I want to search for...

Permit #2009020016

Permit Details

Status: COED

Parcel Id: 09-12-31-0000-02030-0020
COMMERCIAL SQUARE FOOTAGE: 3000 sqft
Total Square Footage: 3000 sqft
Block: 02030
Subdivision: -
Job Phone: 407-916-7235
Location Address: 60 MEMORIAL MEDICAL PKWY
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 03/10/2009
NOC: RECORDED
Applicant name: ROCKY MCMICHEN
Owner: MEMORIAL HOSPITAL-FLAGLER INC

Address

875 STERTHAUS AVENUE

ORMOND BEACH, FL 32174

Lot: 0020
Contracted Stated Job Value: ¤500,000.00
Job Description: EMERGENCY ROOM & LAB RENOVATION
Type: CN

Contractor

THE ROBINS & MORTON GROUP
Status Location Address Mailing Address State License Number Phone Fax
CANCEL

1900 SUMMIT TOWER BLVD.

ORLANDO, FL 32810

SUITE 150

ORLANDO, FL 32810

CGC1506087 (Exp: 08/31/2012) 407-916-7235 407-916-7632

Sub Contractors

RANCE F BORDERICK
Status Location Address State License Number Phone Fax
ACTIVE

430 WEST DRIVE

ALTAMONTE SPRINGS, FL 32714

EC0000981 (Exp: 08/31/2026) (407)788-3500 407-788-2007
TODD SHERWOOD MORGAN
Status Location Address State License Number Phone Fax
CANCEL

777 BENNETT DRIVE

LONGWOOD, FL 32750

CFC043045 (Exp: 08/31/2022) (407)682-1313 (407)682-5166
TODD SHERWOOD MORGAN
Status Location Address State License Number Phone Fax
CANCEL

777 BENNETT DRIVE

LONGWOOD , FL 32750

CMC039581 (Exp: 08/31/2022) 407-682-1313 (407)682-5166

Inspection History

Type Request Date Result Inspector
COMMERCIAL POWER INSPECTION 06/25/2009 APPROVED RMARVEL
COMMERCIAL BUILDING FINAL 06/25/2009 FINAL APPROVED RMARVEL
ELECTRICAL FINAL 06/22/2009 APPROVED LHITES
Note: THIS IS A REINSPECTION Inspection Resulted at 6/22/2009 11:58:47 AM CANNOT FINAL HAS OTHER FINALS TO COMPLETE
ELECTRIC FEEDER 06/22/2009 APPROVED LHITES
H.V.A.C. FINAL 06/19/2009 APPROVED JHINDMAN
GAS FINAL 06/19/2009 APPROVED JHINDMAN
DEMOLITION INSPECTION 06/19/2009 APPROVED JHINDMAN
FIREWALL FINAL INSPECTION 06/19/2009 APPROVED JPATTEE
FLOOR OR WALL PENETRATION 06/19/2009 APPROVED JPATTEE
UTILITY COMMERCIAL FINAL 06/19/2009 APPROVED KKING
UTILITY COMPANY FINAL 06/19/2009 APPROVED KKING
FIRE FINAL 06/19/2009 APPROVED JPATTEE
GAS ROUGH 06/16/2009 APPROVED JHINDMAN
PLUMBING FINAL 06/16/2009 APPROVED JHINDMAN
ELECTRICAL FINAL 06/15/2009 CANCELLED BY APPLICANT RMARVEL
ABOVE CEILING 06/12/2009 PARTIALLY APPROVED RMARVEL
Note: electrical only.
2ND ROUGH ELECTRICAL 06/12/2009 APPROVED RMARVEL
Note: THIS IS A REINSPECTION Pete called to schedule this inspection Inspection Resulted at 6/12/2009 3:32:51 PM ELECTRICAL IN CEILINGS ARE APPROVED.
H.V.A.C. ROUGH 06/12/2009 APPROVED JHINDMAN
Note: THIS IS A REINSPECTION
H.V.A.C. ROUGH 05/22/2009 PARTIALLY APPROVED JHINDMAN
Note: THIS IS A REINSPECTION Inspection Resulted at 5/22/2009 10:34:53 AM ED ROOM INSULATION IS OK. LAB ROOM MAIN SUPPLY IS OK TO INSULATE
H.V.A.C. ROUGH 05/19/2009 PARTIALLY APPROVED JHINDMAN
Note: THIS IS A REINSPECTION Inspection Resulted at 5/19/2009 2:10:08 PM OK TO WRAP DUCTS IN ED ROOM
2ND ROUGH ELECTRICAL 05/07/2009 PARTIALLY APPROVED RMARVEL
Note: Richard called to schedule this inspection Inspection Resulted at 5/7/2009 2:16:05 PM 2ND ROUGH LAB WALLS ONLY.
INSULATION INSPECTION 05/01/2009 PARTIALLY APPROVED JHINDMAN
Note: Inspection Resulted at 5/1/2009 3:21:04 PM ED ROOM IS OK
2ND ROUGH ELECTRICAL 04/29/2009 APPROVED RMARVEL
Note: Hooten called to schedule this inspection
FRAMING 04/28/2009 APPROVED DROCKWELL
SECOND ROUGH PLUMBING INSPECTION 04/27/2009 PARTIALLY APPROVED JHINDMAN
Note: THIS IS A REINSPECTION Inspection Resulted at 4/27/2009 4:03:08 PM PARTIAL COPPER AND MED GAS LINES.
H.V.A.C. ROUGH 04/22/2009 PARTIALLY APPROVED JHINDMAN
Note: THIS IS A REINSPECTION Inspection Resulted at 4/22/2009 3:48:53 PM ED ROOM OK TO WRAP DUCTS.
FIRST ROUGH PLUMBING INSPECTION 04/22/2009 PARTIALLY APPROVED JHINDMAN
Note: Inspection Resulted at 4/22/2009 3:48:53 PM ED ROOM OK EXCEPT S-1. NEED REVISION OF RISER.
SECOND ROUGH PLUMBING INSPECTION 04/22/2009 PARTIALLY APPROVED JHINDMAN
Note: Inspection Resulted at 4/22/2009 3:48:54 PM ED ROOM OK EXCEPT S-1 LAV.
H.V.A.C. ROUGH 04/16/2009 Disapproved -FEE REQUIRED JHINDMAN
Note: Inspection Resulted at 4/16/2009 12:50:36 PM DUCT RUNOUT SIZES DO NOT MATCH DIFFUSER NECK SIZES PER NOTE ON PLAN. TIGHTEN LOOSE DUCT HANGER STRAPS.

Review History

Department Status Date In Date Out
ELEC COMPLETE 06/22/2009 06/22/2009
Note: Released By: JMCGOWEN reviewed by Larry H. and checked by Joe M.
ELEC HOLD 06/19/2009 06/22/2009
Note: Held By: SKNOPF Revision L1N4 L1Ll Panel revision CITY OF PALM COAST BUILDING DIVISION Comments on Revision to #2009020016 (Emergency Room and Lab Renovation @ 60 Memorial Pkwy) 6/22/2009 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. Provide revised power drawing E211 showing additional circuits/devices for both panels L1CL and L1N4. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us
BLD COMPLETE 04/02/2009 04/02/2009
Note: Released By: JMCGOWEN addendum #1 drawings were created in reponse to the stare (ahca) cmments.
ELEC COMPLETE 04/02/2009 04/02/2009
Note: Released By: JMCGOWEN electric revision
ELEC COMPLETE 02/27/2009 02/27/2009
Note: Released By: SKNOPF Approved for Release.
FI1 COMPLETE 02/20/2009 02/27/2009
Note: Released By: JPATTEE submit to comments
UD1 COMPLETE 02/06/2009 02/06/2009
Note: Released By: CJOHNSON
ELEC HOLD 02/05/2009 02/05/2009
Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application #2009020016 (Florida Hospital Flagler Emergency Department and Lab Renovation @ 60 Memorial Medical Pkwy) 2/5/2009 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. E002 and E003: a. Per NEC 220.87, to use the actual maximum demand as the basis of the load calculation, a full year of demand data must be reviewed, not 30 days. Provide 12 months of actual demand data showing highest demand, or revise Demand Load Calculation to reflect all loads of all sub-panels served by Panels LD1N1 and LD1CA. b. New Panel L1N4 and L1CL are both shown on their respective Risers as 120/208V panels, but both panel schedules and load calculations reflect 277/480V panels. Please revise. 2. E211: a. Lounge 1222 shows a refrigerator on circuit L1CK-19, but load in panel schedule is only represented as a convenience receptacle load. Provide appliance nameplate load per NEC 220.14(A) in panel schedule and update load calculation. b. This sheet shows a refrigerator on circuit L1CL-29 and an ice machine on L1CL-27. Panel schedule only shows convenience outlet loads for both circuits. Provide appliance nameplate load per NEC 220.14(A) in panel schedule and update load calculation. c. Circuit L1CL-25 is shown for a Pyxis system, but load in panel schedule is only shown as a convenience receptacle load. Provide appliance/specific load nameplate load per NEC 220.14(A) in panel schedule and update load calculation. d. A Monitor is shown for typical 'CD' on Detail 3/E211, but load shown is only for 2 convenience receptacles. Provide nameplate load for Monitor plus (1) convenience outlet per NEC 220.14(A) for circuits L1CL-7, 8, 15, 16, 24, and 32. e. Circuit L1CL-23 has monitor plus (4) convenience receptacles on this circuit (3 located at Nurses Station). FBC 419.3.15.7.4 states "There shall be no more than two receptacles per circuit" at each patient station. Revise. f. A TV is shown on circuit L1N1B-17 in addition to (3) convenience receptacles. Provide nameplate load for the TV in addition to the (3) convenience receptacle loads, and update load calculation per NEC 220.14(A). g. NEC 220.14(H) provides (2) options for fixed multi-outlet assembly shown in Equipment Alcove 1047. Revise load in panel per NEC 220.14(H)(2). h. Circuit is not identified on E211 for new NCMS shown on E411. Provide circuit and update panel load. 3. E311: a. Provide updated panel schedules for Panels H1CA and H1SB to reflect revised lighting circuits. b. Circuit L1N4-16 is shown for (4) convenience receptacles on Sheet E211, and for new recessed fluorescent lighting on E311. Update panel circuit identification and loads. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us
FI1 HOLD 02/05/2009 02/06/2009
Note: Held By: JPATTEE Plans submitted on February, 3rd 2009 do not comply with the Florida Fire Prevention Code adopted December, 31 2008. Review and ammend to comply with new adopted codes.
MECH COMPLETE 02/05/2009 02/05/2009
Note: Released By: FREODICA
PLUM COMPLETE 02/05/2009 02/05/2009
Note: Released By: FREODICA
ZON COMPLETE 02/03/2009 02/03/2009
Note: Released By: ECOYNE
BLD COMPLETE 02/03/2009 02/04/2009
Note: Released By: JJOSEPH

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REVISION ¤40.00 06/26/2009
REVISION ¤40.00 04/21/2009
REVISION ¤40.00 04/21/2009
REINSPECTION FEE ¤40.00 04/21/2009
SITE PLAN 20 ¤20.00 03/10/2009
ADMIN COMMERCIAL ¤60.00 03/10/2009
ELECTRIC FEE ¤360.00 03/10/2009
FIRE PLANS REVIEW ¤30.00 03/10/2009
MECHANICAL FEE ¤360.00 03/10/2009
PERMIT FEE ¤3,500.00 03/10/2009
PLAN CHECK FEE ¤575.00 03/10/2009
PLUMBING FEE ¤360.00 03/10/2009
Fees Total Due: ¤0.00 Total Paid: ¤5,425.00