I want to search for...

Permit #2009040045

Permit Details

Status: COED

Parcel Id: 09-12-31-0000-02030-0020
COMMERCIAL SQUARE FOOTAGE: 1897 sqft
Total Square Footage: 1897 sqft
Block: 02030
Subdivision: -
Job Phone: 407-916-7235
Location Address: 60 MEMORIAL MEDICAL PKWY
Type: CA - COMM ADDITION
Issue Date: 04/30/2009
NOC: RECORDED
Applicant name: ROCKY MCMICHEN
Owner: MEMORIAL HOSPITAL-FLAGLER INC

Address

875 STERTHAUS AVENUE

ORMOND BEACH, FL 32174

Lot: 0020
Contracted Stated Job Value: ¤1,085,000.00
Job Description: MEMORIAL MEDICAL PARK HOSPITAL CATH LAB ADDITION-- APPLICATION # 1662
Type: CN

Contractor

THE ROBINS & MORTON GROUP
Status Location Address Mailing Address State License Number Phone Fax
CANCEL

1900 SUMMIT TOWER BLVD.

ORLANDO, FL 32810

SUITE 150

ORLANDO, FL 32810

CGC1506087 (Exp: 08/31/2012) 407-916-7235 407-916-7632

Sub Contractors

ANTHONY A TIDWELL
Status Location Address State License Number Phone Fax
INACTIVE

1300 FT. NEGLEY BLVD

NASHVILLE, TN 37203

EC0002156 (Exp: 08/31/2012) 615-350-7270 615-350-7242
TODD SHERWOOD MORGAN
Status Location Address State License Number Phone Fax
CANCEL

777 BENNETT DRIVE

LONGWOOD , FL 32750

CMC039581 (Exp: 08/31/2022) 407-682-1313 (407)682-5166
TODD SHERWOOD MORGAN
Status Location Address State License Number Phone Fax
CANCEL

777 BENNETT DRIVE

LONGWOOD, FL 32750

CFC043045 (Exp: 08/31/2022) (407)682-1313 (407)682-5166
DAVID HENRY SCHMITT
Status Location Address State License Number Phone Fax
CANCEL

405 NEWTECH COURT

DEBARY, FL 32713

CCC045926 (Exp: 08/31/2020) (386)753-1388 (386)753-1588

Inspection History

Type Request Date Result Inspector
LANDSCAPE FINAL 11/30/2009 APPROVED WBUTLER
COMMERCIAL BUILDING FINAL 11/13/2009 APPROVED RMARVEL
UTILITY COMMERCIAL FINAL 11/06/2009 APPROVED DSPENCER
UTILITY COMPANY FINAL 11/06/2009 APPROVED TSCHWEERS
FIRE FINAL 11/06/2009 APPROVED JPATTEE
FIREWALL FINAL INSPECTION 11/06/2009 APPROVED JPATTEE
H.V.A.C. FINAL 11/03/2009 APPROVED JMCGOWEN
PLUMBING FINAL 11/02/2009 APPROVED JHINDMAN
ENGINEERING FINAL 11/02/2009 APPROVED MCOBB
TRAFFIC ENGINEER 11/02/2009 FINAL APPROVED MCOBB
ELECTRIC FEEDER 11/02/2009 APPROVED RMARVEL
Note: THIS IS A REINSPECTION
COMMERCIAL POWER INSPECTION 11/02/2009 APPROVED RMARVEL
ELECTRICAL FINAL 11/02/2009 APPROVED - AS NOTED RMARVEL
Note: Inspection Resulted at 11/2/2009 1:53:06 PM CHECK FOR REVISED PANEL SCH. CPB IN ROOM.
SECOND ROUGH PLUMBING INSPECTION 10/13/2009 APPROVED JHINDMAN
Note: THIS IS A REINSPECTION
ELECTRIC FEEDER 10/13/2009 PARTIALLY APPROVED RMARVEL
ABOVE CEILING 10/13/2009 APPROVED JHINDMAN
H.V.A.C. ROUGH 09/24/2009 APPROVED JHINDMAN
Note: THIS IS A REINSPECTION Inspection Resulted at 9/24/2009 2:55:31 PM MECHANICAL PIPING COMPLETE.
2ND ROUGH ELECTRICAL 08/28/2009 APPROVED LHITES
Note: THIS IS A REINSPECTION
H.V.A.C. ROUGH 08/26/2009 PARTIALLY APPROVED JHINDMAN
Note: THIS IS A REINSPECTION Inspection Resulted at 8/26/2009 2:59:59 PM OK TO INSULATE VTU LINES
2ND ROUGH ELECTRICAL 08/18/2009 PARTIALLY APPROVED RMARVEL
Note: THIS IS A REINSPECTION Inspection Resulted at 8/18/2009 1:30:58 PM NEED REVISION FOR HEAD WALL AND BACK WALL. OTHER WALLS ARE APPROVED.
INSULATION INSPECTION 08/18/2009 APPROVED - AS NOTED RMARVEL
Note: THIS IS A REINSPECTION Inspection Resulted at 8/18/2009 1:30:59 PM NEED AN APPROVED ENERGY SHOWING INSULATION R-VALUE. THERE IS R-19 AT PRESENT.(8/18/2009)
SECOND ROUGH PLUMBING INSPECTION 08/17/2009 CANCELLED BY APPLICANT JHINDMAN
Note: THIS IS A REINSPECTION
SECOND ROUGH PLUMBING INSPECTION 08/14/2009 PARTIALLY APPROVED JMCGOWEN
Note: med. gas test pressure ok, plumbing test pressure ok, need to provide approved revised plumbing plans.
FRAMING 08/14/2009 APPROVED CMINI
Note: THIS IS A REINSPECTION
H.V.A.C. ROUGH 08/14/2009 PARTIALLY APPROVED LHITES
Note: THIS IS A REINSPECTION Inspection Resulted at 8/14/2009 12:46:19 PM AREAS APPROVED ARE HIGHLITED ON PLANS
H.V.A.C. ROUGH 08/07/2009 PARTIALLY APPROVED JHINDMAN
Note: THIS IS A REINSPECTION Inspection Resulted at 8/7/2009 2:45:52 PM PARTIAL SUPPLY DUCTS OK TO INSULATE, PARTIAL RETURN DUCT. SEE PLANS FOR LOCATIONS.
FRAMING 08/06/2009 PARTIALLY APPROVED JHINDMAN
Note: Inspection Resulted at 8/6/2009 1:20:26 PM SHAFTWALL FRAMING
FIREWALL INSPECTION 2ND ROUGH 08/06/2009 Disapproved - NO FEE JPATTEE
Note: Unable to determine what to inspect
ROOF IN PROGRESS 08/05/2009 APPROVED CMINI
ROOF SHEATHING/BRACES/TIES/ DOWN CELL 08/05/2009 APPROVED CMINI
H.V.A.C. ROUGH 08/05/2009 PARTIALLY APPROVED JHINDMAN
Note: Inspection Resulted at 8/5/2009 2:58:30 PM PARTIAL CHILLED WATER LINES ARE OK TO WRAP.
INSULATION INSPECTION 08/03/2009 PARTIALLY APPROVED JHINDMAN
Note: Inspection Resulted at 8/3/2009 2:37:57 PM WALL INSULATION FOR THE HILL HOUSE.
2ND ROUGH ELECTRICAL 07/30/2009 PARTIALLY APPROVED RMARVEL
Note: penthouse holding cooling unit walls only.
EXTERIOR WALL SHEATHING/SHEAR WALL 07/22/2009 APPROVED CMINI
Note: THIS IS A REINSPECTION
MONOLITHIC SLAB INSPECTION/SLAB 07/22/2009 APPROVED CMINI
Note: THIS IS A REINSPECTION
LINTEL 07/21/2009 APPROVED CMINI
FRAMING 07/21/2009 APPROVED CMINI
Note: THIS IS A REINSPECTION
EXTERIOR WALL SHEATHING/SHEAR WALL 07/21/2009 PARTIALLY APPROVED CMINI
ROOF SHEATHING/BRACES/TIES/ DOWN CELL 07/21/2009 APPROVED CMINI
UNDERGROUND ELECTRICAL 07/21/2009 APPROVED RMARVEL
Note: THIS IS A REINSPECTION Hooten called to schedule this inspection
FRAMING 07/16/2009 PARTIALLY APPROVED CMINI
Note: Inspection Resulted at 7/16/2009 3:32:19 PM PARTIAL METAL STUD WALLS 1ST FL TO ROOF ONLY AND 2ND FL SECTION COMPLETE.
MONOLITHIC SLAB INSPECTION/SLAB 07/02/2009 PARTIALLY APPROVED CMINI
Note: Inspection Resulted at 7/2/2009 3:37:48 PM 1ST FL PERIMETER SLAB AND SECOND FL SECTION OF SLAB.
UNDERGROUND ELECTRICAL 07/02/2009 PARTIALLY APPROVED CMINI
Note: Hooten called to schedule this inspection Inspection Resulted at 7/2/2009 3:37:47 PM ELECTRIC CONDUIT IN SLAB TO BE POURED.
FIRST ROUGH PLUMBING INSPECTION 06/29/2009 APPROVED JHINDMAN
FIRST ROUGH PLUMBING INSPECTION 06/26/2009 Disapproved -FEE REQUIRED JHINDMAN
Note: THIS IS A REINSPECTION Inspection Resulted at 6/26/2009 2:37:50 PM DWV DOES NOT MATCH PLANS. TEST PRESSURE IS OK.
FIRST ROUGH PLUMBING INSPECTION 06/19/2009 PARTIALLY APPROVED JHINDMAN
Note: Inspection Resulted at 6/19/2009 3:15:27 PM UNDER SLAB STORM DRAIN LINE.
FOOTER 05/13/2009 APPROVED CMINI

Review History

Department Status Date In Date Out
ELEC COMPLETE 11/12/2009 11/12/2009
Note: Released By: SKNOPF revision - S & S revised schedule Approved for Release.
ELEC COMPLETE 08/31/2009 08/31/2009
Note: Released By: LHITES
PLUM COMPLETE 08/31/2009 08/31/2009
Note: Released By: FREODICA Revision 1 dated 2/17/09- Sheets P001, P202 & P203.
BLD COMPLETE 08/31/2009 09/01/2009
Note: Released By: JJOSEPH Revision Life safety G111 A11, A641, A801- Detail changes Pool- Plumbing schedule P202- water change P203
MECH COMPLETE 08/27/2009 08/27/2009
Note: Released By: JMCGOWEN revision- relocation of outlet, mcb panel, modify duct, headwall layout, med-gas outlets.
ELEC COMPLETE 08/27/2009 08/27/2009
Note: Released By: JMCGOWEN revision- relocation of outlet, mcb panel, modify duct, headwall layout
PLUM COMPLETE 08/27/2009 08/27/2009
Note: Released By: JMCGOWEN revision- relocation of outlet, mcb panel, modify duct, headwall layout, med-gas outlets.
MECH HOLD 08/25/2009 08/25/2009
Note: Held By: FREODICA revision- relocation of outlet, mcb panel, modify duct, headwall layout, med-gas outlets. Review comment: 1. Provide (2) stamped copies of full size plan instead of 8-1/2 x11 size drawing.
ELEC HOLD 08/25/2009 08/25/2009
Note: Held By: SKNOPF revision- relocation of outlet, mcb panel, modify duct, headwall layout CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application #2009040045 (Cath Lab Renovation @ 60 Memorial Medical Pkwy.) 8/25/2009 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. Provide revision plan changes on plan size sheets, signed and sealed by the architect/engineer of record (2 copies). …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us
PLUM HOLD 08/25/2009 08/25/2009
Note: Held By: FREODICA revision- relocation of outlet, mcb panel, modify duct, headwall layout, med-gas outlets. Review comment: 1. Provide (2) stamped copies of full size plan instead of 8-1/2 x11 size drawing.
BLD COMPLETE 08/17/2009 08/17/2009
Note: Released By: JMCGOWEN revision - rev # 3
FD1 COMPLETE 08/17/2009 08/18/2009
Note: Released By: JPATTEE revision - rev # 3
ELEC COMPLETE 08/14/2009 08/17/2009
Note: Released By: JMCGOWEN revision - rev # 3 Approved for Release. Revision: Relocated Cath Panel Moved a receptacle and a data outlet Added a Warning Light Revised overhead and floor duct locations
PLUM COMPLETE 06/26/2009 06/26/2009
Note: Released By: JMCGOWEN revision - p 201 - underground
MECH COMPLETE 04/24/2009 04/27/2009
Note: Released By: BBEMBRY Correction submitted indicating a mechanical/electrical review was necessary. it was determinted the correction letter submitted was only necessary for fire.
FD1 COMPLETE 04/23/2009 04/23/2009
Note: Released By: JPATTEE correction - electricial & mechanical s and s code letters
FD1 COMPLETE 04/22/2009 04/23/2009
Note: Released By: JPATTEE In reviewing the AHCA letter dated February 5, 2009 it has become apparent that the code review completed by AHCA after January 1, 2009 had referenced the codes which were no longer applicable and approved the the plans. I will forward this Information to the State Fire Marshal for follow up investigation
MECH COMPLETE 04/21/2009 04/21/2009
Note: Released By: FREODICA Correction Sheet M002- new constant volume terminal unit schedule Email Corr. and AHCA approved letter dated 2/5/09 Signed & Sealed construction documents dated 1/23/09
BLD COMPLETE 04/13/2009 04/13/2009
Note: Released By: JJOSEPH
FI1 COMPLETE 04/13/2009 04/23/2009
Note: Released By: JPATTEE
UD1 COMPLETE 04/06/2009 04/08/2009
Note: Released By: CJOHNSON
ELEC COMPLETE 04/06/2009 04/06/2009
Note: Released By: SKNOPF Approved for Release.
FI1 HOLD 04/06/2009 04/08/2009
Note: Held By: JPATTEE Sheet G001, Various NFPA codes indicated are outdated, resubmit corrected plans according to current adopted codes.
MECH HOLD 04/03/2009 04/03/2009
Note: Held By: FREODICA 1. Sheet M002: New Constant Volume Terminal Unit Schedule: a. Clarify if the units are constant or variable volume units as the plans and schedule do not match.
PLUM COMPLETE 04/03/2009 04/03/2009
Note: Released By: FREODICA
BLD HOLD 04/03/2009 04/06/2009
Note: Held By: JJOSEPH 1.The design code needs to be updated to the Statement 2007 and supplement 2009 of The Florida Building Code
ZON COMPLETE 04/02/2009 04/02/2009
Note: Released By: ECOYNE

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REVISION ¤80.00 11/16/2009
REVISION ¤40.00 11/16/2009
REVISION ¤40.00 11/16/2009
REVISION ¤80.00 11/16/2009
REVISION ¤40.00 11/16/2009
REVISION ¤40.00 08/18/2009
REINSPECTION FEE ¤40.00 08/18/2009
REVISION ¤40.00 08/18/2009
REVISION ¤80.00 08/18/2009
SITE PLAN 20 ¤20.00 04/30/2009
TRANSPORTATION IMPACT FEE ¤8,502.39 04/30/2009
ADMIN COMMERCIAL ¤60.00 04/30/2009
BUILDING CODE ADMIN FUND ¤9.49 04/30/2009
ELECTRIC FEE ¤711.00 04/30/2009
FIRE PLANS REVIEW ¤25.00 04/30/2009
FIRE IMPACT FEE RES 4/01/08 ¤1,000.48 04/30/2009
MECHANICAL FEE ¤711.00 04/30/2009
PERMIT FEE ¤7,595.00 04/30/2009
PLAN CHECK FEE ¤1,247.75 04/30/2009
PLUMBING FEE ¤711.00 04/30/2009
RADON FEE ¤9.49 04/30/2009