I want to search for...
Permit #2010100262
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-5112-00000-0050 |
| Block: 00000 |
| Subdivision: 1164 - PINE LAKES INDUSTRIAL PARK |
| Job Phone: (386) 767-5895 |
| Location Address: 11 COMMERCE BLVD |
| Type: EL - ELECTRICAL |
| Issue Date: 10/13/2010 |
| NOC: RECORDED |
| Applicant name: BRADLEY S GILES |
| Owner: PCD ACQUISITION LLC |
|
Address 11 COMMERCE BLVD PALM COAST, FL 32137 |
| Lot: 0050 |
| Contracted Stated Job Value: ¤50,000.00 |
| Job Description: BUILD 400 AMP SERVICE & WIRE NEW UPS SYSTEM |
| Type: CN |
Contractor
GILES ELECTRIC COMPANY
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
PO BOX 214176 S. DAYTONA, FL 32119 |
EC0001538 (Exp: 08/31/2026) | (386) 767-5895 | (386)767-6260 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRICAL FINAL | 08/31/2011 | FINAL APPROVED | LHITES |
| Note: THIS IS A REINSPECTION | |||
| COMMERCIAL POWER INSPECTION | 03/16/2011 | APPROVED | RMARVEL |
| ELECTRICAL FINAL | 03/16/2011 | Disapproved -FEE REQUIRED | RMARVEL |
| Note: Inspection Resulted at 3/16/2011 10:37:01 AM NEED CITY APPROVED PLANS ON SITE FOR INSPECTION. CLEAN PAINT FROM UNDER GROUND LUG IN J BOX. FINISHING TAPPING OUT LUG FOR C PHASE IN MAIN DISCONNECT.TIGHTEN GROUNDS IN ATS CONTROL PANEL. ADD COMMERCIAL POWER INSPECTION TO PERMIT. NEED TO OPEN END OF GROUND RODS TO SEE PROPER CONNECTION. | |||
| MONOLITHIC SLAB INSPECTION/SLAB | 11/24/2010 | APPROVED - AS NOTED | CMINI |
| Note: Inspection Resulted at 11/24/2010 2:59:56 PM APPROVED PER REVISION | |||
| UNDERGROUND ELECTRICAL | 11/17/2010 | APPROVED | CMINI |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 03/16/2011 | 03/16/2011 |
| Note: Released By: LWOODROME Revision approved no fee | |||
| ELEC | HOLD | 12/15/2010 | 12/15/2010 |
| Note: Held By: LHITES revision- increase the service size to 600 amp 1. Please provide manufacturers specifications for generator and transfer switch | |||
| BLD | COMPLETE | 11/18/2010 | 11/18/2010 |
| Note: Released By: JMCGOWEN generator slab detail | |||
| BLD | COMPLETE | 10/11/2010 | 10/11/2010 |
| Note: Released By: JMCGOWEN |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 08/30/2011 |
| REVISION | ¤40.00 | 03/15/2011 |
| SURCHARGE FS 533.721 | ¤2.63 | 10/13/2010 |
| SURCHARGE - FS 468.631 | ¤2.63 | 10/13/2010 |
| ADMIN COMMERCIAL | ¤60.00 | 10/13/2010 |
| BUILDING DISCOUNT 100% | (¤157.50) | 10/13/2010 |
| ELECTRIC FEE | ¤90.00 | 10/13/2010 |
| PLAN REVIEW 25 | ¤25.00 | 10/13/2010 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤102.76 |