I want to search for...
Permit #2010040768
Permit Details
Status: FINAL
| Parcel Id: 16-11-30-0000-01010-0020 |
| Block: 01010 |
| Subdivision: - |
| Job Phone: 386-447-6767 |
| Location Address: 77 HARGROVE GRADE |
| Type: CMP - COMMERCIAL MISC |
| Issue Date: 05/17/2010 |
| NOC: Unknown |
| Applicant name: CHARLES M BURGAN III |
| Owner: MATSCHEL OF FLAGLER INC |
|
Address 71 HARGROVE GRADE PALM COAST, FL 32137 |
| Lot: 0020 |
| Contracted Stated Job Value: ¤700.00 |
| Job Description: RELOCATE 3 PLASTIC STORAGE TANKS & 1 STAINLESS STEEL TANK |
| Type: CN |
Contractor
CHARLES BURGAN, LLC
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
1132 HARDY ST BUNNELL, FL 32110 |
CGC1512729 (Exp: 08/31/2026) | 386-206-3150 | 386-206-3150 |
Sub Contractors
RICHARD R EDWARDS
| Status | Location Address | State License Number | Phone |
| CANCEL |
P. O. Box 1637 Bunnell, FL 32110 |
ER0011603 (Exp: 08/31/2022) | (386) 437-1537 |
Inspection History
| Type | Request Date | Result | Inspector |
| FINAL INSPECTION (MISC) | 06/03/2010 | FINAL APPROVED | CMINI |
| Note: THIS IS A REINSPECTION | |||
| ELECTRICAL FINAL | 06/02/2010 | APPROVED | CMINI |
| Note: THIS IS A REINSPECTION | |||
| 2ND ROUGH ELECTRICAL | 06/02/2010 | APPROVED | CMINI |
| Note: THIS IS A REINSPECTION | |||
| ELECTRICAL FINAL | 05/25/2010 | CANCELLED BY APPLICANT | CMINI |
| MONOLITHIC SLAB INSPECTION/SLAB | 05/25/2010 | CANCELLED BY INSPECTOR | CMINI |
| Note: Inspection Resulted at 5/25/2010 2:21:17 PM NOT REQUIRED | |||
| 2ND ROUGH ELECTRICAL | 05/25/2010 | Disapproved -FEE REQUIRED | CMINI |
| Note: Inspection Resulted at 5/25/2010 2:21:16 PM NEED REVISION TO SHOW CORRECT WIRE SIZE OR CHANGE OCP IN PANEL TO PROTECT NO. 10 WIRE....NEED TO STRAP CONDUIT WITHIN 3`` OF PANEL AND BETTER STRAPPING ON RUN...NEED TO HAVE PANEL SCHEDULE AND IDENTIFY BREAKERS.... | |||
| FINAL INSPECTION (MISC) | 05/25/2010 | CANCELLED BY APPLICANT | CMINI |
| LANDSCAPE FINAL | 05/25/2010 | APPROVED | WBUTLER |
Review History
| Department | Status | Date In | Date Out |
| ZON | COMPLETE | 05/12/2010 | 05/12/2010 |
| Note: Released By: CBENTLEY Location inside of building Tanks will consist of water and light chemicals. | |||
| ENGIN1 | COMPLETE | 05/12/2010 | 05/12/2010 |
| Note: Released By: AWEBB | |||
| PLLA | COMPLETE | 05/11/2010 | 05/11/2010 |
| Note: Released By: WBUTLER | |||
| PLENV | COMPLETE | 05/11/2010 | 05/11/2010 |
| Note: Released By: DBEVAN Released by Denise Bevan | |||
| UTL | COMPLETE | 05/07/2010 | 05/10/2010 |
| Note: Released By: CJOHNSON | |||
| FD1 | COMPLETE | 05/05/2010 | 05/07/2010 |
| Note: Released By: JPATTEE | |||
| ELEC | COMPLETE | 05/05/2010 | 05/05/2010 |
| Note: Released By: JMCGOWEN Correction response to comments | |||
| BLD | COMPLETE | 04/28/2010 | 04/28/2010 |
| Note: Released By: JMCGOWEN | |||
| ELEC | HOLD | 04/28/2010 | 04/28/2010 |
| Note: Held By: LHITES 1. Please provide size and type of electrical conduit. 2. Provide size and type of electrical wire. 3. Provide agitator motor size and load 4. Please provide service type re: single phase or 3 phase | |||
| ZON | HOLD | 04/27/2010 | 04/27/2010 |
| Note: Held By: ECOYNE provide site plan showing location of storage and steel tank provide purpose of tanks faxed 04/27/10 ecoyne 4:56pm |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 06/02/2010 |
| ADMIN COMMERCIAL | ¤60.00 | 05/17/2010 |
| BUILDING DISCOUNT 100% | (¤189.00) | 05/17/2010 |
| PERMIT FEE | ¤50.00 | 05/17/2010 |
| PLAN CHECK FEE | ¤100.00 | 05/17/2010 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤61.00 |