I want to search for...

Permit #2009030089

Permit Details

Status: COED

Parcel Id: 06-12-31-5825-00000-0090
COMMERCIAL SQUARE FOOTAGE: 8070 sqft
Total Square Footage: 8070 sqft
Subdivision: 2088 - TOWN CENTER
Job Phone: (386)677-8736
Location Address: 145 CITY PL
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 04/29/2009
NOC: RECORDED
Applicant name: LEONARD MARINACCO
Owner: CITY CENTRE OF PALM COAST, INC.

Address

4B OLD KINGS RD NORTH

PALM COAST, FL 32137

Lot: 9
Contracted Stated Job Value: ¤325,000.00
Job Description: SUITE 300-- INTERIOR OFFICE BUILDOUT
Type: CN

Contractor

BOMAR CONSTRUCTION INC
Status Location Address State License Number Phone Fax
INACTIVE

27 S ORCHARD STREET

ORMOND BEACH, FL 32174

CGC015648 (Exp: 08/31/2022) (386)677-8736 (386)677-7726

Sub Contractors

MATTHEW JOHN WITTWER
Status Location Address State License Number Phone Fax
ACTIVE

231 JEAN STREET

DAYTONA BEACH, FL 32114

EC0002058 (Exp: 08/31/2026) (386)255-1418 (386)255-3429
DONALD G MEYER
Status Location Address State License Number Phone
CANCEL

P. O. Drawer 730008

Ormond Beach, FL 32174

CAC039739 (Exp: 08/31/2016) (386) 253-7774
ISAAC WALTER JOHNSTON
Status Location Address State License Number Phone
ACTIVE

887 BRENTWOOD DRIVE

Daytona Beach, FL 32117

CFC023634 (Exp: 08/31/2026) (386) 252-7047

Inspection History

Type Request Date Result Inspector
UTILITY COMPANY FINAL 10/22/2009 FINAL APPROVED DSPENCER
UTILITY COMMERCIAL FINAL 10/21/2009 APPROVED DSPENCER
FINAL COMPLETE BUILDING INSPECTION 10/21/2009 APPROVED CMINI
H.V.A.C. FINAL 10/07/2009 APPROVED JHINDMAN
Note: THIS IS A REINSPECTION
ELECTRICAL FINAL 10/06/2009 APPROVED RMARVEL
FIRE FINAL 10/02/2009 APPROVED JPATTEE
H.V.A.C. FINAL 09/28/2009 CANCELLED BY APPLICANT JHINDMAN
PLUMBING FINAL 09/28/2009 APPROVED JHINDMAN
COMMERCIAL POWER INSPECTION 09/17/2009 APPROVED - AS NOTED CMINI
Note: Inspection Resulted at 9/17/2009 3:16:34 PM POWER FOR FEEDERS ON UNIT 300.
ABOVE CEILING 09/14/2009 PARTIALLY APPROVED RMARVEL
Note: Inspection Resulted at 9/14/2009 3:23:30 PM ELECTRICAL ONLY.
ABOVE CEILING 09/11/2009 APPROVED - AS NOTED JHINDMAN
H.V.A.C. ROUGH 09/11/2009 APPROVED JHINDMAN
Note: THIS IS A REINSPECTION
H.V.A.C. ROUGH 07/29/2009 PARTIALLY APPROVED JHINDMAN
Note: Inspection Resulted at 7/29/2009 12:41:59 PM OK TO WRAP METEL DUCT.
FRAMING 07/22/2009 APPROVED CMINI
Note: THIS IS A REINSPECTION
INSULATION INSPECTION 07/20/2009 APPROVED JHINDMAN
INSULATION INSPECTION 07/06/2009 CANCELLED BY INSPECTOR CMINI
FRAMING 06/25/2009 CANCELLED BY APPLICANT CMINI
2ND ROUGH ELECTRICAL 06/23/2009 PARTIALLY APPROVED CMINI
Note: THIS IS A REINSPECTION Inspection Resulted at 6/23/2009 3:49:10 PM WALLS ONLY.
2ND ROUGH ELECTRICAL 06/19/2009 Disapproved -FEE REQUIRED RMARVEL
Note: Inspection Resulted at 6/19/2009 3:35:08 PM NOT READY.
SECOND ROUGH PLUMBING INSPECTION 05/28/2009 APPROVED JHINDMAN

Review History

Department Status Date In Date Out
ELEC COMPLETE 10/01/2009 10/01/2009
Note: Released By: SKNOPF plan revisions showing as-built conditions for electric Approved for Release. Revision: Moved Electric panels to different wall same room Moved phone board Moved receptacle in electric room Added 1 each receptacle to circuits 17, 46 and 50. Added disposal in lounge on dedicated circuit. Added multiple phone outlets
MECH COMPLETE 09/09/2009 09/10/2009
Note: Released By: JMCGOWEN revision - field modifications
BLD COMPLETE 07/15/2009 07/16/2009
Note: Released By: JJOSEPH interior wall & vision lite changes
FD1 COMPLETE 07/14/2009 07/15/2009
Note: Released By: JPATTEE
MECH COMPLETE 04/24/2009 04/24/2009
Note: Released By: FREODICA plan review comment corrections
PLUM COMPLETE 04/09/2009 04/09/2009
Note: Released By: FREODICA
BLD COMPLETE 04/08/2009 04/08/2009
Note: Released By: JJOSEPH provide plan review comments changes
MECH HOLD 04/08/2009 04/09/2009
Note: Held By: FREODICA 1. Provide an approved and tested drywell.
UD1 COMPLETE 03/16/2009 03/17/2009
Note: Released By: CJOHNSON
FI1 COMPLETE 03/13/2009 03/16/2009
Note: Released By: JPATTEE Sheet E-1 detail 2 indicates fire alarm horn/strobe paint to match wall. Device cannot be painted except by manufacturer. Fire alarm installation shall be a separate permit.
MECH HOLD 03/11/2009 03/11/2009
Note: Held By: FREODICA 1. Revise the energy calculations using the updated Form 400A-07 based on FBC 2007 which is in effect since March 1, 2009. Please see Section 13- 400.3. ABC.3 Forms. 2. Sheet M-2: Plan keynote 8 indicates condensate piping drains to be discharged to drywell. Provide location of drywell and its detail. 3. Sheet M5: Mechanical Specifications: Update all FBC reference codes for building, mechanical and plumbing from 2004 to 2007.
PLUM HOLD 03/11/2009 03/11/2009
Note: Held By: FREODICA 1. Provide piping material specifications for sanitary drainage, vent and domestic water (hot & cold).
ELEC COMPLETE 03/11/2009 03/13/2009
Note: Released By: SKNOPF Approved for Release.
BLD HOLD 03/09/2009 03/11/2009
Note: Held By: JJOSEPH 1. Provide accessible counters and elevation details (offics 115and 109) 2.Provide Statement of 2007 Florida Building code as the design code. 3. Page A2.1 indicating '' Enlarge Ceiling Plan and Details" is missing.
ZON COMPLETE 03/06/2009 03/09/2009
Note: Released By: ECOYNE

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION FEE ¤40.00 10/21/2009
REVISION ¤40.00 10/21/2009
REVISION ¤40.00 10/21/2009
REVISION ¤40.00 10/21/2009
SITE PLAN 20 ¤20.00 04/29/2009
ADMIN COMMERCIAL ¤60.00 04/29/2009
ELECTRIC FEE ¤255.00 04/29/2009
FIRE PLANS REVIEW ¤80.70 04/29/2009
MECHANICAL FEE ¤255.00 04/29/2009
PERMIT FEE ¤2,275.00 04/29/2009
PLAN CHECK FEE ¤373.75 04/29/2009
PLUMBING FEE ¤255.00 04/29/2009
Fees Total Due: ¤0.00 Total Paid: ¤3,734.45