I want to search for...

Permit #2009020269

Permit Details

Status: CANCEL

Parcel Id: 18-11-31-0000-02010-0070
Block: 02010
Subdivision: -
Job Phone: (386) 445-4350
Location Address: 5 UTILITY DR
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 03/11/2009
NOC: RECORDED
Applicant name: MICHAEL GLEN MACHIN
Owner: M MACHIN ENTERPRISES INC

Address

P O BOX 353460

PALM COAST, FL 32135

Address

129 BARRINGTON DRIVE

PALM COAST, FL 32135

Lot: 0070
Contracted Stated Job Value: ¤12,500.00
Job Description: UNIT 25 -- INTERIOR ALTERATION- ADD WALLS, BATHROOM & DROP CEILING OFFICE USE
Type: CN

Contractor

MACHIN CONSTRUCTION CO
Status Location Address State License Number Phone Fax
INACTIVE

3 HARGROVE GRADE SUITE 1

Palm Coast, FL 32137

CGC058789 (Exp: 08/31/2024) (386) 445-4350 (386)446-5459

Sub Contractors

DANIEL P HUCKS
Status Location Address State License Number Phone Fax
CANCEL

400 N. U.S. 1

Ormond Beach, FL 32174

CAC029376 (Exp: 08/31/2024) 386-672-8494 386-673-7856
JONATHAN M PEARSON
Status Location Address State License Number Phone Fax
ACTIVE

209 N FORSYTH ST

BUNNELL, FL 32110

CFC1425941 (Exp: 08/31/2026) 386-597-0944 386-437-4996
BEN K REIHL
Status Location Address State License Number Phone Fax
ACTIVE

605 MCINTOSH ROAD

Ormond Beach, 32174

EC0002867 (Exp: 08/31/2026) (386) 677-4464 386-673-4199

Inspection History

Type Request Date Result Inspector
2ND ROUGH ELECTRICAL 01/26/2011 APPROVED CMINI
Note: THIS IS A REINSPECTION requested by contractor
2ND ROUGH ELECTRICAL 01/24/2011 Disapproved -FEE REQUIRED CMINI
Note: Inspection Resulted at 1/24/2011 3:01:22 PM NEED REVISION TO REFLECT WHAT IS INSTALLEDC
FRAMING 07/27/2010 APPROVED JHINDMAN
SECOND ROUGH PLUMBING INSPECTION 02/01/2010 APPROVED JHINDMAN
FIRST ROUGH PLUMBING INSPECTION 08/05/2009 APPROVED - AS NOTED JHINDMAN
Note: Inspection Resulted at 8/5/2009 2:58:28 PM THIS WAS ALREADY INSPECTED ON THE BUILDING SHELL PERMIT.
MONOLITHIC SLAB INSPECTION/SLAB 08/05/2009 APPROVED - AS NOTED JHINDMAN
Note: Inspection Resulted at 8/5/2009 2:58:29 PM THIS WAS ALREADY INSPECTED ON THE BUILDING SHELL PERMIT.
PLUMBING FINAL
ABOVE CEILING
H.V.A.C. ROUGH
H.V.A.C. FINAL
COMMERCIAL POWER INSPECTION
ELECTRICAL FINAL
FIREWALL INSPECTION
FIREWALL FINAL INSPECTION
COMMERCIAL BUILDING FINAL
UTILITY COMMERCIAL FINAL
UTILITY COMPANY FINAL
FIRE FINAL

Review History

Department Status Date In Date Out
ELEC COMPLETE 01/25/2011 01/25/2011
ELEC COMPLETE 02/25/2009 02/25/2009
Note: Released By: JMCGOWEN
MECH COMPLETE 02/24/2009 02/25/2009
Note: Released By: JMCGOWEN ADDRESSING COMMENTS
ELEC HOLD 02/19/2009 02/19/2009
Note: Held By: JMCGOWEN Plan shows in new panel A that both the air handler and the condenser are 60 amp 2 pole breakers with #8 wire. please revise plan to show that these will be fed with proper wire size for 60 amp which is #6 wire
MECH HOLD 02/19/2009 02/19/2009
Note: Held By: JMCGOWEN 1. Provide energy calculations. 2. For clarity, indicate on plan that HVAC system duct layout is the same for both unit 25 and unit 26.
ELEC HOLD 02/17/2009 02/17/2009
Note: Held By: JMCGOWEN Plan shows in new panel A that both the air handler and the condenser are 60 amp 2 pole breakers with #8 wire. please revise plan to show that these will be fed with proper wire size for 60 amp which is #6 wire
FI1 COMPLETE 02/17/2009 02/17/2009
Note: Released By: JPATTEE
MECH HOLD 02/17/2009 02/17/2009
Note: Held By: FREODICA 1. Provide energy calculations. 2. For clarity, indicate on plan that HVAC system duct layout is the same for both unit 25 and unit 26.
PLUM COMPLETE 02/17/2009 02/17/2009
Note: Released By: FREODICA
UD1 COMPLETE 02/17/2009 02/18/2009
Note: Released By: CJOHNSON
ZON COMPLETE 02/16/2009 02/16/2009
Note: Released By: ECOYNE
BLD COMPLETE 02/16/2009 02/17/2009
Note: Released By: JJOSEPH

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
CONTRACTOR CHANGE ¤40.00 03/05/2010
ELECTRIC FEE ¤67.50 03/11/2009
FIRE PLANS REVIEW ¤25.00 03/11/2009
MECHANICAL FEE ¤67.50 03/11/2009
PERMIT FEE ¤87.50 03/11/2009
PLAN CHECK FEE ¤100.00 03/11/2009
PLUMBING FEE ¤67.50 03/11/2009
ADMIN COMMERCIAL ¤60.00 03/11/2009
SITE PLAN 20 ¤20.00 03/11/2009
REINSPECTION FEE ¤40.00
REVISION ¤40.00
Fees Total Due: ¤80.00 Total Paid: ¤535.00