I want to search for...

Permit #2010100262

Permit Details

Status: FINAL

Parcel Id: 07-11-31-5112-00000-0050
Block: 00000
Subdivision: 1164 - PINE LAKES INDUSTRIAL PARK
Job Phone: (386) 767-5895
Location Address: 11 COMMERCE BLVD
Type: EL - ELECTRICAL
Issue Date: 10/13/2010
NOC: RECORDED
Applicant name: BRADLEY S GILES
Owner: PCD ACQUISITION LLC

Address

11 COMMERCE BLVD

PALM COAST, FL 32137

Lot: 0050
Contracted Stated Job Value: ¤50,000.00
Job Description: BUILD 400 AMP SERVICE & WIRE NEW UPS SYSTEM
Type: CN

Contractor

GILES ELECTRIC COMPANY
Status Location Address State License Number Phone Fax
ACTIVE

PO BOX 214176

S. DAYTONA, FL 32119

EC0001538 (Exp: 08/31/2026) (386) 767-5895 (386)767-6260

Inspection History

Type Request Date Result Inspector
ELECTRICAL FINAL 08/31/2011 FINAL APPROVED LHITES
Note: THIS IS A REINSPECTION
COMMERCIAL POWER INSPECTION 03/16/2011 APPROVED RMARVEL
ELECTRICAL FINAL 03/16/2011 Disapproved -FEE REQUIRED RMARVEL
Note: Inspection Resulted at 3/16/2011 10:37:01 AM NEED CITY APPROVED PLANS ON SITE FOR INSPECTION. CLEAN PAINT FROM UNDER GROUND LUG IN J BOX. FINISHING TAPPING OUT LUG FOR C PHASE IN MAIN DISCONNECT.TIGHTEN GROUNDS IN ATS CONTROL PANEL. ADD COMMERCIAL POWER INSPECTION TO PERMIT. NEED TO OPEN END OF GROUND RODS TO SEE PROPER CONNECTION.
MONOLITHIC SLAB INSPECTION/SLAB 11/24/2010 APPROVED - AS NOTED CMINI
Note: Inspection Resulted at 11/24/2010 2:59:56 PM APPROVED PER REVISION
UNDERGROUND ELECTRICAL 11/17/2010 APPROVED CMINI

Review History

Department Status Date In Date Out
ELEC COMPLETE 03/16/2011 03/16/2011
Note: Released By: LWOODROME Revision approved no fee
ELEC HOLD 12/15/2010 12/15/2010
Note: Held By: LHITES revision- increase the service size to 600 amp 1. Please provide manufacturers specifications for generator and transfer switch
BLD COMPLETE 11/18/2010 11/18/2010
Note: Released By: JMCGOWEN generator slab detail
BLD COMPLETE 10/11/2010 10/11/2010
Note: Released By: JMCGOWEN

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION FEE ¤40.00 08/30/2011
REVISION ¤40.00 03/15/2011
SURCHARGE FS 533.721 ¤2.63 10/13/2010
SURCHARGE - FS 468.631 ¤2.63 10/13/2010
ADMIN COMMERCIAL ¤60.00 10/13/2010
BUILDING DISCOUNT 100% (¤157.50) 10/13/2010
ELECTRIC FEE ¤90.00 10/13/2010
PLAN REVIEW 25 ¤25.00 10/13/2010
Fees Total Due: ¤0.00 Total Paid: ¤102.76