I want to search for...
Permit #2010030287
Permit Details
Status: COED
| Parcel Id: 33-11-31-3060-00020-0070 |
| CONDITIONED SPACE: 1638 sqft |
| GARAGE: 465 sqft |
| OPENED PORCH (WITH ROOF) : 120 sqft |
| OPENED PORCH (WITH ROOF) : 24 sqft |
| Total Square Footage: 2247 sqft |
| Block: 00020 |
| Subdivision: 2106 - HIDDEN LAKES, PHASE 1 |
| Job Phone: (386) 246-6125 |
| Location Address: 40 ARROWHEAD DR |
| Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY |
| Issue Date: 03/24/2010 |
| NOC: RECORDED |
| Applicant name: BRIAN ANDREW GAZZOLI |
| Owner: SEAGATE HOMES LLC |
|
Address 185 CYPRESS POINT PKWY PALM COAST, FL 32164 |
|
Address SUITE 7 PALM COAST, FL 32164 |
| Lot: 0070 |
| Contracted Stated Job Value: ¤138,754.00 |
| Job Description: SINGLE FAMILY RESIDENCE |
| Type: CN |
Contractor
SEAGATE HOMES, LLC
| Status | Location Address | Mailing Address | State License Number | Phone |
| ACTIVE |
185 CYPRESS POINT PARKWAY Palm Coast, FL 32137 |
SUITE 7 Palm Coast, FL 32137 |
CGC1518372 (Exp: 08/31/2026) | 386-246-6132 |
Sub Contractors
WILLIAM FRANK DUDLEY JR.
| Status | Location Address | State License Number | Phone |
| ACTIVE |
P.O. BOX 978 Bunnell, FL 32110 |
EC0003177 (Exp: 08/31/2026) | (386)437-3068 |
MICHAEL G MORELLO JR
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
2 HARGROVE GRADE PALM COAST, FL 32137 |
CAC014293 (Exp: 08/31/2014) | (386)447-3950 | (386)446-4614 |
DENNIS GENE GAINEY
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
P.O. BOX 1203 Bunnell, FL 32110 |
CFC046004 (Exp: 08/31/2026) | (386) 437-5637 | 386-437-3012 |
SANTOS L HERNANDEZ
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
946 SHADDICK DRIVE ORANGE CITY, FL 32763 |
CCC1328011 (Exp: 08/31/2026) | 386-218-4942 | 386-218-4937 |
MICHAEL L GARDNER
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
21 Sunshine Blvd Ormond Beach, FL 32174 |
CRC036596 (Exp: 08/31/2012) | (386) 677-2677 | (386)676-2467 |
Inspection History
| Type | Request Date | Result | Inspector |
| FINAL COMPLETE BUILDING INSPECTION | 07/13/2010 | FINAL APPROVED | JHINDMAN |
| Note: THIS IS A REINSPECTION 7/8/10 (PA) - LANDSCAPE OK | |||
| FINAL COMPLETE BUILDING INSPECTION | 07/08/2010 | Disapproved -FEE REQUIRED | JHINDMAN |
| Note: Inspection Resulted at 7/8/2010 3:06:49 PM THE RECEPTACLE AT THE LEFT HAND SIDE OF THE SINK IS MORE THAN 24" FROM THE SINK. THE RECEPTACLE TO THE RIGHT OF THE STOVE IS MORE THAN 24" FROM THE STOVE. | |||
| STORMWATER FINAL INSPECTION | 07/06/2010 | APPROVED | DRANDALL |
| Note: 4/14/10 everything ok per site check by DR | |||
| UTILITY COMPANY FINAL | 06/28/2010 | APPROVED | MBACON |
| Note: TV BY MARTY BACON EVERYTHING OK sewer clean out needs to be 6". Not a 6" pipe over top of a piece of 4" pipe. | |||
| RESIDENTIAL EARLY POWER | 06/21/2010 | APPROVED | JHINDMAN |
| Note: Inspection Resulted at 6/21/2010 2:55:17 PM CALLED FPL ON 6-21-10 AT 2:50 P.M. | |||
| INSULATION INSPECTION | 05/18/2010 | APPROVED | DROCKWELL |
| LATH /BRICK FLASHING | 05/12/2010 | APPROVED | JHINDMAN |
| Note: REQUESTED BY BOB | |||
| ALL ROUGH | 05/11/2010 | APPROVED | JHINDMAN |
| Note: THIS IS A REINSPECTION | |||
| ALL ROUGH | 05/10/2010 | CANCELLED BY APPLICANT | JHINDMAN |
| ROOF SHEATHING/BRACES/TIES/ DOWN CELL | 05/10/2010 | APPROVED | JHINDMAN |
| Note: THIS IS A REINSPECTION | |||
| ROOF SHEATHING/BRACES/TIES/ DOWN CELL | 05/04/2010 | Disapproved -FEE REQUIRED | CMINI |
| Note: Inspection Resulted at 5/4/2010 2:56:15 PM NEED TO HAVE REVISED PLAN ON JOB FOR DELETED WINDOW AND ADDED SKYLIGHTS. | |||
| EXTERIOR WALL SHEATHING/SHEAR WALL | 05/03/2010 | APPROVED - AS NOTED | CMINI |
| Note: Inspection Resulted at 5/3/2010 3:09:16 PM NAIL PATTEREN ON GABLE AND FRONT ENTRY...NEED REVISION FOR DELETED WINDOW AT REAR. | |||
| LINTEL | 04/20/2010 | APPROVED | JHINDMAN |
| FOUNDATION SURVEY APPROVED BY STORMWATER | 04/19/2010 | APPROVED | LAPTEKAR |
| FOUNDATION SURVEY APPROVED BY ZONING | 04/19/2010 | APPROVED | BBARTON |
| MONOLITHIC SLAB INSPECTION/SLAB | 04/15/2010 | APPROVED | JHINDMAN |
| FIRST ROUGH PLUMBING INSPECTION | 04/13/2010 | APPROVED | DROCKWELL |
Review History
| Department | Status | Date In | Date Out |
| BLD | COMPLETE | 05/04/2010 | 05/03/2010 |
| Note: Released By: JMCGOWEN converted dent ot bedroom # 3 added skylights archtectural package and foyer columns added screen to covered lanai changed master bedroom sgd to a french door added set of half round columns to master bedroom entry sheets 0.1,1.0,2.0,4.0,4.3,5.0,6.0,7.0,affected re printred the entire job | |||
| ZON | COMPLETE | 05/03/2010 | 05/03/2010 |
| Note: Released By: BBARTON added screen to covered lanai | |||
| ELEC | COMPLETE | 03/17/2010 | 03/17/2010 |
| Note: Released By: SKNOPF revised load calcualtions to include microwave disposal and irrigation pump updated electrical riser to show CU and AL Approved for Release. | |||
| ZON | COMPLETE | 03/16/2010 | 03/16/2010 |
| Note: Released By: BBARTON | |||
| SW1 | COMPLETE | 03/16/2010 | 03/16/2010 |
| Note: Released By: LAPTEKAR received new site plan with rear set back erosion control measures required (side note: driveway detail plan supplied is not required as this is a culvert detail with concrete apron, this subdivision does not have culverts and the driveway on the site plan is pavers) | |||
| MECH | COMPLETE | 03/16/2010 | 03/16/2010 |
| Note: Released By: FREODICA Correction to energy calculations. | |||
| BLD | COMPLETE | 03/15/2010 | 03/15/2010 |
| Note: Released By: JJOSEPH | |||
| ELEC | HOLD | 03/15/2010 | 03/15/2010 |
| Note: Held By: SKNOPF CITY OF PALM COAST BUILDING DIVISION Comments on Permit Application #2010030287 (Single Family Residence @ 40 Arrowhead Dr.) 3/15/2010 The following items must be resolved in order to complete the Building Permit plan review. Electrical Comments: 1. Provide revised Load Calculation to include all appliances, ie microwave, disposal, irrigation pump. …………………………………………… Susan J. Knopf Plans Examiner City of Palm Coast - Building Division 160 Cypress Point Pkwy Ste B106 Palm Coast, Florida 32164-3216 [tel]: (386) 986-2463 [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us [fax]: (386) 986-3781 [email]: sknopf@ci.palm-coast.fl.us | |||
| MECH | HOLD | 03/15/2010 | 03/15/2010 |
| Note: Held By: FREODICA 1. Energy calculations show design location as St. Augustine, FL (page 1 of 5) but the HVAC unit sizing was based on Daytona Beach, FL (page 1 of Manual J of 8th edition). Please clarify. | |||
| PLUM | COMPLETE | 03/15/2010 | 03/15/2010 |
| Note: Released By: FREODICA | |||
| ZON | HOLD | 03/15/2010 | 03/15/2010 |
| Note: Held By: BBARTON All holds satisfied except the following: 1. Provide ARC color and material approval. spoke with contractor regarding hold comment 03/15/10 @ 4:41pm | |||
| SW1 | HOLD | 03/12/2010 | 03/12/2010 |
| Note: Held By: LAPTEKAR need rear set back information on site plan...30' drainage easement on site with edge of water | |||
| ZON | HOLD | 03/12/2010 | 03/12/2010 |
| Note: Held By: BBARTON 1. Site plan is missing side and rear setbacks. 2. Site plan is missing house dimensions. 3. Plant schedule is missing plant size and spacing. 4. Landscape Plan is missing the Replacement Tree Index. 5. AC pad requires landscaping (min height to be 30" at time of installation). 6. Provide color and materials 7. Boundary/Landscape Plan needs to indicate "No Index Trees" on lot. faxed and emailed hold comments to contractor 03/12/10 @ 1:05 pm Contractor will submitt ARC approval for colors |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| EARLY POWER INSPECTION | ¤40.00 | 07/13/2010 |
| CONTRACTOR CHANGE | ¤40.00 | 07/13/2010 |
| REINSPECTION FEE | ¤40.00 | 07/13/2010 |
| REINSPECTION FEE | ¤40.00 | 07/13/2010 |
| REVISION | ¤40.00 | 07/13/2010 |
| SCHOOL BOARD IMPACT FEE RES | ¤3,600.00 | 03/24/2010 |
| SITE PLAN 20 | ¤20.00 | 03/24/2010 |
| STORM WATER PERMIT FEES | ¤80.00 | 03/24/2010 |
| TRANS IMPACT FEE 7-RESIDENTIAL | ¤3,565.34 | 03/24/2010 |
| NEW RESIDENTIAL INSPECTIONS | ¤354.00 | 03/24/2010 |
| BUILDING DISCOUNT 100% | (¤849.06) | 03/24/2010 |
| ELECTRIC FEE | ¤166.20 | 03/24/2010 |
| FIRE COMM IMPACT FEE 4/1/09 | ¤190.48 | 03/24/2010 |
| MECHANICAL FEE | ¤166.20 | 03/24/2010 |
| PERMIT FEE | ¤20.00 | 03/24/2010 |
| PARKS IMPACT FEE 4/1/09 | ¤1,230.83 | 03/24/2010 |
| PLAN CHECK FEE | ¤70.80 | 03/24/2010 |
| PLUMBING FEE | ¤166.20 | 03/24/2010 |
| RADON FEE | ¤11.24 | 03/24/2010 |
| BUILDING CODE ADMIN FUND | ¤11.24 | 03/24/2010 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤9,003.47 |