I want to search for...
Permit #2012030357
Permit Details
Status: FINAL
| Parcel Id: 27-10-30-0000-01010-0010 |
| Block: 01010 |
| Subdivision: - |
| Job Phone: (386)547-9834 |
| Location Address: 6595 BELLE TERRE PKWY |
| Type: BC - BUILDING COMMERCIAL |
| Issue Date: 04/19/2012 |
| NOC: RECORDED |
| Applicant name: RAMON MICHAEL GIACCONE |
| Owner: PALM COAST UNITED METHODIST CHURCH INC |
|
Address 5200 BELLE TERRE PKWY PALM COAST, FL 32137 |
| Lot: 0010 |
| Contracted Stated Job Value: ¤100,000.00 |
| Job Description: PICNIIC PAVILION |
| Type: CN |
Contractor
VERITAS CONSTRUCTION INC.
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
13 SMITH TRAIL PALM COAST, FL 32164 |
CBC1251714 (Exp: 08/31/2026) | (386)547-9834 | (386)437-2016 |
Sub Contractors
WILLIAM FRANK DUDLEY JR.
| Status | Location Address | State License Number | Phone |
| ACTIVE |
P.O. BOX 978 Bunnell, FL 32110 |
EC0003177 (Exp: 08/31/2026) | (386)437-3068 |
HEATH EDWARD SANFORD
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
1351 HAZELNUT ST BUNNELL, FL 32110 |
CFC1427527 (Exp: 08/31/2026) | 386-445-2532 | 386-445-5575 |
STEPHEN M RENDE
| Status | Location Address | State License Number | Phone |
| CANCEL |
22 ALAMANDA DRIVE ORMOND, FL 32176 |
CCC058058 (Exp: 08/31/2020) | 386-439-7156 |
Inspection History
| Type | Request Date | Result | Inspector |
| PLUMBING FINAL | 02/11/2013 | APPROVED | CMINI |
| ELECTRIC FINAL | 02/11/2013 | FINAL APPROVED | CMINI |
| FIRE FINAL | 09/20/2012 | APPROVED | JHINDMAN |
| Note: THIS IS A REINSPECTION | |||
| BUILDING FINAL | 09/18/2012 | APPROVED - AS NOTED | CMINI |
| Note: Inspection Resulted at 9/18/2012 2:55:02 PM NEED TO CALL IN ELECTRIC FINAL AND PLUMBING FINAL | |||
| FIRE FINAL | 09/18/2012 | Disapproved -FEE REQUIRED | JHINDMAN |
| Note: Inspection Resulted at 9/18/2012 11:27:15 AM 1. PROVIDE 10 LB ABC FIRE EXTINGUISHER PER PLANS AND NFPA10. | |||
| ELECTRIC - EARLY POWER | 08/30/2012 | APPROVED - AS NOTED | CMINI |
| Note: Inspection Resulted at 8/30/2012 1:49:58 PM CALLED FPL AT 10:45 TO RELEASE POWER,SPOKE WITH SUSAN | |||
| LATH/BRICK/WATER BARRIER | 07/27/2012 | APPROVED | CMINI |
| Note: Inspection Requested at 7/26/2012 9:37:54 PM LATH AND BRICK ARE N/A | |||
| FIREWALL | 07/26/2012 | APPROVED | CMINI |
| Note: Inspection Requested at 7/25/2012 4:01:00 PM FIREWALL IS N/A | |||
| ELECTRIC 2ND ROUGH | 07/26/2012 | APPROVED - AS NOTED | CMINI |
| Note: THIS IS A REINSPECTION Inspection Resulted at 7/26/2012 2:57:17 PM NEED REVISION FOR ANY ADDED CIRCUITS TO PANEL AND PANEL SCHEDULE CHANGE TO PLAN FOR FINAL | |||
| ELECTRIC 1ST ROUGH | 07/26/2012 | APPROVED - AS NOTED | CMINI |
| Note: Inspection Requested at 7/25/2012 3:57:14 PM INSPECTION FOR SITE LIGHTING PER DISCUSSION W/CHAR Inspection Resulted at 7/26/2012 2:57:16 PM SITE LIGHTING UNDERGROUND | |||
| MONOLITHIC SLAB | 07/26/2012 | APPROVED | CMINI |
| Note: THIS IS A REINSPECTION Inspection Requested at 7/25/2012 3:59:09 PM INSPECT FLOOR DRAIN FLOOR CUT PER DISCUSSION W/CHA | |||
| PLUMBING 2ND ROUGH | 07/26/2012 | APPROVED | CMINI |
| Note: THIS IS A REINSPECTION | |||
| PLUMBING 2ND ROUGH | 07/25/2012 | Disapproved -FEE REQUIRED | CMINI |
| Note: Inspection Resulted at 7/25/2012 1:24:17 PM NEED TO HAVE TEST GUAGE FOR WATER PIPE AND NEED 5`` HEAD PRESSURE ON DWV PER FPC 312 | |||
| ELECTRIC 2ND ROUGH | 07/25/2012 | CANCELLED BY APPLICANT | CMINI |
| ABOVE CEILING | 07/25/2012 | APPROVED - AS NOTED | RMARVEL |
| Note: Inspection Resulted at 7/25/2012 10:37:18 AM NOT APPLICABLE. | |||
| FRAMING | 07/24/2012 | APPROVED - AS NOTED | CMINI |
| Note: THIS IS A REINSPECTION Inspection Resulted at 7/24/2012 2:48:41 PM INSTALL TAIL ON TRUSS THAT IS MISSING | |||
| ROOF SHEATHING / BRACE / TIE DOWN | 07/24/2012 | APPROVED | CMINI |
| Note: THIS IS A REINSPECTION | |||
| FRAMING | 07/20/2012 | Disapproved - NO FEE | CMINI |
| Note: Inspection Resulted at 7/20/2012 2:42:54 PM MISSING ANCHOR BOLTS AT 24" O.C. AT GABLE END SILL PLATE PER PLAN...AT VALLEY FRAMING WHEN USING 2X8 RAFTERS PLAN CALLS FOR 2X10 RIDGE..MISSING BUCKET FOR RIDGE ON FRONT SIDEL30S USED INSTEAD..MISSING COLLAR TIES PER PLAN DETAIL..MISSING TAIL ON TRUSS RO2 LEFT OF COLUMN..PLAN SHOWING X-BRACING GOING OUT TO 12`` | |||
| ROOF SHEATHING / BRACE / TIE DOWN | 07/20/2012 | Disapproved -FEE REQUIRED | CMINI |
| Note: Inspection Resulted at 7/20/2012 2:42:53 PM MISSING ANCHOR BOLTS AT 24" O.C. AT GABLE END SILL PLATE PER PLAN...AT VALLEY FRAMING WHEN USING 2X8 RAFTERS PLAN CALLS FOR 2X10 RIDGE..MISSING BUCKET FOR RIDGE ON FRONT SIDEL30S USED INSTEAD..MISSING COLLAR TIES PER PLAN DETAIL..MISSING TAIL ON TRUSS RO2 LEFT OF COLUMN..PLAN SHOWING X-BRACING GOING OUT TO 12`` | |||
| LINTEL | 06/19/2012 | APPROVED | CMINI |
| FOUNDATION SURVEY - OFFICE USE ONLY | 06/14/2012 | APPROVED | JMCGOWEN |
| MONOLITHIC SLAB | 05/25/2012 | APPROVED | CMINI |
| Note: THIS IS A REINSPECTION | |||
| FOOTER | 05/25/2012 | APPROVED | CMINI |
| Note: THIS IS A REINSPECTION | |||
| FOOTER | 05/24/2012 | Disapproved - NO FEE | CMINI |
| Note: Inspection Resulted at 5/24/2012 3:46:50 PM NEED TO HAVE COMPACTION RESULTS THAT SHOW 95%OR BETTER PER PLAN DETAILS.NEED TO HAVE TERMITE TREATMENT CERT. PER PLAN DETAIL.NEED TO CREATE AN RELIEVING ARCH IN ORDER TO MAINTAIN 3" CLEARANCE OVER OR UNDER PIPES FROM REINFORCING STEEL .PER NOTE B.5 IN GENERAL NOTES | |||
| MONOLITHIC SLAB | 05/24/2012 | Disapproved -FEE REQUIRED | CMINI |
| Note: Inspection Resulted at 5/24/2012 3:46:49 PM NEED TO HAVE COMPACTION RESULTS THAT SHOW 95%OR BETTER PER PLAN DETAILS.NEED TO HAVE TERMITE TREATMENT CERT. PER PLAN DETAIL.NEED TO CREATE AN RELIEVING ARCH IN ORDER TO MAINTAIN 3" CLEARANCE OVER OR UNDER PIPES FROM REINFORCING STEEL .PER NOTE B.5 IN GENERAL NOTES. | |||
| PLUMBING 1ST ROUGH | 05/21/2012 | APPROVED - AS NOTED | CMINI |
| Note: THIS IS A REINSPECTION Inspection Resulted at 5/21/2012 1:28:43 PM CORRECTED WORK TO MATCH PLANS | |||
| PLUMBING 1ST ROUGH | 05/14/2012 | Disapproved -FEE REQUIRED | CMINI |
| Note: THIS IS A REINSPECTION Inspection Resulted at 5/14/2012 3:46:53 PM PLUMBER MET ME ON SITE TO GO OVER WHAT WAS NEEDED TO APPROVE INSPECTION.REVISION SHOWING CHANGES TO THE PLAN NEEDED | |||
| PLUMBING 1ST ROUGH | 05/10/2012 | Disapproved -FEE REQUIRED | CMINI |
| Note: Inspection Resulted at 5/10/2012 3:39:26 PM NEED TO REVISE PLAN SHOWING ACTUAL SIZES ON JOB.PLAN SHOWING 4"LINE INSTALLED IS 3". ALSO VTR THAT IS CHANGED TO 2" FROM 3" AND WATER PIPE THAT IS SHOWING 1-1/4" CHANGED TO 3/4" | |||
| ELECTRIC 1ST ROUGH | 05/10/2012 | APPROVED - AS NOTED | CMINI |
| Note: requested by contractor Inspection Resulted at 5/10/2012 3:39:26 PM UNDER SLAB ONLY |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 08/08/2012 | 08/08/2012 |
| ENGIN1 | COMPLETE | 06/12/2012 | 06/13/2012 |
| ZON | COMPLETE | 06/11/2012 | 06/11/2012 |
| Note: Released By: JGONZALEZ foundation survey per sara lockhart review | |||
| PLUM | COMPLETE | 05/21/2012 | 05/21/2012 |
| Note: Plumbing revision previously submitted by plumbing contractor was cancelled by same. | |||
| PLUM | HOLD | 05/15/2012 | 05/15/2012 |
| Note: Revisions shall be signed and sealed by engineer of record who originally did the design. | |||
| PLUM | COMPLETE | 04/13/2012 | 04/16/2012 |
| BLD | COMPLETE | 04/13/2012 | 04/16/2012 |
| ELEC | COMPLETE | 04/13/2012 | 04/16/2012 |
| BLD | HOLD | 03/13/2012 | 03/13/2012 |
| Note: 1. Provide engineered wood trusses as per plan. 2. Provide Florida Product Approval for fiberglass roofing material. | |||
| ELEC | HOLD | 03/13/2012 | 03/13/2012 |
| Note: electric plan is a copyrighted material and shall be signed by the engineer or a licensed electric contractor can sign the plan and his license number is indicated on it provided all information on plan title block is removed. Provide electric load calculation | |||
| ENGIN1 | COMPLETE | 03/13/2012 | 03/14/2012 |
| Note: No review required | |||
| FI1 | COMPLETE | 03/13/2012 | 03/15/2012 |
| PLUM | HOLD | 03/13/2012 | 03/13/2012 |
| Note: Plumbing plan is a copyrighted material and shall be signed by the engineer or a licensed plumbing contractor can sign the plan and his license number is indicated on it provided all information on plan title block is removed. | |||
| UD1 | COMPLETE | 03/13/2012 | 03/14/2012 |
| ZON | COMPLETE | 03/13/2012 | 03/15/2012 |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 09/23/2012 |
| REINSPECTION FEE | ¤40.00 | 09/23/2012 |
| REVISION | ¤40.00 | 09/23/2012 |
| REINSPECTION FEE | ¤40.00 | 08/07/2012 |
| REINSPECTION FEE | ¤40.00 | 08/07/2012 |
| REINSPECTION FEE | ¤40.00 | 08/07/2012 |
| REINSPECTION FEE | ¤40.00 | 08/07/2012 |
| SITE PLAN 20 | ¤20.00 | 04/19/2012 |
| SURCHARGE FS 533.721 | ¤2.00 | 04/19/2012 |
| SURCHARGE - FS 468.631 | ¤2.00 | 04/19/2012 |
| ADMIN COMMERCIAL | ¤60.00 | 04/19/2012 |
| BUILDING DISCOUNT 100% | (¤868.50) | 04/19/2012 |
| ELECTRIC FEE | ¤120.00 | 04/19/2012 |
| IMPACT FEE FIRE NONRESIDENTIAL | ¤448.59 | 04/19/2012 |
| FIRE PLANS REVIEW | ¤25.00 | 04/19/2012 |
| IMPACT FEE TRANSPORTATION | ¤4,091.08 | 04/19/2012 |
| PERMIT FEE | ¤550.00 | 04/19/2012 |
| PLAN CHECK FEE | ¤115.00 | 04/19/2012 |
| PLUMBING FEE | ¤120.00 | 04/19/2012 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤4,965.17 |