Permit #2009120254

Permit Details

Status: COED

Parcel Id: 07-11-31-7013-00000-0300
COMMERCIAL SQUARE FOOTAGE: 372 sqft
Total Square Footage: 372 sqft
Block: 00000
Subdivision: 2192 - SECTION 13-BELLE TERRE
Job Phone: 321-259-6124
Location Address: 2850 PALM COAST PKWY NW
Type: BC - BUILDING COMMERCIAL
Issue Date: 01/14/2010
NOC: Unknown
Applicant name: DANIEL JUDE HOWICK
Owner: CITY OF PALM COAST

Address

SUITE B-106

PALM COAST, FL 32164

Address

160 CYPRESS POINT PKWY

PALM COAST, FL 32164

Lot: 0300
Contracted Stated Job Value: ¤68,539.00
Job Description: INSTALL PREFAB CO-LOCATION BLDG FOR COMMUNICATIONS W/POWER SERVICE & GENERATOR
Type: CN

Contractor

DANELLA CONSTRUCTION CORPORATION OF FL, INC
Status Location Address State License Number Phone Fax
ACTIVE

581 WASHBURN ROAD

MELBOURNE, FL 32934

CGC1517889 (Exp: 08/31/2026) 321-259-6124 321-242-0106

Sub Contractors

JOHN WAYNE YANEY II
Status Location Address State License Number Phone Fax
CANCEL

1812 TRAVELERS PALM DR.

EDGEWATER, FL 32132

EC13003852 (Exp: 08/31/2020) 386-427-5687 386-424-9652
DAVID CASH
Status Location Address State License Number Phone Fax
CANCEL

45 SOUTH DIXIE HIGHWAY

ST. AUGUSTINE, FL 32084

01613 (Exp: 08/31/2014) (386)437-3433 904-829-1844

Inspection History

Type Request Date Result Inspector
FIRE FINAL 05/20/2010 FINAL APPROVED JPATTEE
Note: Inspection Requested at 5/19/2010 3:50:05 PM 11 AM INSPECTION PLEASE.
ELECTRICAL FINAL 05/14/2010 APPROVED RMARVEL
Note: THIS IS A REINSPECTION Inspection Requested at 5/13/2010 4:24:25 PM BLDG IS LOCKED, PLEASE CALL 986-4732 FOR ENTRY.
COMMERCIAL BUILDING FINAL 05/14/2010 APPROVED RMARVEL
Note: Inspection Requested at 5/13/2010 4:25:44 PM BLDG IS LOCKED, PLEASE CALL 986-4732 FOR ENTRY.
COMMERCIAL BUILDING FINAL 05/05/2010 CANCELLED BY APPLICANT AIRS WEB
FIRE FINAL 05/05/2010 CANCELLED BY APPLICANT AIRS WEB
LANDSCAPE FINAL 04/15/2010 APPROVED WBUTLER
ELECTRIC FEEDER 03/25/2010 APPROVED RMARVEL
Note: THIS IS A REINSPECTION
COMMERCIAL POWER INSPECTION 03/25/2010 APPROVED RMARVEL
ELECTRICAL FINAL 03/24/2010 CANCELLED BY APPLICANT JMONTARULI
ELECTRIC FEEDER 02/16/2010 Disapproved -FEE REQUIRED LHITES
Note: Inspection Resulted at 2/16/2010 1:47:05 PM NEED PLANS SHOWING GENERATOR HOOK UP. AND WIRE SIZES
FOOTER 01/28/2010 APPROVED CMINI

Review History

Department Status Date In Date Out
ELEC COMPLETE 03/19/2010 03/19/2010
Note: Released By: SKNOPF correction to the revision - elect. riser drawing along with other generator info and elect. wire changes Approved for Release.l
ELEC HOLD 03/15/2010 03/15/2010
Note: Held By: SKNOPF Riser drawing showing additional details for generator wiring CITY OF PALM COAST BUILDING DIVISION Comments on Revision to #2009120254 (Prefab Co-location Bldg with Power Service & Generator@ 2850 Palm Coast Pkwy. NW.) 3/15/2010 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. Provide generator bond size to ground rod if generator is not a separately derived system, as shown by the grounded neutrals being tied together at the ATS. 2. Clarify terminations and purpose of 3-#10 from panel to generator. 3. Provide revised equipment grounding conductor from generator to ATS, and ATS to panel per NEC 250.122. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 160 Cypress Point Pkwy Ste B106 Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us
ELEC HOLD 02/24/2010 02/24/2010
Note: Held By: SKNOPF Riser drawings showing additional details for generator wriing. CITY OF PALM COAST BUILDING DIVISION Comments on Revision to Permit #2009120254 (Prefab Co-location Building with Power Service & Generator @ 2850 Palm Coast Pkwy.) 2/24/2010 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. Electrical Riser needs to be signed and sealed by a design professional, since original riser was signed and sealed. 2. Clarify quantity of conductors and if 500MCM service wire is copper or aluminum. Adjust grounding electrode conductor size as required. 3. Provide generator, ATS and panel on electrical riser. 4. Provide feeder sizes for both generator and ATS equipment including equipment grounding conductor. 5. Provide generator separately derived system ground per NEC 250.30. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 2 Commerce Boulevard Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us
FI1 COMPLETE 01/13/2010 01/14/2010
Note: Released By: JPATTEE corrections letter notice that fire suppression system will be installed prior to c/o issuance
ELEC COMPLETE 12/17/2009 12/17/2009
Note: Released By: LHITES submitted via mail: cut sheets for generator and transfer switch
ELEC HOLD 12/15/2009 12/14/2009
Note: Held By: JMCGOWEN provide cut sheets for generator and transfer switch
FI1 HOLD 12/14/2009 12/15/2009
Note: Held By: JPATTEE Need more information on type of equipment, suppression
BLD COMPLETE 12/14/2009 12/14/2009
Note: Released By: JMCGOWEN
ZON COMPLETE 12/11/2009 12/14/2009
Note: Released By: ECOYNE

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADDITIONAL FEE ¤40.00 04/14/2010
REINSPECTION FEE ¤40.00 04/14/2010
REVISION ¤40.00 04/14/2010
SITE PLAN 20 ¤20.00 01/14/2010
ADMIN COMMERCIAL ¤60.00 01/14/2010
BUILDING CODE ADMIN FUND ¤1.86 01/14/2010
BUILDING DISCOUNT 100% (¤576.81) 01/14/2010
ELECTRIC FEE ¤101.40 01/14/2010
FIRE COMM IMPACT FEE 4/1/09 ¤196.38 01/14/2010
FIRE PLANS REVIEW ¤25.00 01/14/2010
PERMIT FEE ¤379.50 01/14/2010
PLAN CHECK FEE ¤100.00 01/14/2010
RADON FEE ¤1.86 01/14/2010
Fees Total Due: ¤0.00 Total Paid: ¤429.19