Permit #2012090656

Permit Details

Status: COED

Parcel Id: 07-11-31-7025-000C0-013B
Block: 000C0
Subdivision: 1228 - SOUTHWEST QUADRANT
Job Phone: 386-338-7785
Location Address: 10 CYPRESS POINT PKWY
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 10/30/2012
NOC: RECORDED
Applicant name: THOMAS M SCAGLIONE
Owner: ANTOMAR OF PALM COAST LLC

Address

13 UTILITY DRIVE

PALM COAST, FL 32137

Lot: 013B
Contracted Stated Job Value: ¤12,000.00
Job Description: UNIT 104 - INTERIOR RENOVATIONS FOR SALON "THE BEAUTY FACTOR"
Type: CN

Contractor

T-CON GROUP, INC.
Status Location Address State License Number Phone
CANCEL

3246 NORTH POWERLINE ROAD

POMPANO BEACH, FL 33069

CBC1251999 (Exp: 08/31/2020) 954-825-8369

Sub Contractors

RICHARD R EDWARDS
Status Location Address State License Number Phone
CANCEL

P. O. Box 1637

Bunnell, FL 32110

ER0011603 (Exp: 08/31/2022) (386) 437-1537
MICHAEL ALLEN PHILLIPS
Status Location Address State License Number Phone Fax
CANCEL

PO BOX 478

BUNNELL, FL 32110

CAC1814966 (Exp: 08/31/2014) 386-262-6034 866-369-7390
JOHN CHARLES GRAY
Status Location Address State License Number Phone Fax
ACTIVE

2707 ANNETTE STREET

FLAGLER BEACH, FL 32136

CFC1425975 (Exp: 08/31/2026) (386)793-3690 (386)439-7585

Inspection History

Type Request Date Result Inspector
BUILDING FINAL 11/21/2012 FINAL APPROVED RMARVEL
FIRE FINAL 11/21/2012 APPROVED JHINDMAN
U - UTILITY COMMERCIAL FINAL 11/21/2012 APPROVED DSPENCER
PLUMBING 2ND ROUGH 11/20/2012 APPROVED RMARVEL
PLUMBING FINAL 11/20/2012 APPROVED RMARVEL
HVAC FINAL 11/20/2012 APPROVED RMARVEL
ELECTRIC FINAL 11/20/2012 APPROVED RMARVEL
ABOVE CEILING 11/20/2012 APPROVED RMARVEL
PLUMBING 1ST ROUGH 11/07/2012 APPROVED RMARVEL
FRAMING 11/07/2012 APPROVED RMARVEL
ELECTRIC 2ND ROUGH 11/07/2012 APPROVED RMARVEL

Review History

Department Status Date In Date Out
ELEC COMPLETE 10/29/2012 10/29/2012
MECH COMPLETE 10/29/2012 10/29/2012
PLUM COMPLETE 10/29/2012 10/29/2012
ELEC HOLD 10/26/2012 10/26/2012
Note: the electrical plan drawing will need to be signed and sealed FBC 107.1 plan submitted is missing detail and can not be reviewed
PLUM HOLD 10/26/2012 10/26/2012
Note: Previous comment need to be addressed - Provide size of existing pipe where laundry tub and washing machine are tied into as previously requested. The required size is important to determine if it complies with 2010 FBC P Sections 406.3 and Table 909.3.
MECH HOLD 10/26/2012 10/26/2012
Note: Previous comment 1 need to be addressed - 1. Provide the outdoor air duct, size, source entry location and the required outdoor air ventilation calculation per 2010 FBC M Section 403.2.
ELEC HOLD 10/22/2012 10/23/2012
Note: Electric hand drawn riser detail will need electrician’s name and license number, the electrical plan drawing will need to be signed and sealed FBC 107.1
PLUM HOLD 10/22/2012 10/23/2012
Note: Provide size of existing pipe where laundry tub and washing machine are tied into as previously requested. The required size is important to determine if it complies with 2010 FBC P Sections 406.3 and Table 909.3.
MECH HOLD 10/22/2012 10/23/2012
Note: Previous hold comments need to be addressed- 1. Provide the outdoor air duct, size, source entry location and the required outdoor air ventilation calculation per 2010 FBC M Section 403.2. 2. Provide exhaust fan specification per 2010 FBC Section 107.3.5. Note: Provide a note on plan that the space will not install a nail salon thereby removing the exhaust fan on plan. See previous comment 2.
BLD COMPLETE 10/22/2012 10/23/2012
FI1 COMPLETE 09/28/2012 09/28/2012
MECH HOLD 09/28/2012 09/28/2012
Note: 1. Provide the outdoor air duct, size, source entry location and the required outdoor air ventilation calculation per 2010 FBC M Section 403.2. 2. Provide exhaust fan specification per 2010 FBC Section 107.3.5.
PLUM HOLD 09/28/2012 09/28/2012
Note: 1. Provide the size of existing pipe where laundry tub and washing machine are tied into as shown on riser diagram per 2010 FBC 107.3.5. 2. Future wash sink is not shown on plan but shown on riser diagram. Coordinate and revise to comply with 2010 FBC 107.2.1.
UD1 COMPLETE 09/28/2012 10/01/2012
ZON COMPLETE 09/28/2012 10/04/2012
BLD HOLD 09/28/2012 09/28/2012
Note: Held By: JHINDMAN 1. provide a detail the new openings 2010FBC 107.2.1.
ELEC HOLD 09/28/2012 09/28/2012
Note: Provide electric load calculations, riser detail and panel schedule FBC 107.3.5

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADMIN COMMERCIAL ¤60.00 10/30/2012
BUILDING DISCOUNT 100% (¤415.44) 10/30/2012
ELECTRIC FEE ¤67.20 10/30/2012
FIRE PLANS REVIEW ¤25.00 10/30/2012
MECHANICAL FEE ¤67.20 10/30/2012
PERMIT FEE ¤100.00 10/30/2012
PLAN CHECK FEE ¤100.00 10/30/2012
PLUMBING FEE ¤67.20 10/30/2012
SITE PLAN 20 ¤20.00 10/30/2012
SURCHARGE FS 533.721 ¤2.00 10/30/2012
SURCHARGE - FS 468.631 ¤2.00 10/30/2012
Fees Total Due: ¤0.00 Total Paid: ¤95.16