Permit #2011050416
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7009-00210-0220 |
| CONDITIONED SPACE: 418 sqft |
| OPENED PORCH (WITH ROOF) : 54 sqft |
| Total Square Footage: 472 sqft |
| Block: 21 |
| Subdivision: 2208 - SECTION 9-FLORIDA PARK |
| Job Phone: 386-586-7093 |
| Location Address: 60 FALLEN OAK LN |
| Type: BA - BUILDING ADDITION |
| Issue Date: 06/16/2011 |
| NOC: RECORDED |
| Applicant name: ERIC GLENN SAMUELSON |
| Owner: GREEN CYNTHIA & HOWELL G H&W & JOEL O GREEN (ASM) |
|
Address 60 FALLEN OAK LANE PALM COAST, FL 32137 |
| Lot: 22 |
| Contracted Stated Job Value: ¤38,000.00 |
| Job Description: NEW ROOM ADDITION W/BATH & CONSTRUCT NEW COVERED ENTRANCE ADDITION |
| Type: CN |
Contractor
VIKING CONTRACTORS
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
597 JOHN ANDERSON HIGHWAY PALM COAST, FL 32164 |
CBC1257381 (Exp: 08/31/2014) | 386-586-7093 | 386-586-6146 |
Sub Contractors
JOHN EDWARD GAMBONE
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
55 BARRISTER LN PALM COAST, FL 32137 |
ER13013466 (Exp: 08/31/2014) | 386-586-9144 | (386)246-6305 |
DANIEL P HUCKS
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
400 N. U.S. 1 Ormond Beach, FL 32174 |
CAC029376 (Exp: 08/31/2024) | 386-672-8494 | 386-673-7856 |
DAVID L MILLER
| Status | Location Address | State License Number | Phone |
| CANCEL |
170 OLD MOODY BLVD BUNNELL, FL 32110 |
CFC1425948 (Exp: 08/31/2022) | (386) 439-2169 |
KENNETH MARTIN REED
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
83 LANCELOT DRIVE BUNNELL , FL 32110 |
CCC1328712 (Exp: 08/31/2026) | 386-446-3100 | 386-445-6074 |
Inspection History
| Type | Request Date | Result | Inspector |
| U -UTILITY RESIDENTIAL FINAL | 01/11/2013 | FINAL APPROVED | DSPENCER |
| BLD - BUILDING FINAL | 01/09/2013 | APPROVED | DROCKWELL |
| STORMWATER FINAL | 11/30/2012 | APPROVED | DROCKWELL |
| Note: THIS IS A REINSPECTION | |||
| ROW DAMAGE | 11/30/2012 | APPROVED | GLALIMA |
| Note: THIS IS A REINSPECTION | |||
| FOUND SURVEY APPROVED (OFFICE) | 10/17/2012 | APPROVED | JMCGOWEN |
| STORMWATER FINAL | 10/04/2012 | Disapproved -FEE REQUIRED | DROCKWELL |
| Note: Inspection Resulted at 10/4/2012 2:50:52 PM COVER ALL LOOSE SOILS WITH SOD TO SWALE.CURRENTLY SOIL IS COVERING DRIVWAY AND ENCROACHING INTO SWALE | |||
| ROW DAMAGE | 10/04/2012 | Disapproved -FEE REQUIRED | GLALIMA |
| Note: PICTURES . NEED TO HAVE ALL EROSION UNDER CONTROL . SWEEP ALL SAND AND FILL OFF DRIVEWAY . REPAIR ALL RUTS IN SWALE TO RIGHT ON VACANT LOT . ADD SOD IF NEEDED AT SIDE OF DRIVEWAY TO STOP EROSION . WHEN PLACING SOD IT MUST BE AT SAME ELEVATION AS OTHER. CALL GARY IF NEEDED 986 - 4767 | |||
| PROJECT STATUS (OFFICE USE) | 03/30/2012 | Disapproved - NO FEE | DROCKWELL |
| Note: Inspection Resulted at 3/30/2012 12:36:45 PM WORK APPEARS COMPLETE FROM EXTERIOR..... | |||
| PLUMBING 1ST ROUGH UNDERGROUND | 10/20/2011 | APPROVED | DROCKWELL |
| INSULATION | 09/28/2011 | APPROVED | DROCKWELL |
| ALL ROUGH | 09/20/2011 | APPROVED | DROCKWELL |
| Note: THIS IS A REINSPECTION | |||
| LATH/BRICK/ WATER BARRIER | 09/19/2011 | APPROVED | CMINI |
| ALL ROUGH | 09/19/2011 | CANCELLED BY APPLICANT | AIRS WEB |
| Note: THIS IS A REINSPECTION | |||
| ALL ROUGH | 09/15/2011 | Disapproved -FEE REQUIRED | DROCKWELL |
| Note: Inspection Resulted at 9/15/2011 12:21:50 PM FIREBLOCK BATH WALL AT EXISTING HOUSE/WIRE EXHAUST FAN/SUPPORT EXHAUSTDUCT AT MID-POINT W/STRAP/NEED WATER TEST ON SANITARY LINES/PROVIDE APPROVE A/C PLAN SHOWING SUPPLY AND RETURN LINES | |||
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 08/17/2011 | APPROVED | DROCKWELL |
| Note: THIS IS A REINSPECTION | |||
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 08/11/2011 | Disapproved -FEE REQUIRED | CMINI |
| Note: THIS IS A REINSPECTION REQUESTED BY CONTRACTOR Inspection Resulted at 8/11/2011 3:08:27 PM NEED TO COMPLETE GABLE END BLOCKING PER PLAN.....CANNOT NAIL STRAPS INTO OTHER STRAPS PER SIMPSON...ANCHORS INTO WALL PLATE GOING INTO EXISTING HOUSE NOT TO PLAN...AT SAME PLATE NEED TO CORRECT STRAP THAT HAS SLACK IN IT..NEED TO COMPLETE FURRING OUT ON INTERIOR WALL AS PER PLAN. | |||
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 08/04/2011 | Disapproved -FEE REQUIRED | DROCKWELL |
| Note: Inspection Resulted at 8/4/2011 12:28:40 PM ENTRY GABLE END NOT BLOCKED TO PLAN/BEAM ANCHORING INTO EXISTING WALL HAS NO DETAIL/INSTALL TRUSS CLIPS PROPERLY AT RAFTER TIE IN TO SLEEPER/FURNISH DETAIL FOR ANCHORING NEW TRUSSES TO EXISTING EXTERIOR WALL REAR ADDITION/VOLUME CEILING IN REAR ADDITION ENDS AT A FRAME WALL THAT IS NOT BALLON FRAMED-SUGGEST ARCHITECT VISIT SITE TO DETERMINE DEGREE OF PROBLEM/COMPLETE NAILING AT EXTERIOR SHEATHING/ROOF METALS INSTALLED BY THIS INSPECTION | |||
| MONOLITHIC SLAB | 07/06/2011 | APPROVED | DROCKWELL |
| Note: THIS IS A REINSPECTION | |||
| MONOLITHIC SLAB | 07/05/2011 | Disapproved -FEE REQUIRED | DROCKWELL |
| Note: Inspection Resulted at 7/5/2011 12:41:48 PM NO FOOTING DETAIL ON SITE/DRILLED DOWELS ARE TO BE 2FT ON CENTER PER PLAN |
Review History
| Department | Status | Date In | Date Out |
| SW1 | COMPLETE | 10/17/2012 | 10/17/2012 |
| Note: Released By: JMCGOWEN FOUNDATION SURVEY | |||
| ZON | COMPLETE | 10/17/2012 | 10/17/2012 |
| Note: Released By: JMCGOWEN FOUNDATION SURVEY | |||
| BLD | COMPLETE | 08/16/2011 | 08/16/2011 |
| Note: Released By: JMCGOWEN frame to block connection | |||
| BLD | COMPLETE | 08/09/2011 | 08/10/2011 |
| Note: released by J. Hindman | |||
| MECH | COMPLETE | 06/14/2011 | 06/14/2011 |
| ZON | COMPLETE | 06/06/2011 | 06/07/2011 |
| Note: Released by KDavis | |||
| PLUM | COMPLETE | 06/06/2011 | 06/06/2011 |
| BLD | COMPLETE | 06/06/2011 | 06/06/2011 |
| Note: released by J. Hindman | |||
| MECH | HOLD | 06/06/2011 | 06/06/2011 |
| Note: Provide total square foot of house and total BTU of existing A/C unit and give us a determination if existing unit can handle the added load. | |||
| ZON | HOLD | 05/18/2011 | 05/19/2011 |
| Note: The site plan submitted does not match the site plan on file for the house. The site plan on file has a 10x22 concrete porch situated on the rear middle portion of the house; but the site plan submitted has a larger porch that extends further out then 10'. It also appears that a concrete slab was poured on the rear right side of the house with no permit on file. This permit application must include hatched out areas not only for the new extension but also square footages for the extension to the previously approved 10x22 slab and the slab located on the rear right side of house. | |||
| PLUM | HOLD | 05/18/2011 | 05/19/2011 |
| Note: Held by Freodica 1. Provide sanitary riser diagram and DWV material specification. | |||
| SW1 | COMPLETE | 05/18/2011 | 05/19/2011 |
| Note: Released by JJoseph | |||
| ELEC | COMPLETE | 05/18/2011 | 05/19/2011 |
| Note: released by J. Hindman | |||
| MECH | HOLD | 05/18/2011 | 05/19/2011 |
| Note: Held by Freodica 1. Provide hvac duct system layout for the additional rooms. 2. Energy calculations shows only for the additional rooms but it does not show the capacity of the unit to be used. If the existing unit would be used, submit energy calculation based on the whole house to determine if the existing unit capacity can handle the existing and the additional load. | |||
| BLD | HOLD | 05/18/2011 | 05/19/2011 |
| Note: Held by J. Hindman 1. provide anchorage detail for shutters at egress window on CMU wall. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 10/17/2012 |
| REINSPECTION FEE | ¤40.00 | 10/17/2012 |
| EXTENSION | ¤40.00 | 10/04/2012 |
| REINSPECTION FEE | ¤40.00 | 04/12/2012 |
| REINSPECTION FEE | ¤40.00 | 04/12/2012 |
| REINSPECTION FEE | ¤40.00 | 04/12/2012 |
| REINSPECTION FEE | ¤40.00 | 04/12/2012 |
| REVISION | ¤40.00 | 04/12/2012 |
| REVISION | ¤40.00 | 04/12/2012 |
| EXTENSION | ¤40.00 | 04/12/2012 |
| BUILDING DISCOUNT 100% | (¤324.90) | 06/16/2011 |
| ELECTRIC FEE | ¤174.00 | 06/16/2011 |
| SITE PLAN 20 | ¤20.00 | 06/16/2011 |
| SURCHARGE FS 533.721 | ¤2.00 | 06/16/2011 |
| SURCHARGE - FS 468.631 | ¤2.00 | 06/16/2011 |
| REMODEL/ADDITION/ACCES INSPECT | ¤80.00 | 06/16/2011 |
| MECHANICAL FEE | ¤174.00 | 06/16/2011 |
| PERMIT FEE | ¤200.00 | 06/16/2011 |
| PLAN CHECK FEE | ¤80.00 | 06/16/2011 |
| PLUMBING FEE | ¤174.00 | 06/16/2011 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤981.10 |