I want to search for...

Permit #2013040078

Permit Details

Status: COED

Parcel Id: 10-11-30-4937-00000-0180
Block: 00000
Subdivision: 2262 - PALM COAST INDUSTRIAL PARK
Job Phone: 386-238-1570
Location Address: 5 HARGROVE GRADE
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 05/01/2013
NOC: RECORDED
Applicant name: GARY LYNN ROBERTS
Owner: HANCOCK BANK

Address

1022 WEST 23RD STREET

PANAMA CITY, FL 32405

Lot: 0180
Contracted Stated Job Value: ¤99,673.00
Job Description: INTERIOR RENOVATION "GIOIA SAILS" (MANUFACTURER BOAT SEAT / CANVAS AWNING)
Type: CN

Contractor

COMMERCIAL CONSTRUCTION INC.
Status Location Address State License Number Phone Fax
ACTIVE

7 SUNSHINE BLVD

ORMOND BEACH, FL 32174

CGC059441 (Exp: 08/31/2026) 386-238-1570 386-238-1571

Sub Contractors

JOHN FREDERICK WANERKA JR
Status Location Address State License Number Phone Fax
CANCEL

P.O. BOX 350214

BUNNELL, FL 32110

EC13003318 (Exp: 08/31/2022) (386)446-9626 (386)445-3131
JUAN EUGENIO CAMPELO
Status Location Address State License Number Phone Fax
INACTIVE

114 ALLGOOD CIRCLE SUITE #101

ST AUGUSTINE, FL 32086

CAC1813797 (Exp: 08/31/2026) 904-824-4275 904-824-4614
ISAAC WALTER JOHNSTON
Status Location Address State License Number Phone
ACTIVE

887 BRENTWOOD DRIVE

Daytona Beach, FL 32117

CFC023634 (Exp: 08/31/2026) (386) 252-7047

Inspection History

Type Request Date Result Inspector
ELECTRIC FINAL 06/06/2013 FINAL APPROVED CMINI
Note: THIS IS A REINSPECTION
ELECTRIC FINAL 06/04/2013 Disapproved -FEE REQUIRED CMINI
Note: THIS IS A REINSPECTION Inspection Resulted at 6/4/2013 3:14:43 PM NEED TO SHOW ADDED CIRCUITS ON BUILDING B AND SUB PANEL ON PLANS ALSO WHAT SUB PANEL IS FEEDING WITH LOAD CALCS.
HVAC FINAL 06/04/2013 APPROVED CMINI
Note: THIS IS A REINSPECTION
BUILDING FINAL 06/04/2013 APPROVED CMINI
FIRE FINAL 06/04/2013 APPROVED JHINDMAN
PLUMBING FINAL 06/03/2013 APPROVED CMINI
Note: THIS IS A REINSPECTION
PLUMBING FINAL 05/30/2013 PARTIALLY APPROVED CMINI
Note: Inspection Resulted at 5/30/2013 3:40:10 PM BUILDING A ONLY
HVAC FINAL 05/30/2013 PARTIALLY APPROVED CMINI
Note: Inspection Resulted at 5/30/2013 3:40:11 PM BUILDING A ONLY
ELECTRIC FINAL 05/30/2013 PARTIALLY APPROVED CMINI
Note: Inspection Resulted at 5/30/2013 3:40:08 PM PARTIAL ON CIRCUITS IN CELING OK..NEED REVISION ON PANEL SCHEDULES TO MATCH PLAN SHOWING SIZES OF PANEL AND BREAKERS TO MATCH NEW CIRCUITS ,RISER DOES NOT MATCH PLAN..,NEW TO SHOW ADDED LIGHTS IN BUILDING A ALSO
U - UTILITY COMMERCIAL FINAL 05/30/2013 APPROVED DSPENCER
ELECTRIC 2ND ROUGH 05/28/2013 APPROVED - AS NOTED CMINI
Note: THIS IS A REINSPECTION Inspection Resulted at 5/28/2013 2:16:37 PM CEILING OUTLETS
ELECTRIC 2ND ROUGH 05/24/2013 CANCELLED BY APPLICANT CMINI
Note: Inspection Resulted at 5/24/2013 12:53:32 PM
HVAC ROUGH 05/21/2013 APPROVED CMINI
Note: THIS IS A REINSPECTION
MONOLITHIC SLAB 05/21/2013 APPROVED - AS NOTED CMINI
Note: Inspection Resulted at 5/21/2013 2:15:34 PM PLUMBING COVER UP
ABOVE CEILING 05/21/2013 APPROVED CMINI
Note: THIS IS A REINSPECTION
FINAL 05/21/2013 CANCELLED BY INSPECTOR CMINI
Note: Inspection Resulted at 5/21/2013 2:16:47 PM WRONG INSPECTION CALLED IN
ABOVE CEILING 05/20/2013 Disapproved -FEE REQUIRED CMINI
Note: Inspection Resulted at 5/20/2013 2:43:58 PM M.C NEEDS TO BE STRAPPED AND SUPPORTED EVERY 6`` INTERVALS,NEED TO STRAP MC WITHIN 12" OF BOXES..CHECK BOX FILL ON JUNCTION BOX..DUCT WORK STILL NOT COMPLETE
HVAC ROUGH 05/20/2013 Disapproved - NO FEE CMINI
Note: Inspection Resulted at 5/20/2013 2:43:59 PM DUCT WORK STILL NOT COMPLETE
PLUMBING 1ST ROUGH 05/20/2013 APPROVED CMINI
PLUMBING 2ND ROUGH 05/20/2013 APPROVED CMINI
Note: THIS IS A REINSPECTION
PLUMBING 2ND ROUGH 05/13/2013 PARTIALLY APPROVED CMINI
Note: Inspection Resulted at 5/13/2013 2:39:40 PM 1ST PHASE
MONOLITHIC SLAB 05/06/2013 APPROVED - AS NOTED CMINI
Note: Inspection Resulted at 5/6/2013 12:09:15 PM PLUMBING COVER UP
PLUMBING 1ST ROUGH 05/03/2013 APPROVED RMARVEL

Review History

Department Status Date In Date Out
ELEC COMPLETE 06/05/2013 06/06/2013
ELEC COMPLETE 06/04/2013 06/04/2013
PLUM COMPLETE 04/26/2013 04/29/2013
FI1 COMPLETE 04/26/2013 04/30/2013
PLUM HOLD 04/22/2013 04/22/2013
Note: 1. Provide pipe sizes (sanitary and vent) for added/relocated fixtures on sanitary riser diagram for building A per 2010 FBC 107.3.5. 2. Provide sanitary riser diagram for building B per 2010 FBC 107.3.5.
ELEC COMPLETE 04/22/2013 04/22/2013
MECH COMPLETE 04/22/2013 04/22/2013
BLD COMPLETE 04/22/2013 04/22/2013
FI1 HOLD 04/22/2013 04/22/2013
Note: 1. Provide a layout of all fixtures, racks, tables and equipment with dimensions for review.
BLD HOLD 04/02/2013 04/03/2013
Note: 1. Provide a floorplan with dimensions. 210 FBC 107.2.1. 2. The minimum corridor width does not comply with 2010 FBC 1023.2.
ELEC HOLD 04/02/2013 04/02/2013
Note: Provide electric load calculations, panel schedules and service riser detail NEC 220 and 230
FI1 HOLD 04/02/2013 04/03/2013
Note: 1. Provide a lifesafety plan with dimensions that includes all paths of travel and all fixtures, tables, racks and equipment. 2. The life safety plan in building A has two sections of F1/ Industrial with different occupant load factors. Provide correct load factors. If the 300 sq ft per person area is storage is there any high pile racks? 3.Provide correct Occupancy classification and occupant load totals on the Lifesafety plan. 4. Sheet TBL and the Lifesafety plan do not have the same exit details. 5. The dead end corridor width does not meet Table 40.2.5 of the 2010 FFPC.
MECH HOLD 04/02/2013 04/03/2013
Note: Provide hvac plans and details suitable for review, inspection and construction per 2010 FBC 107.2.1.
PLUM HOLD 04/02/2013 04/02/2013
Note: 1. Provide service sink each for building A and building B per 2010 FBC P Table 403.1
ZON COMPLETE 04/02/2013 04/04/2013

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REVISION ¤40.00 06/06/2013
REINSPECTION FEE ¤40.00 06/05/2013
REINSPECTION FEE ¤40.00 06/04/2013
REVISION ¤40.00 06/04/2013
SITE PLAN 20 ¤20.00 05/01/2013
SURCHARGE FS 533.721 ¤18.48 05/01/2013
SURCHARGE - FS 468.631 ¤18.48 05/01/2013
ADMIN COMMERCIAL ¤60.00 05/01/2013
INSPECTION - COMMERCIAL ADD ¤697.71 05/01/2013
ELECTRIC FEE ¤119.80 05/01/2013
FIRE PLANS REVIEW ¤25.00 05/01/2013
MECHANICAL FEE ¤119.80 05/01/2013
PLAN CHECK FEE ¤114.63 05/01/2013
PLUMBING FEE ¤119.80 05/01/2013
Fees Total Due: ¤0.00 Total Paid: ¤1,473.70