Permit #2010100159

Permit Details

Status: FINAL

Subdivision: 2242 - PALM COAST LANDING AT TOWN CENTER, PH VII
Job Phone: 386-738-3473
Location Address: 5294 HIGHWAY 100 E
Type: FS - FIRE SPRINKLER WET COMMERCIAL
Issue Date: 10/12/2010
NOC: RECORDED
Applicant name: ROBERT THOMPSON
Owner: PALM COAST CENTER LLC WEINGARTEN REALTY INVESTORS

Address

P.O. BOX 3467

HOUSTON, TX 77253

Contracted Stated Job Value: ¤19,999.00
Job Description: OLIVE GARDEN/RED LOBSTER FIRE SPRINKLER SYSTEM
Type: CN

Contractor

NORTH FLORIDA FIRE PROTECTION, INC
Status Location Address State License Number Phone Fax
CANCEL

1402 EAST YORKTOWN STREET

DELAND, FL 32724

9077980012000 (Exp: 06/30/2012) 386-738-3473 386-785-1384

Inspection History

Type Request Date Result Inspector
FIRE SPRINKLER FINAL INSPECTION 01/20/2011 FINAL APPROVED LHITES
Note: THIS IS A REINSPECTION
FIRE SPRINKLER FINAL INSPECTION 01/19/2011 CANCELLED BY APPLICANT LHITES
FIRE SPRINKLER HYDROSTATIC TEST 11/16/2010 APPROVED LHITES
Note: THIS IS A REINSPECTION
FIRE SPRINKLER 1ST ROUGH 11/16/2010 APPROVED LHITES
Note: THIS IS A REINSPECTION Inspection Resulted at 11/16/2010 12:40:04 PM SYSTEM IS LIVE AND WILL REMAIN UNDER PRESSURE. NOTED 2 PAINTED HEADS AT RED LOBSTER DINING THAT WILL NEED TO BE REPLACED.
FIRE SPRINKLER 1ST ROUGH 11/09/2010 CANCELLED BY APPLICANT LHITES
Note: THIS IS A REINSPECTION requested by Roberto
FIRE SPRINKLER HYDROSTATIC TEST 11/09/2010 CANCELLED BY APPLICANT LHITES
Note: THIS IS A REINSPECTION requested by robert
FIRE SPRINKLER 1ST ROUGH 11/05/2010 Disapproved -FEE REQUIRED LHITES
Note: Inspection Resulted at 11/5/2010 12:30:10 PM ENTRY OF RED LOBSTER UNABLE TO INSPECT PIPE ABOVE CEILING, SOME LOOSE HANGERS THROUGHOUT BUILDING. 2 AREAS WHERE BRANCH AREM IS BEING SUPPORTED BY ANOTHER. CONTRACTOR NOT ON SITE....INCOMPLETE INSPECTION
FIRE SPRINKLER HYDROSTATIC TEST 11/05/2010 Disapproved -FEE REQUIRED LHITES
Note: Inspection Resulted at 11/5/2010 12:30:10 PM CONTRACTOR NOT ON SITE. SYSTEM HAS LEAK IN NW CORNER OF KITCHEN

Review History

Department Status Date In Date Out
FD1 COMPLETE 01/19/2011 01/19/2011
Note: Released By: LHITES REVISED AS BUILT SPRINKLER DRAWINGS AS REQUESTED PER LARRY HITES
FI1 COMPLETE 10/12/2010 10/12/2010
Note: Released By: LHITES Per Jeff Pattee.
FI1 HOLD 10/06/2010 10/07/2010
Note: Held By: JPATTEE Sheet FP, Why are only upright sprinkler heads indicated in the office and mechanical rooms? Do these areas have ceilings ?

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION FEE ¤40.00 11/08/2010
REINSPECTION FEE ¤40.00 11/08/2010
ADMIN COMMERCIAL ¤60.00 10/12/2010
BUILDING DISCOUNT 100% (¤54.00) 10/12/2010
FIRE PLANS REVIEW ¤25.00 10/12/2010
Fees Total Due: ¤0.00 Total Paid: ¤111.00