I want to search for...
Permit #2013050235
Permit Details
Status: COED
| Parcel Id: 08-12-31-5835-00000-0010 |
| CONDITIONED SPACE: 2426 sqft |
| OPENED PORCH (WITH ROOF) : 186 sqft |
| Total Square Footage: 2612 sqft |
| Block: 00000 |
| Subdivision: 2117 - Town Center Phase III, BROOKHAVEN |
| Job Phone: 407-741-8500 |
| Location Address: 114 BROOKHAVEN CT N |
| Type: BM - BUILDING MULTI - APARTMENT |
| Issue Date: 09/13/2013 |
| NOC: RECORDED |
| Applicant name: SCOTT W CULP |
| Owner: BROOKHAVEN DEVELOPMENT LAND LTD |
|
Address 200 E CANTON AVE # 1020 WINTER PARK, FL 32789 |
| Lot: 0010 |
| Contracted Stated Job Value: ¤255,698.00 |
| Job Description: BUILDING 28 - BROOKHAVEN 2 UNIT APARTMENT |
| Type: CN |
Contractor
CPG CONSTRUCTION LLP
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
200 E CANTON AVE # 102 WINTER PARK, FL 32789 |
CGC1512998 (Exp: 08/31/2016) | 407-741-8500 | 407-643-2551 |
Sub Contractors
RANCE F BORDERICK
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
430 WEST DRIVE ALTAMONTE SPRINGS, FL 32714 |
EC0000981 (Exp: 08/31/2026) | (407)788-3500 | 407-788-2007 |
DAVID A CROSON
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
31550 COUNTY ROAD 437 SORRENTO, FL 32776 |
CFC1426109 (Exp: 08/31/2022) | 352-729-7100 | 352-735-0623 |
JOSEPH RICHARD CASSIDY JR
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
17304 PHIL C PETERS RD WINTER GARDEN, FL 34787 |
CCC1327385 (Exp: 08/31/2020) | 407-654-4426 | (407)654-4307 |
JOHN MAXEN BARTKOVICH
| Status | Location Address | State License Number | Phone |
| ACTIVE |
818 SHADOWMOSS DR WINTERGARDEN, FL 32787 |
CAC1815793 (Exp: 08/31/2026) | 407-886-3729 |
Inspection History
| Type | Request Date | Result | Inspector |
| LDSC- LANDSCAPE FINAL | 03/31/2014 | APPROVED | CJMINI |
| Note: THIS IS A REINSPECTION | |||
| LDSC- LANDSCAPE FINAL | 03/27/2014 | Disapproved -FEE REQUIRED | CJMINI |
| Note: Building # 28 CJM Remove shrub access to the FDC. Place FDC sign on pole per Fire Inspector direction. Need to change plant material on plans (prodocarpus) Replace lorapetilums that are too small facing Brookhaven Way Sod needs to be rerolled and new sod laid in rear (northside of Building 28 next to upland buffer). Sod need to be leveled. Too many sporadic portions of sod. Replace second ligustrum from west corner of building across from the light pole. Replace front two oleanders and one in back row closest to crepe myrtle. Does not meet specifications. In front bed, replace two jasmines. Does not meet specifications. Due to drip irrigation being insufficient resource, add bubbler to trees that are located in landscape beds. ¼ " for ligustrums and crepe myrtles ; ½" on magnolias and oaks Please ensure that all irrigation is adjusted prior to punch-list reinspection. | |||
| LDSC- LANDSCAPE FINAL | 03/26/2014 | CANCELLED BY INSPECTOR | JMONTARULI |
| FIRE FINAL | 03/24/2014 | APPROVED | JHINDMAN |
| Note: THIS IS A REINSPECTION | |||
| FIRE FINAL | 03/21/2014 | Disapproved -FEE REQUIRED | JHINDMAN |
| Note: Inspection Resulted at 3/21/2014 2:30:03 PM 1. IDENTIFY RISER ROOM. 2. FIRE PROTECTION SYSTEMS ARE NOT COMPLETE. | |||
| U - UTILITY COMMERCIAL FINAL | 03/21/2014 | FINAL APPROVED | DSPENCER |
| PLUMBING FINAL | 03/20/2014 | APPROVED | RMARVEL |
| HVAC FINAL | 03/20/2014 | APPROVED | RMARVEL |
| ELECTRIC - EARLY POWER | 03/20/2014 | CANCELLED BY APPLICANT | AIRS WEB |
| ELECTRIC FINAL | 03/20/2014 | APPROVED | RMARVEL |
| BUILDING FINAL | 03/20/2014 | APPROVED | RMARVEL |
| ELECTRIC - EARLY POWER | 02/28/2014 | APPROVED | RMARVEL |
| Note: permit contractor Inspection Resulted at 2/28/2014 2:29:43 PM CALLED FPL AT 10:30 | |||
| ELECTRIC 1ST ROUGH | 02/26/2014 | CANCELLED BY APPLICANT | RMARVEL |
| FIREWALL | 02/04/2014 | APPROVED | JHINDMAN |
| Note: THIS IS A REINSPECTION | |||
| FIREWALL | 01/06/2014 | PARTIALLY APPROVED | JHINDMAN |
| Note: THIS IS A REINSPECTION Inspection Resulted at 1/6/2014 12:21:05 PM FIRST LAYER ON WALL | |||
| FIREWALL | 01/03/2014 | PARTIALLY APPROVED | JHINDMAN |
| Note: THIS IS A REINSPECTION Inspection Resulted at 1/3/2014 11:28:26 AM FIRE COATING. | |||
| INSULATION | 01/03/2014 | APPROVED | RMARVEL |
| Note: THIS IS A REINSPECTION | |||
| INSULATION | 01/02/2014 | CANCELLED BY APPLICANT | RMARVEL |
| FIREWALL | 01/02/2014 | PARTIALLY APPROVED | JHINDMAN |
| Note: THIS IS A REINSPECTION Inspection Resulted at 1/2/2014 12:22:56 PM ATTIC PARTYWALL PENETRATIONS | |||
| FIREWALL | 12/31/2013 | Disapproved -FEE REQUIRED | JHINDMAN |
| Note: Inspection Resulted at 12/31/2013 12:33:16 PM EXHAUSTR VENT PENETRATIONS ARE NOT 4 FEET FROM THE PARTYWALL. 2010 FBC 107.4. | |||
| ALL ROUGH | 12/30/2013 | APPROVED | RMARVEL |
| Note: THIS IS A REINSPECTION | |||
| ALL ROUGH | 12/26/2013 | CANCELLED BY APPLICANT | CMINI |
| Note: THIS IS A REINSPECTION | |||
| ALL ROUGH | 12/19/2013 | CANCELLED BY APPLICANT | JMONTARULI |
| Note: THIS IS A REINSPECTION | |||
| HVAC ROUGH | 12/11/2013 | CANCELLED BY APPLICANT | RMARVEL |
| PLUMBING 2ND ROUGH | 12/11/2013 | CANCELLED BY APPLICANT | RMARVEL |
| ELECTRIC 2ND ROUGH | 12/11/2013 | CANCELLED BY APPLICANT | RMARVEL |
| Note: THIS IS A REINSPECTION | |||
| ALL ROUGH | 12/11/2013 | Disapproved -FEE REQUIRED | RMARVEL |
| Note: Inspection Resulted at 12/11/2013 2:54:00 PM REVISE SIZE OF VTR AND SINKS IN MASTER BATH. PROVIDE 10IN DUCT AT AHU FOR FRONT ROOM AREA. REMOVE STRAP CAUSING SAGGING AT FRONT ROOM AREA OF DUCT. STRAP DUCT IN MASTER CLOSET. USE APPROVED MEANS OF STRAPPING AT LIGHT SWITCH AT KITCHEN ENTRANCE AREA ON LEFT SIDE. PROVIDE REPAIRS FOR OVERNOTCHED STUDS AND TOP PLATES OF BEARING AND NON BEARING WALLS. PROVIDE REVISION FOR LOCATION OF DOORS AT FRONT ENTRANCE FOR WATER HEATER CLOSETS. PROVIDE REVISION FOR ADDED CHASE WALL FOR REFIGERANT LINES FOR AIR CONDITIONING SYSTEM. OK TO START SIDING. | |||
| LATH/BRICK/WATER BARRIER | 12/10/2013 | APPROVED | RMARVEL |
| GRAVITY SEWER | 12/10/2013 | APPROVED | RMARVEL |
| U - SEWER TIE IN | 12/10/2013 | APPROVED | DSPENCER |
| FRAMING | 12/05/2013 | APPROVED - AS NOTED | DROCKWELL |
| Note: window fasteners Inspection Resulted at 12/5/2013 3:25:08 PM THIS IS A WINDOW ATTACHMENT INSPECTION. | |||
| ELECTRIC 2ND ROUGH | 11/22/2013 | Disapproved -FEE REQUIRED | RMARVEL |
| Note: Inspection Resulted at 11/22/2013 2:57:03 PM ADD RECEPTACLE IN FRONT ROOM TO MEET WALL SPACE. NEC 2008 210.52. REVISE PLANS TO SHOW CHANGES IN ELECTRICAL PLACEMENT INCLUDING LIGHTING ON FRONT PORCH AND AT KITCHEN PENINSULA.. SHOW WHERE AHU HAS MOVED LOCATIONS. VERIFY WHICH ELECTRICAL DRAWING IS TO BE USED. THERE ARE 2 DIFFERANT ONES. | |||
| ROOF SHEATHING / BRACE / TIE DOWN | 11/20/2013 | APPROVED | RMARVEL |
| Note: THIS IS A REINSPECTION | |||
| EXTERIOR STRAP/CLIP | 11/18/2013 | APPROVED | CMINI |
| ROOF SHEATHING / BRACE / TIE DOWN | 11/18/2013 | Disapproved -FEE REQUIRED | CMINI |
| Note: THIS IS A REINSPECTION Inspection Resulted at 11/18/2013 3:51:15 PM NEED REVISION FOR TRUSS REPAIR | |||
| ROOF SHEATHING / BRACE / TIE DOWN | 11/12/2013 | Disapproved -FEE REQUIRED | CMINI |
| Note: THIS IS A REINSPECTION Inspection Resulted at 11/12/2013 3:30:38 PM SHINERS NEED TO BE REMOVED...NEED REPAIR REVISION FOR BROKEN TRUSS..BOLTS NEED TO BE 4`` O.C. | |||
| EXTERIOR WALL SHEATHING / SHEARWALL | 10/28/2013 | APPROVED | DROCKWELL |
| ROOF SHEATHING / BRACE / TIE DOWN | 10/28/2013 | PARTIALLY APPROVED | DROCKWELL |
| Note: Inspection Resulted at 10/28/2013 2:48:42 PM ROOF DECKING ONLY.REMOVE MANY SHINERS | |||
| ELECTRIC TEMP POLE | 10/18/2013 | CANCELLED BY APPLICANT | RMARVEL |
| MONOLITHIC SLAB | 10/03/2013 | APPROVED | RMARVEL |
| ELECTRIC 1ST ROUGH | 10/03/2013 | APPROVED | RMARVEL |
| Note: Inspection Resulted at 10/3/2013 3:43:48 PM UFER GROUND. 20FT CONCRETE ENCASED ELECTRODE. | |||
| PLUMBING 1ST ROUGH | 09/27/2013 | APPROVED | CMINI |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 03/26/2014 | 03/26/2014 |
| ELEC | COMPLETE | 01/08/2014 | 01/08/2014 |
| BLD | COMPLETE | 12/26/2013 | 12/27/2013 |
| FI1 | COMPLETE | 12/26/2013 | 12/27/2013 |
| BLD | HOLD | 12/19/2013 | 12/20/2013 |
| Note: 1. Provide the correct strap Id for the other wall straps. 2010 FBC 107.2.1. | |||
| ELEC | COMPLETE | 12/19/2013 | 12/19/2013 |
| Note: no electric changes | |||
| MECH | COMPLETE | 12/19/2013 | 12/20/2013 |
| Note: Revision - not applicable | |||
| PLUM | COMPLETE | 12/19/2013 | 12/20/2013 |
| Note: Revision - not applicable | |||
| BLD | HOLD | 12/18/2013 | 12/18/2013 |
| Note: 1. Provide a correct wall strap. Simpson RSP 18 strap is not one of their products. If you meant a RPS 18 strap please correct the letter.2010 FBC 107.2.1 | |||
| FI1 | HOLD | 12/18/2013 | 12/18/2013 |
| Note: 1. Provide the manufacturers testing that was done for the Flame Control 20-20a used with the DTM acrylic primer along with the installation instructions for its use on smooth metal surfaces. | |||
| BLD | COMPLETE | 12/11/2013 | 12/12/2013 |
| FI1 | HOLD | 12/10/2013 | 12/11/2013 |
| Note: 1. According to the manufacturers specifications, Flame control No 20-20a (under new surfaces) states that No 20-20a will not give a fire resistive rating on metal surfaces. 2. The primer must also be compatible with the fire retardant. 2010 FBC 709.4.1.1. | |||
| PLUM | COMPLETE | 12/10/2013 | 12/10/2013 |
| Note: Revision - 1. Revised sanitary riser diagram only (Sheet No. AP2.3a, dated 11-18 -13. Disregard domestic water layout on this sheet and refer to revision 1 of the same Sheet No. AP2.3a dated 07-29-13 for domestic water only.) | |||
| PLUM | HOLD | 12/05/2013 | 12/05/2013 |
| Note: Previous plumbing revision hold comment below shall be addressed first before processing another plumbing revision. This is how the computer review process works. - Submitted revised Plumbing Sheet No. AP2.3a dated 11-18-13 shall reflect the latest revised domestic water underground layout dated 7-29-13 on revision 1 where it shows separate water service to each building unit OR delete domestic water on this new revision (11-18-13 ) and show only revised sanitary layout and riser diagram for clarity per 2010 FBC 107.2.1. | |||
| ELEC | COMPLETE | 12/05/2013 | 12/05/2013 |
| MECH | COMPLETE | 12/05/2013 | 12/05/2013 |
| Note: Revision 4 - changed duct layout, hvac units, details | |||
| BLD | COMPLETE | 11/19/2013 | 12/05/2013 |
| PLUM | HOLD | 11/19/2013 | 11/22/2013 |
| Note: Submitted revised Plumbing Sheet No. AP2.3a dated 11-18-13 shall reflect the latest revised domestic water underground layout dated 7-29-13 on revision 1 where it shows separate water service to each building unit OR delete domestic water on this new revision (11-18-13 ) and show only revised sanitary layout and riser diagram for clarity per 2010 FBC 107.2.1. | |||
| BLD | COMPLETE | 11/14/2013 | 11/14/2013 |
| Note: Released By: JMCGOWEN revision, letter from D.P.O.R. on stud spacing | |||
| BLD | COMPLETE | 11/14/2013 | 11/15/2013 |
| Note: Released By: JMCGOWEN Truss repair | |||
| BLD | HOLD | 11/08/2013 | 11/08/2013 |
| Note: Held By: JHINDMAN 1. Provide a complete structural drawing for the header changes that is suitable for review, construction and inspection. 2010 FBC 107.2.1. | |||
| BLD | HOLD | 11/08/2013 | 11/08/2013 |
| Note: Held By: JHINDMAN 1. Provide a complete structural drawing for the header changes that is suitable for review, construction and inspection. 2010 FBC 107.2.1. | |||
| BLD | HOLD | 11/06/2013 | 11/06/2013 |
| Note: Held By: JHINDMAN 1. Provide clarification for the uplift value and the number of screws and that are required per stud to plate connection. 2010 FBC 107.2.1 | |||
| PLUM | COMPLETE | 10/18/2013 | 10/18/2013 |
| Note: Released By: BBEMBRY Plumbing revision was submitted for this building by accident. Barbie, I accidentally added the permit number to this last revision for Bldg #28 (2013050235). I need to remove that from the last revision submittal. There is no revision for Bldg 28. Thank you -----Original Message----- From: NOTIFICATION USER - AUTOMATED [mailto:bbembry@PALMCOASTGOV.COM] Sent: Thursday, October 17, 2013 8:38 AM To: Jeffrey Morgan; Philip Latta Subject: Plan Review Status Change Notification | |||
| BLD | COMPLETE | 10/16/2013 | 10/16/2013 |
| Note: n/a | |||
| UD1 | COMPLETE | 10/16/2013 | 10/17/2013 |
| PLUM | HOLD | 10/16/2013 | 10/17/2013 |
| Note: There are no plumbing revision plans for this permit from the submitted package of 9 permit revisions. Please clarify per 2010 FBC 107.2.1. | |||
| BLD | COMPLETE | 09/30/2013 | 09/30/2013 |
| BLD | HOLD | 09/23/2013 | 09/24/2013 |
| Note: 1. Provide signed and sealed drawings per 2010 FBC 107.1. | |||
| BLD | COMPLETE | 08/22/2013 | 08/22/2013 |
| BLD | HOLD | 08/07/2013 | 08/07/2013 |
| Note: 1. Provide roof truss engineering for review per 2010 FBC 107.3.5. | |||
| UD1 | COMPLETE | 08/07/2013 | 08/08/2013 |
| ZON | COMPLETE | 08/07/2013 | 08/08/2013 |
| PLLA | COMPLETE | 07/16/2013 | 07/16/2013 |
| Note: Released By: WBUTLER | |||
| BLD | HOLD | 07/08/2013 | 07/08/2013 |
| Note: 1. Provide Roof truss engineering per 2010 FBC107.3.5. | |||
| ELEC | COMPLETE | 07/08/2013 | 07/08/2013 |
| ENGIN1 | COMPLETE | 07/08/2013 | 07/08/2013 |
| FI1 | COMPLETE | 07/08/2013 | 07/08/2013 |
| MECH | COMPLETE | 07/08/2013 | 07/08/2013 |
| PLLA | HOLD | 07/08/2013 | 07/08/2013 |
| Note: Reviewer: Bill Butler, Landscape Architect 7-8-13 1. Need landscape and irrigation plans to be submitted for review and approval. | |||
| PLUM | COMPLETE | 07/08/2013 | 07/08/2013 |
| UD1 | HOLD | 07/08/2013 | 07/15/2013 |
| Note: Plans show single water service in to building. Each unit shall have individual service and meter located in green space outside of building in existing utility easement | |||
| BLD | HOLD | 05/10/2013 | 05/13/2013 |
| Note: Held By: FREODICA 1. Provide specific plans and details applicable to this permit application per 2010 FBC 107.2.1. | |||
| UD1 | COMPLETE | 05/10/2013 | 05/10/2013 |
| ZON | HOLD | 05/10/2013 | 07/15/2013 |
| Note: 1. Please revise the plans to provide a screen porch elevation detailing the materials to be used on the screen enclosure, including any kickplates if applicable. 2. Please revise sheet AA6.3 to include the length and width dimensions of the buildings, which should match the previously approved elevations in the Development Order approval. 3. Per LDC Sec. 12.03.01.H and I, street address signs or building occupant signs affixed to the wall shall not exceed 2 square feet in sign copy area. Please revise the plans to include a detail of the "Brookhaven" occupant or street address wall sign to show the dimensions, not to exceed 2 square feet. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 04/01/2014 |
| REVISION | ¤40.00 | 04/01/2014 |
| ADDITIONAL FEE | ¤500.00 | 03/25/2014 |
| IMPACT FEE PARKS | ¤2,687.96 | 03/24/2014 |
| IMPACT FEE SCHOOL | ¤1,862.00 | 03/24/2014 |
| IMPACT FEE TRANSPORTATION | ¤5,431.20 | 03/24/2014 |
| INSPECTION FEE 20 | ¤20.00 | 03/24/2014 |
| REINSPECTION FEE | ¤40.00 | 03/24/2014 |
| REINSPECTION FEE | ¤40.00 | 03/24/2014 |
| REINSPECTION FEE | ¤40.00 | 03/24/2014 |
| REVISION | ¤40.00 | 03/24/2014 |
| REVISION | ¤40.00 | 03/24/2014 |
| REVISION | ¤40.00 | 03/24/2014 |
| REVISION | ¤40.00 | 03/24/2014 |
| REVISION | ¤40.00 | 03/24/2014 |
| REVISION | ¤40.00 | 03/24/2014 |
| REVISION | ¤40.00 | 03/24/2014 |
| REVISION | ¤40.00 | 03/24/2014 |
| REVISION | ¤40.00 | 03/24/2014 |
| REVISION | ¤40.00 | 03/24/2014 |
| REVISION | ¤40.00 | 03/24/2014 |
| REVISION | ¤40.00 | 03/24/2014 |
| REINSPECTION FEE | ¤40.00 | 03/24/2014 |
| REINSPECTION FEE | ¤40.00 | 03/24/2014 |
| REINSPECTION FEE | ¤40.00 | 03/24/2014 |
| SURCHARGE FS 533.721 | ¤37.19 | 09/13/2013 |
| SURCHARGE - FS 468.631 | ¤37.19 | 09/13/2013 |
| MECHANICAL FEE | ¤219.00 | 09/13/2013 |
| PERMIT FEE | ¤1,457.50 | 09/13/2013 |
| PLAN CHECK FEE | ¤304.75 | 09/13/2013 |
| PLUMBING FEE | ¤219.00 | 09/13/2013 |
| FIRE PLANS REVIEW | ¤26.12 | 09/13/2013 |
| ADMIN COMMERCIAL | ¤60.00 | 09/13/2013 |
| ELECTRIC FEE | ¤219.00 | 09/13/2013 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤13,880.91 |