Permit #2013040154
Permit Details
Status: COED
| Parcel Id: 07-11-31-1090-00000-00B0 |
| Block: 00000 |
| Subdivision: 1228 - SOUTHWEST QUADRANT |
| Job Phone: 904-826-1426 |
| Location Address: 160 CYPRESS POINT PKWY |
| Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION |
| Issue Date: 05/08/2013 |
| NOC: RECORDED |
| Applicant name: FRANK ROBERT SORRENTINO |
| Owner: KATHRYN ZBIKOWSKI |
|
Address 160 CYPRESS POINT PKWY PALM COAST, FL 32164 |
|
Address BUILDING D, UNITS 112 & 113 PALM COAST, FL 32164 |
| Lot: 00B0 |
| Contracted Stated Job Value: ¤10,000.00 |
| Job Description: D 112&113 - INTERIOR BUILDOUT- ZFITNESS & ZIBKO REALTY |
| Type: CN |
Contractor
CLEAR CHOICE WINDOWS OF NORTH FLORIDA
| Status | Location Address | State License Number | Phone |
| CANCEL |
212 BEECHWOOD LANE PALM COAST, FL 32137 |
CBC1258275 (Exp: 08/31/2016) | 386-225-3304 |
Sub Contractors
GLEN WILLIAM KEHLE
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
P. O. Box 353511 BUNNELL, FL 32110 |
CFC057241 (Exp: 08/31/2026) | (386) 447-4249 | (386) 437-8488 |
JAMES KUYKENDALL
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
2550 US 1 NORTH SUITE 3 BUNNELL, FL 32110 |
CAC1815546 (Exp: 08/31/2022) | (386)437-2929 | (386)437-2942 |
JOHN EDWARD GAMBONE
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
55 BARRISTER LN PALM COAST, FL 32137 |
ER13013466 (Exp: 08/31/2014) | 386-586-9144 | (386)246-6305 |
Inspection History
| Type | Request Date | Result | Inspector |
| PLUMBING FINAL | 07/03/2013 | APPROVED | RMARVEL |
| HVAC FINAL | 07/03/2013 | APPROVED | RMARVEL |
| ELECTRIC FINAL | 07/03/2013 | APPROVED | RMARVEL |
| ABOVE CEILING | 07/03/2013 | APPROVED | RMARVEL |
| Note: THIS IS A REINSPECTION | |||
| BUILDING FINAL | 07/03/2013 | FINAL APPROVED | RMARVEL |
| FIRE FINAL | 07/03/2013 | APPROVED | JHINDMAN |
| U - UTILITY COMMERCIAL FINAL | 07/03/2013 | APPROVED | RMARVEL |
| Note: Inspection Resulted at 7/3/2013 3:24:43 PM PER DANNY SPENCER. | |||
| ELECTRIC 2ND ROUGH | 06/07/2013 | APPROVED | RMARVEL |
| Note: THIS IS A REINSPECTION Inspection Resulted at 6/7/2013 8:20:24 AM WALLS ONLY. | |||
| ABOVE CEILING | 06/07/2013 | Disapproved -FEE REQUIRED | RMARVEL |
| Note: Inspection Resulted at 6/7/2013 8:20:23 AM NOT READY. STILL NEED TO INSTALL POWER AND BOXES FOR FANS IN CEILING. CALL IN FOR REINSPECTION WHEN WORK IS COMPLETE. | |||
| FRAMING | 06/04/2013 | APPROVED | RMARVEL |
| Note: THIS IS A REINSPECTION | |||
| PLUMBING 2ND ROUGH | 06/04/2013 | APPROVED | RMARVEL |
| FRAMING | 05/31/2013 | PARTIALLY APPROVED | CMINI |
| Note: Inspection Resulted at 5/31/2013 3:35:23 PM FRAMING ON WALLS ALL CAN BE 1 SIDED EXCEPT SHOWER WALL,NEED TO COMPLETE PLUMBING AND CALL 2ND ROUGH PLUMBING INSPECTION BEFORE COVER UP ON SHOWER WALL.. | |||
| ELECTRIC 2ND ROUGH | 05/31/2013 | PARTIALLY APPROVED | CMINI |
| Note: Inspection Resulted at 5/31/2013 3:35:25 PM NEED REVISION APPROVED ON ELECTRIC .CHECKED STRAPPING OK.. ALL CAN BE 1 SIDED EXCEPT SHOWER WALL,NEED TO COMPLETE PLUMBING AND CALL 2ND ROUGH PLUMBING INSPECTION BEFORE COVER UP ON SHOWER WALL.. | |||
| HVAC ROUGH | 05/29/2013 | APPROVED | RMARVEL |
| PLUMBING 1ST ROUGH | 05/20/2013 | APPROVED | CMINI |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 06/05/2013 | 06/06/2013 |
| ELEC | HOLD | 05/30/2013 | 05/31/2013 |
| Note: The original electric drawings are signed and sealed so revised drawings will need to be signed and sealed FBC 107.1 | |||
| PLUM | COMPLETE | 05/07/2013 | 05/07/2013 |
| MECH | COMPLETE | 05/07/2013 | 05/07/2013 |
| FI1 | COMPLETE | 05/07/2013 | 05/08/2013 |
| FI1 | HOLD | 04/26/2013 | 04/30/2013 |
| Note: 1. Provide a complete coordinated drawing by a design professional. per the Building Official. | |||
| MECH | HOLD | 04/26/2013 | 04/29/2013 |
| Note: 1. Submitted hvac plan with return air from individual office using 6 in x 10 opening above the door is not adequate to comply with 2010 FBC M 601.4 for balance retun air requirement. | |||
| PLUM | HOLD | 04/26/2013 | 04/29/2013 |
| Note: 1. Provide water heater specifications and instalation instructions as previously requested. 2. Drinking fountain as previously requested shall be included in the riser diagrams for both sanitary and domestic water per 2010 FBC 107.3.5. | |||
| ELEC | COMPLETE | 04/26/2013 | 05/07/2013 |
| ELEC | COMPLETE | 04/23/2013 | 04/23/2013 |
| FI1 | HOLD | 04/23/2013 | 04/23/2013 |
| Note: 1. Provide the occupancy type as listed in the Building and Fire codes. 2. Calculate the occupant load based on the square footage and the Building and Fire codes. | |||
| MECH | HOLD | 04/23/2013 | 04/24/2013 |
| Note: 1. Plan indicates no change in existing hvac. The proposed plan shows 3 offices with full height patitions. How would supply and return be accomplished in those areas per 2010 FBC 107.2.1. Previous comment item 2 shall be addressed - 2. Provide the existing capacity of hvac units to verify if they meet the submitted calculated heating/cooling load per 2010 FBC EC 403.6. | |||
| PLUM | HOLD | 04/23/2013 | 04/24/2013 |
| Note: 1. Provide specifications of water heater, its location and manufacturer installation instructions per 2010 FBC P 502.1. 2. Provide drinking fountain per 2010 FBC P Table 403.1. | |||
| PLUM | HOLD | 04/19/2013 | 04/19/2013 |
| Note: Provide domestic water riser diagram and material specification per 2010 FBC 107.3.5. | |||
| ELEC | HOLD | 04/19/2013 | 04/19/2013 |
| Note: Provide load calculations and panel schedules NEC Article 220 | |||
| FI1 | HOLD | 04/19/2013 | 04/19/2013 |
| Note: 1. The life safety plan must be for the new configuration of the space. It must show the exits, exit sign locations, emergency lights, travel distances, fire extinguisher locations, all door and hallway widths, occupant load and occupancy type. | |||
| MECH | HOLD | 04/19/2013 | 04/19/2013 |
| Note: 1. Provide proposed hvac plan suitable for review, inspection and construction per 2010 FBC 107.3.5. 2. Provide the existing capacity of hvac units to verify if they meet the submitted calculated heating/cooling load per 2010 FBC EC 403.6. | |||
| BLD | HOLD | 04/04/2013 | 04/04/2013 |
| Note: Provide plan drawings with detail suitable for review, construction and inspection FBC 107.2.1 | |||
| ELEC | HOLD | 04/04/2013 | 04/04/2013 |
| Note: Provide plan drawings with detail suitable for review, construction and inspection FBC 107.2.1 | |||
| FI1 | HOLD | 04/04/2013 | 04/05/2013 |
| Note: 1. Provide a Lifesafety plan that is suitable for review, construction and inspection. FFPC | |||
| PLUM | HOLD | 04/04/2013 | 04/04/2013 |
| Note: Provide plan drawings with detail suitable for review, construction and inspection FBC 107.2.1 | |||
| UD1 | COMPLETE | 04/04/2013 | 04/04/2013 |
| ZON | COMPLETE | 04/04/2013 | 04/04/2013 |
| BLD | COMPLETE | 04/04/2013 | 05/08/2013 |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 07/03/2013 |
| REVISION | ¤40.00 | 07/03/2013 |
| SITE PLAN 20 | ¤20.00 | 05/08/2013 |
| SURCHARGE FS 533.721 | ¤6.42 | 05/08/2013 |
| SURCHARGE - FS 468.631 | ¤6.42 | 05/08/2013 |
| ADMIN COMMERCIAL | ¤60.00 | 05/08/2013 |
| INSPECTION - COMMERCIAL ADD | ¤70.00 | 05/08/2013 |
| ELECTRIC FEE | ¤66.00 | 05/08/2013 |
| FIRE PLANS REVIEW | ¤25.00 | 05/08/2013 |
| MECHANICAL FEE | ¤66.00 | 05/08/2013 |
| PLAN CHECK FEE | ¤100.00 | 05/08/2013 |
| PLUMBING FEE | ¤66.00 | 05/08/2013 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤565.84 |