I want to search for...
Permit #2012100463
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7001-0RPAB-0010 |
| COMMERCIAL SQUARE FOOTAGE: 479 sqft |
| Total Square Footage: 479 sqft |
| Block: 0RPAB |
| Subdivision: 2143 - SECTION 1-FLORIDA PARK |
| Job Phone: (386)763-4190 |
| Location Address: 264 PALM COAST PKWY NE |
| Type: CA - COMM ADDITION |
| Issue Date: 11/20/2012 |
| NOC: RECORDED |
| Applicant name: PAUL KEITH CULVER |
| Owner: HINMAN ROY H II |
|
Address 264 PALM COAST PKWY NE PALM COAST, FL 32137 |
| Lot: 0010 |
| Contracted Stated Job Value: ¤47,900.00 |
| Job Description: 479 SQ FT ADDITION "ISLAND DOCTORS" |
| Type: CN |
Contractor
PAUL CULVER CONSTRUCTION INC
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
1301 BEVILLE RD SUITE #6 DAYTONA BEACH, FL 32119 |
CGC059149 (Exp: 08/31/2026) | (386)763-4190 | (386)322-6724 |
Sub Contractors
MARK R JOHNSTON
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
815 N RIDGEWOOD AVE ORMOND BEACH, FL 32174 |
ER13014376 (Exp: 08/31/2016) | 386-615-8216 | 386-615-8216 |
KEVIN HENRY BEHRENS
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
1200 SOUTH NOVA ROAD DAYTONA BEACH, FL 32114 |
CAC054733 (Exp: 08/31/2026) | (386)761-7751 | (386) 258-0058 |
ISAAC WALTER JOHNSTON
| Status | Location Address | State License Number | Phone |
| ACTIVE |
887 BRENTWOOD DRIVE Daytona Beach, FL 32117 |
CFC023634 (Exp: 08/31/2026) | (386) 252-7047 |
JOSEPH MARTIN DELIA JR
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
200 PALMETTO PINES RD DAYTONA BEACH, FL 32114 |
CCC1326358 (Exp: 08/31/2026) | (386)673-6600 | (386)673-6600 |
Inspection History
| Type | Request Date | Result | Inspector |
| U - UTILITY COMMERCIAL FINAL | 06/13/2013 | FINAL APPROVED | DSPENCER |
| BUILDING FINAL | 02/08/2013 | APPROVED - AS NOTED | CMINI |
| Note: THIS IS A REINSPECTION Inspection Resulted at 2/8/2013 3:46:29 PM UTILTY STILL OUT | |||
| FIRE FINAL | 02/08/2013 | APPROVED | JHINDMAN |
| FINAL SURVEY (OFFICE USE ONLY) | 02/07/2013 | APPROVED | JHINDMAN |
| BUILDING FINAL | 02/05/2013 | Disapproved -FEE REQUIRED | CMINI |
| Note: Inspection Resulted at 2/5/2013 2:51:34 PM NEED TO HAVE FINAL SURVEY APPROVED FOR FINAL INSPECTION.FBC 105.7 | |||
| PLUMBING FINAL | 01/30/2013 | APPROVED | CMINI |
| HVAC FINAL | 01/29/2013 | APPROVED | CMINI |
| ELECTRIC FINAL | 01/29/2013 | APPROVED | CMINI |
| ABOVE CEILING | 01/24/2013 | APPROVED - AS NOTED | CMINI |
| Note: Inspection Resulted at 1/24/2013 2:51:39 PM CHECK FOR JB IN CELING TO BE GROUNDED ON ELECTRIC FINAL | |||
| HVAC ROUGH | 01/22/2013 | APPROVED | CMINI |
| Note: THIS IS A REINSPECTION | |||
| INSULATION | 01/16/2013 | APPROVED | CMINI |
| ALL ROUGH | 01/11/2013 | APPROVED - AS NOTED | CMINI |
| Note: PARTIAL FRAMING ONLY Inspection Resulted at 1/11/2013 2:15:40 PM INTERIOR FRAMING | |||
| FOUND SURVEY APPROVED (OFFICE) | 01/10/2013 | APPROVED | JMCGOWEN |
| HVAC ROUGH | 01/09/2013 | Disapproved -FEE REQUIRED | CMINI |
| Note: Inspection Resulted at 1/9/2013 3:32:38 PM RTU NOT STRAPPED DOWN PER PLAN FBC 107.3 | |||
| ELECTRIC 2ND ROUGH | 01/07/2013 | APPROVED | CMINI |
| PLUMBING 2ND ROUGH | 01/04/2013 | APPROVED | CMINI |
| LATH/BRICK/WATER BARRIER | 12/28/2012 | APPROVED | CMINI |
| EXTERIOR WALL SHEATHING / SHEARWALL | 12/26/2012 | APPROVED | CMINI |
| Note: THIS IS A REINSPECTION | |||
| EXTERIOR WALL SHEATHING / SHEARWALL | 12/21/2012 | PARTIALLY APPROVED | CMINI |
| Note: Inspection Resulted at 12/21/2012 2:14:17 PM NORTH WALL NAIL OFF ONLY | |||
| ROOF SHEATHING / BRACE / TIE DOWN | 12/21/2012 | APPROVED | CMINI |
| Note: THIS IS A REINSPECTION | |||
| ROOF SHEATHING / BRACE / TIE DOWN | 12/20/2012 | Disapproved -FEE REQUIRED | DROCKWELL |
| Note: Inspection Requested at 12/19/2012 10:09:36 PM AFTER 1PM INSPECTION IF POSSIBLE Inspection Resulted at 12/20/2012 1:58:08 PM NOT READY FOR INSPECTION....OK TO DRY-IN ROOF DECKING | |||
| FOOTER | 12/10/2012 | APPROVED - AS NOTED | DROCKWELL |
| Note: Inspection Resulted at 12/10/2012 3:03:00 PM THIS IS A MONO-SLAB POUR | |||
| PLUMBING 1ST ROUGH | 12/06/2012 | APPROVED | CMINI |
Review History
| Department | Status | Date In | Date Out |
| BLD | COMPLETE | 02/04/2013 | 02/05/2013 |
| DSD | COMPLETE | 02/04/2013 | 02/06/2013 |
| ENGIN1 | COMPLETE | 02/04/2013 | 02/05/2013 |
| SW1 | COMPLETE | 02/04/2013 | 02/05/2013 |
| UD1 | COMPLETE | 02/04/2013 | 02/05/2013 |
| ZON | COMPLETE | 02/04/2013 | 02/06/2013 |
| MECH | COMPLETE | 01/17/2013 | 01/17/2013 |
| Note: revision Changed A/C curb and attachment to roof deck | |||
| BLD | COMPLETE | 12/26/2012 | 12/26/2012 |
| Note: no changes | |||
| SW1 | COMPLETE | 12/26/2012 | 01/04/2013 |
| ZON | COMPLETE | 12/26/2012 | 12/27/2012 |
| ELEC | COMPLETE | 11/19/2012 | 11/19/2012 |
| ELEC | HOLD | 11/09/2012 | 11/09/2012 |
| Note: Provide electric load calculations NEC 220.16 provide existing load and service size NEC ARTICAL 220 | |||
| PLUM | COMPLETE | 11/09/2012 | 11/13/2012 |
| MECH | COMPLETE | 11/09/2012 | 11/13/2012 |
| BLD | COMPLETE | 11/09/2012 | 11/13/2012 |
| DSD | COMPLETE | 11/06/2012 | 11/08/2012 |
| ZON | COMPLETE | 11/06/2012 | 11/08/2012 |
| BLD | HOLD | 11/06/2012 | 11/06/2012 |
| Note: 1. Provide the structural design loads for the addition per the 2010 FBC 1603.1. This includes the wind speed, risk category and exposure of the structure. It also includes the soil bearing design values. | |||
| ELEC | HOLD | 10/19/2012 | 10/19/2012 |
| Note: Provide electric load calculations NEC 220.16 | |||
| MECH | HOLD | 10/19/2012 | 10/19/2012 |
| Note: 1. Provide energy calculations per 2010 FBC EC 503.2.1 | |||
| PLUM | HOLD | 10/19/2012 | 10/19/2012 |
| Note: 1. Provide plumbing riser diagrams (sanitary and domestic water) per 2010 FBC Section 107.3.5. 2. Provide fixtures and piping material specifications per 2010 Section 107.3.5. | |||
| BLD | HOLD | 10/19/2012 | 10/19/2012 |
| Note: 1. Provide the structural design loads for the addition per the 2010 FBC 1603.1 2. Provide for the protection of the wood that is in contact with the concrete or masonry per 2010 FBC 2304.11.2.4. 3. Provide a wall and roof sheating nailing detail per 2010 FBC 2304.6.1. 4. Provide Florida product approval and installation instructions for the exterior door per 2010 FBC 1715.5.2. | |||
| DSD | HOLD | 10/19/2012 | 10/19/2012 |
| Note: Applicant must submit for a Site Development permit before building permit can be approved. | |||
| ENGIN1 | COMPLETE | 10/19/2012 | 10/19/2012 |
| FI1 | COMPLETE | 10/19/2012 | 10/19/2012 |
| SW1 | COMPLETE | 10/19/2012 | 10/19/2012 |
| UD1 | COMPLETE | 10/19/2012 | 10/22/2012 |
| ZON | HOLD | 10/19/2012 | 10/19/2012 |
| Note: Applicant must submit for a Site Development permit before building permit can be approved. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 02/05/2013 |
| REVISION | ¤40.00 | 01/17/2013 |
| REINSPECTION FEE | ¤40.00 | 01/17/2013 |
| REINSPECTION FEE | ¤40.00 | 01/04/2013 |
| SITE PLAN 20 | ¤20.00 | 11/20/2012 |
| SURCHARGE FS 533.721 | ¤11.44 | 11/20/2012 |
| SURCHARGE - FS 468.631 | ¤11.44 | 11/20/2012 |
| ADMIN COMMERCIAL | ¤60.00 | 11/20/2012 |
| ELECTRIC FEE | ¤88.80 | 11/20/2012 |
| IMPACT FEE FIRE NONRESIDENTIAL | ¤124.20 | 11/20/2012 |
| FIRE PLANS REVIEW | ¤25.00 | 11/20/2012 |
| IMPACT FEE TRANSPORTATION | ¤3,051.83 | 11/20/2012 |
| MECHANICAL FEE | ¤88.80 | 11/20/2012 |
| PERMIT FEE | ¤336.00 | 11/20/2012 |
| PLAN CHECK FEE | ¤100.00 | 11/20/2012 |
| PLUMBING FEE | ¤88.80 | 11/20/2012 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤4,166.31 |