. Automatic fire sprinkler alteration shall require separate permitting not included on this permit.
MECH HOLD 12/31/2008 01/05/2009
Note: Held By: FREODICA 1. Sheet M-1: Key plan shows the area of work does not match with Architectural plan sheet A0.0. 2. Sheet M-2: Corridor is supplied by AHU-4 from Shell Building Permit No. 2007100054. Please clarify if the new proposed design work is in addition to the existing. 3. Sheet M-3: Locations of condensing units HP-1 through HP-5 do not match with the locations shown on Shell Building Permit. Please clarify and coodinate.
BLD HOLD 12/30/2008 01/06/2009
Note: Held By: JJOSEPH 1. Need to use the gross area to calculate the occupant load.
ELEC HOLD 12/30/2008 12/31/2008
Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application #2008120525 (Palm Coast City Center Law @ 143 City Place) 12/31/2008 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. E-2 Load Calculation: a. Per NEC 220.14(A), an outlet for a specific appliance or load shall be calculated based on amp rating of that appliance or load served. Load calculation for Panel A cannot use the demand factor of NEC 220.44 for appliances, copiers, printers, server, etc. These loads must be calculated at full nameplate load. Revise Demand Load Calculation. b. Per NEC 422.13 Storage-type Water Heaters less than 120 gallons shall be considered a continuous load. Revise Demand Load Calculation. 2. E-3: a. Panel A schedule shows all lighting circuits are A-43 thru A-57 odd circuits. Power Plan sheet E-3 shows lighting circuits as A-1 thru A-15 odd circuits, and these circuits are already being used for various branch power items on Sheet E-4. Revise plan sheet E-3 circuits for lighting. b. Plans show a new wall being added within the empty room located at the east end of the North Stairwell, dividing this room into 2 rooms. According to the Shell Building permit #2007100054, this space is "House" space, and therefore the wall must be added as a Revision to the Shell Building permit. Submit revision for this wall. Please note that if either of the 2 new rooms, such as the Server Room, is to be part of the Law Office Tenant space, the square footage and calculations for the House and Tenant space will also need to be adjusted on the Shell building permit #20071200054. c. Plans show a new strip light being added and an existing strip light being relocated in the 2 new rooms located on the east end of the North Stairwell. Both lights are shown to be attached to the existing "House" circuit. "House" space work cannot be performed on this permit application, and a Revision needs to be submitted for any changes made within the "House" designated spaces. d. Transformers for Lobby lighting cannot be located within the "House" common corridor, and must be located within the Tenant space area. 3. E-4: a. Shell Building permit #2007100054 Rev 2 drawings dated 11-5-2007 shows the 3rd Floor Meter Center and 3rd Floor Phone board located in the 2nd Floor Electrical Room adjacent to the North Stairwell. Sheet E-4 and Riser on E-2 both show the 3rd Floor Meter Center on the 3rd floor. Submit a Revision to the Shell Building permit #2007100054 to move this Meter Center. b. If Tenant Panel "A" and "future Tenant panels" are to be installed in the "House" designated space of the new Electrical/Meter room on the 3rd floor, Tenants must have full access to this room and Panel A, such as a key, per NEC 240.24(B); or Panel A can be relocated within the Tenant 'A' spaces. c. Receptacles on circuit A-44, 46, 48 in new Server room cannot be on a Tenant circuit, unless this space is being given to the Tenant for his use, in which case all circuits including lighting must be on Tenant circuits and space must be re-designated as belonging to this Tenant as a Revision to permit #20071200054. See Item 2b above. d. Two receptacles are shown as "existing" located in the new Electrical/Meter room at the east end of the North Stairwell. Existing plans on file for Shell Building permit #2007100054 show no receptacles in this room. Add these receptacles and their circuits under a Revision to the Shell Building permit, and update Shell Building permit load calculations accordingly. e. There are (3) receptacles shown in Corridor 128 which is a common House access corridor. These receptacles, if required, must be added on a "House" circuit as a Revision to the Shell Building permit #2007100054, and cannot be on a Tenant circuit due to their location. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us
ZON COMPLETE 12/30/2008 12/30/2008
Note: Released By: ECOYNE

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION FEE ¤40.00 11/18/2009
REVISION ¤80.00 11/18/2009
SITE PLAN 20 ¤20.00 04/21/2009
ADMIN COMMERCIAL ¤60.00 04/21/2009
ELECTRIC FEE ¤240.00 04/21/2009
FIRE PLANS REVIEW ¤57.43 04/21/2009
MECHANICAL FEE ¤240.00 04/21/2009
PERMIT FEE ¤2,100.00 04/21/2009
PLAN CHECK FEE ¤345.00 04/21/2009
PLUMBING FEE ¤240.00 04/21/2009
Fees Total Due: ¤0.00 Total Paid: ¤3,422.43