Permit #2013050243
Permit Details
Status: COED
| Parcel Id: 08-12-31-5835-00000-0010 |
| CONDITIONED SPACE: 2240 sqft |
| CONDITIONED SPACE: 2984 sqft |
| GARAGE: 996 sqft |
| OPENED PORCH (WITH ROOF) : 440 sqft |
| Total Square Footage: 6660 sqft |
| Block: 00000 |
| Subdivision: 2117 - Town Center Phase III, BROOKHAVEN |
| Job Phone: 407-741-8500 |
| Location Address: 112 BROOKHAVEN CV |
| Type: BM - BUILDING MULTI - APARTMENT |
| Issue Date: 10/11/2013 |
| NOC: RECORDED |
| Applicant name: SCOTT W CULP |
| Owner: BROOKHAVEN DEVELOPMENT LAND LTD |
|
Address 200 E CANTON AVE # 102 WINTER PARK, FL 32789 |
| Lot: 0010 |
| Contracted Stated Job Value: ¤310,085.00 |
| Job Description: BUILDING 7 - BROOKHAVEN 4 UNIT APARTMENT |
| Type: CN |
Contractor
CPG CONSTRUCTION LLP
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
200 E CANTON AVE # 102 WINTER PARK, FL 32789 |
CGC1512998 (Exp: 08/31/2016) | 407-741-8500 | 407-643-2551 |
Sub Contractors
RANCE F BORDERICK
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
430 WEST DRIVE ALTAMONTE SPRINGS, FL 32714 |
EC0000981 (Exp: 08/31/2026) | (407)788-3500 | 407-788-2007 |
DAVID A CROSON
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
31550 COUNTY ROAD 437 SORRENTO, FL 32776 |
CFC1426109 (Exp: 08/31/2022) | 352-729-7100 | 352-735-0623 |
JOSEPH RICHARD CASSIDY JR
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
17304 PHIL C PETERS RD WINTER GARDEN, FL 34787 |
CCC1327385 (Exp: 08/31/2020) | 407-654-4426 | (407)654-4307 |
JOHN MAXEN BARTKOVICH
| Status | Location Address | State License Number | Phone |
| ACTIVE |
818 SHADOWMOSS DR WINTERGARDEN, FL 32787 |
CAC1815793 (Exp: 08/31/2026) | 407-886-3729 |
Inspection History
| Type | Request Date | Result | Inspector |
| FIRE FINAL | 04/07/2014 | APPROVED | JHINDMAN |
| LDSC- LANDSCAPE FINAL | 04/07/2014 | APPROVED - AS NOTED | WBUTLER |
| Note: LANDSCAPE/ IRRIGATION FINALS FOR BROOKHAVEN BUILDINGS 6, 7 AND 8 Permit number 2013050242 (building 6) Permit number 2013050243 (building 7) Permit number 2013050244 (building 8) 4-7-14 NOTE: THESE ITEMS WILL BE REINSPECTED AT THE NEXT BUILDING GROUP STAGE INSPECTION 1. Landscape buffer on the east side of buildings 6 and 7 not planted per the approved plan. Need to re-space magnolia and wax myrtle trees and add as needed. Due to existing natural vegetation and trees at the south end of the buffer, the last two magnolias and the last 6 wax myrtles do not need to be planted and irrigated. Can pick this change up on the as-builts. 2. Need to build earthen watering dams around all trees to contain water from bubblers. 3. The concrete splash blocks between the buildings and sidewalks need to be turned 90 degrees and elevated such that the water coming from the downspouts flows out of the bed and onto the sidewalk. One splash block near the west entrance to building 7 is broken and needs to be replaced. All other splash blocks that empty directly into planting beds need to be removed and downspout extensions are to be installed to reach the edge of the lawn. Some areas may require the shifting of the foundation plants to provide a straight shot from the building to the grass. 4. Add 3 more podocarpus between the sidewalk and the backflow preventer pad to screen this unit from street view. Pick up on as-built. 5. Check for possible irrigation leak in sod behind building 7. 6. Add bubblers to the trees that are currently being planted at the south end of the eastern landscape buffer. 7. Move one rotor head closer to the parking lot directly east of building 6. This head is blasting into a wax myrtle tree. 8. At the north side of the planting bed around the FPL transformer, change the irrigation head from a rotor head to a PGJ head. 9. Add missing spray head "Y" to the east corner of the three parking spaces west of building 6. Move adjacent head "H" to center in the area. 10. Missing a full circle PGJ head in the sod behind building 8. 11. In front of buildings 6, 7 and 8, need to install the correct nozzle ("G") to irrigate the sodded area. There are two in front of each building. 12. Need purple bubblers on all trees. Some of the paint on the PGJ heads is coming off so need to replace with factory purple heads. 13. Need landscape and irrigation as-builts provided that are signed and sealed by a registered Florida landscape architect. These will be required prior to the certificate of occupancy of the last unit. Make sure the following is provided: - Measurements from two fixed points for all valve boxes, drip zone flush plugs and wire splices. - The as-built irrigation plan zone numbering agrees with the way the controller is wired. - A card in the controller indicating the general area that zone operates and what type of zone it is (spray, rotor or drip) - Any deviations from the approved plan must be indicated. | |||
| U - UTILITY COMMERCIAL FINAL | 04/07/2014 | FINAL APPROVED | DSPENCER |
| BUILDING FINAL | 04/04/2014 | APPROVED | RMARVEL |
| PLUMBING FINAL | 04/04/2014 | APPROVED | RMARVEL |
| HVAC FINAL | 04/04/2014 | APPROVED | RMARVEL |
| ELECTRIC FINAL | 04/04/2014 | APPROVED | RMARVEL |
| ELECTRIC - EARLY POWER | 03/19/2014 | APPROVED | RMARVEL |
| Note: Inspection Resulted at 3/19/2014 3:23:36 PM CALLED FPL AT 11:17 | |||
| U - SEWER TIE IN | 03/17/2014 | APPROVED | DSPENCER |
| GRAVITY SEWER | 03/05/2014 | APPROVED | RMARVEL |
| LATH/BRICK/WATER BARRIER | 02/27/2014 | APPROVED | DROCKWELL |
| FIREWALL | 02/14/2014 | APPROVED | RMARVEL |
| Note: THIS IS A REINSPECTION | |||
| INSULATION | 02/12/2014 | APPROVED | RMARVEL |
| ALL ROUGH | 02/10/2014 | CANCELLED BY APPLICANT | CMINI |
| Note: THIS IS A REINSPECTION | |||
| ALL ROUGH | 02/10/2014 | APPROVED | RMARVEL |
| FIREWALL | 02/10/2014 | Disapproved -FEE REQUIRED | CMINI |
| Note: THIS IS A REINSPECTION Inspection Resulted at 2/10/2014 3:28:58 PM SOFFIT NOT COMPLETE AND PORCH AREAS NOT COMPOUNDED FULLY | |||
| FIREWALL | 02/07/2014 | PARTIALLY APPROVED | JHINDMAN |
| Note: THIS IS A REINSPECTION Inspection Resulted at 2/7/2014 1:10:15 PM ATTIC SPRAY | |||
| WINDOW NAILING | 02/07/2014 | APPROVED | JHINDMAN |
| ALL ROUGH | 02/07/2014 | CANCELLED BY APPLICANT | JHINDMAN |
| ELECTRIC 1ST ROUGH | 02/05/2014 | APPROVED | JHINDMAN |
| Note: Inspection Resulted at 2/5/2014 12:54:37 PM UNDERGROUND SERVICE PIPING | |||
| FIREWALL | 01/24/2014 | PARTIALLY APPROVED | JHINDMAN |
| Note: THIS IS A REINSPECTION wall taping | |||
| FIREWALL | 01/22/2014 | PARTIALLY APPROVED | JHINDMAN |
| Note: THIS IS A REINSPECTION wall screws behind chasewalls | |||
| EXTERIOR WALL SHEATHING / SHEARWALL | 01/16/2014 | APPROVED | DROCKWELL |
| ROOF SHEATHING / BRACE / TIE DOWN | 01/16/2014 | APPROVED | DROCKWELL |
| EXTERIOR STRAP/CLIP | 01/16/2014 | APPROVED | DROCKWELL |
| FIREWALL | 01/13/2014 | PARTIALLY APPROVED | JHINDMAN |
| Note: THIS IS A REINSPECTION Inspection Resulted at 1/13/2014 1:23:32 PM TAPING IN ATTIC | |||
| FIREWALL | 01/09/2014 | PARTIALLY APPROVED | JHINDMAN |
| Note: Inspection Resulted at 1/9/2014 2:08:55 PM ATTIC SCREWS | |||
| MONOLITHIC SLAB | 11/01/2013 | APPROVED | RMARVEL |
| Note: THIS IS A REINSPECTION | |||
| MONOLITHIC SLAB | 10/31/2013 | Disapproved -FEE REQUIRED | RMARVEL |
| Note: Inspection Resulted at 10/31/2013 2:55:18 PM NOT READY. WORK IN PROGRESS. | |||
| ELECTRIC 1ST ROUGH | 10/31/2013 | APPROVED | RMARVEL |
| Note: Inspection Resulted at 10/31/2013 2:55:17 PM UFER | |||
| PLUMBING 1ST ROUGH | 10/28/2013 | APPROVED | CMINI |
Review History
| Department | Status | Date In | Date Out |
| BLD | COMPLETE | 02/10/2014 | 02/10/2014 |
| Note: Revisions 5 and 6. | |||
| ELEC | COMPLETE | 02/10/2014 | 02/10/2014 |
| FI1 | COMPLETE | 02/10/2014 | 02/10/2014 |
| PLUM | COMPLETE | 02/10/2014 | 02/10/2014 |
| Note: Revision - Changed sanitary riser diagram, sheet P3.3b, rev. 5. | |||
| BLD | COMPLETE | 12/30/2013 | 12/31/2013 |
| FI1 | COMPLETE | 12/30/2013 | 12/30/2013 |
| Note: Released By: JHINDMAN | |||
| ELEC | COMPLETE | 12/11/2013 | 12/12/2013 |
| FI1 | HOLD | 12/11/2013 | 12/12/2013 |
| Note: . According to the manufacturers specifications, Flame control No 20-20a (under new surfaces) states that No 20-20a will not give a fire resistive rating on metal surfaces. 2. The primer must also be compatible with the fire retardant. 2010 FBC 709.4.1.1 | |||
| MECH | COMPLETE | 12/11/2013 | 12/12/2013 |
| Note: Revision 4 dated 11-18-13. | |||
| PLUM | COMPLETE | 12/11/2013 | 12/12/2013 |
| Note: Revision 4 dated 11-18-13. | |||
| BLD | COMPLETE | 11/19/2013 | 12/13/2013 |
| BLD | COMPLETE | 11/14/2013 | 11/14/2013 |
| Note: Released By: JMCGOWEN revision, letter from D.P.O.R. on stud spacing | |||
| BLD | HOLD | 11/14/2013 | 11/15/2013 |
| Note: Divide plans into building types that corresponds with the associate permits FBC 107.2.1 | |||
| BLD | HOLD | 11/08/2013 | 11/08/2013 |
| Note: Held By: JHINDMAN 1. Provide a complete structural drawing for the header changes that is suitable for review, construction and inspection. 2010 FBC 107.2.1. | |||
| BLD | HOLD | 11/08/2013 | 11/08/2013 |
| Note: Held By: JHINDMAN 1. Provide a complete structural drawing for the header changes that is suitable for review, construction and inspection. 2010 FBC 107.2.1. | |||
| BLD | HOLD | 11/06/2013 | 11/06/2013 |
| Note: Held By: JHINDMAN 1. Provide clarification for the uplift value and the number of screws and that are required per stud to plate connection. 2010 FBC 107.2.1 | |||
| BLD | COMPLETE | 09/30/2013 | 09/30/2013 |
| BLD | HOLD | 09/23/2013 | 09/24/2013 |
| Note: 1. Provide signed and sealed drawings per 2010 FBC 107.1. | |||
| BLD | COMPLETE | 08/22/2013 | 08/22/2013 |
| FI1 | COMPLETE | 08/22/2013 | 08/22/2013 |
| ZON | COMPLETE | 08/22/2013 | 08/22/2013 |
| FI1 | HOLD | 08/08/2013 | 08/08/2013 |
| Note: Provide a Maltese Cross with a RF designation per 2010 F.A.C. 69 A. | |||
| ZON | HOLD | 08/08/2013 | 08/08/2013 |
| Note: 1. Although the Area and Height Limitation table on Sheet A1.0 was revised, it appears that the area called out (3,687 square feet) only represents the 1st floor of the building, inclusive of the riser closet and tenant separation space. Please revise the table to reflect the total building area of 6,671 square feet. 2. The revised sheet A6.4 shows that the side elevation dimension is 51 ft-6 in. from the front face of the garages to the outer limit of the column at the rear patio. The color elevations approved with the Development Order show that same dimension at 51 ft-2 in. Please revise the plans so that the dimension matches the approved color elevations incorporated into the Development Order. As an alternative, a modification can be made to the Development Order by submitting a new color elevation with the corrected dimension consistent with the dimension shown on the elevations in the Building Permit set. | |||
| BLD | HOLD | 08/08/2013 | 08/08/2013 |
| Note: Provide roof and floor truss engineering per 2010 FBC 107.3.5. | |||
| BLD | HOLD | 07/09/2013 | 07/11/2013 |
| Note: Held By: JHINDMAN 1. Provide roof and floor truss engineering per 2010 FBC 107.3.5. | |||
| ELEC | COMPLETE | 07/09/2013 | 07/10/2013 |
| ENGIN1 | COMPLETE | 07/09/2013 | 07/11/2013 |
| FI1 | HOLD | 07/09/2013 | 07/11/2013 |
| Note: 1. Provide a Maltese Cross with a RF designation per F.A.C.69A. | |||
| MECH | COMPLETE | 07/09/2013 | 07/10/2013 |
| PLLA | COMPLETE | 07/09/2013 | 07/10/2013 |
| PLUM | COMPLETE | 07/09/2013 | 07/10/2013 |
| UD1 | COMPLETE | 07/09/2013 | 07/11/2013 |
| Note: Released By: CJOHNSON | |||
| BLD | HOLD | 05/10/2013 | 05/13/2013 |
| Note: Held By: FREODICA 1. Provide specific plans and details applicable to this permit application per 2010 FBC 107.2.1. | |||
| ZON | HOLD | 05/10/2013 | 07/16/2013 |
| Note: 1. On Sheet A0.2a, there are inconsistencies in the building area data when the two provided tables are compared to each other. One table states that the 1st floor A/C area per unit is 560 SF, and the 1st floor non-A/C area (garage and porches) is 359 SF for a total of 919 SF of Non-A/C area. 919 SF x 4 units is 3676 SF, but the second table shows 3687 SF gross. Also, the total gross area per unit on one table is 1665 SF and 1665 SF x 4 units is 6660 SF, but the second table GSF is stated as 6671 SF. Please revise the data tables so that the building areas expressed on them are consistent with each other. 2. On Sheet A1.0, the Area and Height Limitation Table makes references to the 1-Story Villa buildings. Please revise the table so that all references and data correspond to the Townhouse style buildings. 3. On Sheet A1.0, the reference plan or key plan showing the building locations incorrectly labels Building 15 as a “CCCCCC” type building and the callout is “greyed” out. Please revise to show Building 15 as a “CCCC” type building and show the callout in black. 4. Please revise the TH-4 Area Calculations on Sheets A2.4a and A2.4b to be consistent with the area calculations (once revised) found on Sheet A0.2a. The Non-A/C area found on sheet A0.2a is stated as 359 SF, and 359 SF x 4 units is 1436 SF, not 1447 SF. Also, the total GSF appears to be 6660 SF. 5. Please revise the plans to state that all metal roof fasteners must be color matched to the roof panels. 6. Please revise the plans to provide screen porch elevations detailing the materials to be used on the screen enclosures, including any kickplates if applicable. 7. Please revise sheet A6.4 to include the length and width dimensions of the buildings, which should match the previously approved elevations in the Development Order approval. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 04/01/2014 |
| REINSPECTION FEE | ¤40.00 | 04/01/2014 |
| REVISION | ¤40.00 | 04/01/2014 |
| REVISION | ¤40.00 | 04/01/2014 |
| REVISION | ¤40.00 | 04/01/2014 |
| REVISION | ¤40.00 | 04/01/2014 |
| REVISION | ¤40.00 | 04/01/2014 |
| REVISION | ¤40.00 | 04/01/2014 |
| REVISION | ¤40.00 | 04/01/2014 |
| REVISION | ¤40.00 | 04/01/2014 |
| REVISION | ¤40.00 | 04/01/2014 |
| REVISION | ¤40.00 | 04/01/2014 |
| REVISION | ¤40.00 | 04/01/2014 |
| REVISION | ¤40.00 | 04/01/2014 |
| REVISION | ¤40.00 | 04/01/2014 |
| IMPACT FEE FIRE NONRESIDENTIAL | ¤831.96 | 04/01/2014 |
| IMPACT FEE PARKS | ¤5,375.92 | 04/01/2014 |
| IMPACT FEE SCHOOL | ¤3,724.00 | 04/01/2014 |
| IMPACT FEE TRANSPORTATION | ¤10,862.40 | 04/01/2014 |
| INSPECTION FEE 20 | ¤20.00 | 04/01/2014 |
| ADDITIONAL FEE | ¤200.00 | 02/10/2014 |
| ADMIN COMMERCIAL | ¤60.00 | 10/11/2013 |
| ELECTRIC FEE | ¤426.60 | 10/11/2013 |
| MECHANICAL FEE | ¤426.60 | 10/11/2013 |
| PERMIT FEE | ¤3,360.50 | 10/11/2013 |
| PLAN CHECK FEE | ¤702.65 | 10/11/2013 |
| PLUMBING FEE | ¤426.60 | 10/11/2013 |
| FIRE PLANS REVIEW | ¤66.60 | 10/11/2013 |
| SURCHARGE FS 533.721 | ¤81.05 | 10/11/2013 |
| SURCHARGE - FS 468.631 | ¤81.05 | 10/11/2013 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤27,245.93 |