Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 06/10/2013
NOC: Unknown
Applicant name: MICHAEL J LILLY
Owner: CHRIST THE KING EVANGELICAL LUTHERAN CHURCH AND

Address

17 PINE CIRCLE DR

PALM COAST, FL 32164

Address

PRESCHOOL (WELS) INC

PALM COAST, FL 32164

Lot: 0010
Contracted Stated Job Value: ¤12,000.00
Job Description: DRYWALL, INSULATION ELECTRICAL-SPLIT POWER SWITCHES
Type: CN

Contractor

SERVPRO OF FLAGLER COUNTY
Status Location Address State License Number Phone Fax
INACTIVE

2205 DOBBS ROAD

BUNNELL, FL 32110

CGC1514660 (Exp: 08/31/2024) 904-429-4457 386-206-2188

Sub Contractors

JOHN FREDERICK WANERKA JR
Status Location Address State License Number Phone Fax
CANCEL

P.O. BOX 350214

BUNNELL, FL 32110

EC13003318 (Exp: 08/31/2022) (386)446-9626 (386)445-3131

Inspection History

Type Request Date Result Inspector
BUILDING FINAL 05/06/2014 FINAL APPROVED RMARVEL
Note: THIS IS A REINSPECTION
BUILDING FINAL 12/31/2013 Disapproved -FEE REQUIRED CMINI
Note: THIS IS A REINSPECTION Inspection Resulted at 12/31/2013 3:29:50 PM NO ACCESS INTO BUILDING FOR INSPECTION
ELECTRIC FINAL 12/31/2013 Disapproved - NO FEE CMINI
Note: THIS IS A REINSPECTION Inspection Resulted at 12/31/2013 3:29:49 PM NO ACCESS INTO BUILDING FOR INSPECTION
ELECTRIC FINAL 12/30/2013 CANCELLED BY APPLICANT AIRS WEB
Note: THIS IS A REINSPECTION
BUILDING FINAL 12/30/2013 CANCELLED BY APPLICANT AIRS WEB
Note: THIS IS A REINSPECTION
BUILDING FINAL 12/26/2013 CANCELLED BY APPLICANT AIRS WEB
Note: THIS IS A REINSPECTION
BUILDING FINAL 12/26/2013 CANCELLED BY APPLICANT AIRS WEB
Note: THIS IS A REINSPECTION
ELECTRIC FINAL 12/26/2013 CANCELLED BY APPLICANT AIRS WEB
Note: THIS IS A REINSPECTION
FRAMING 12/11/2013 CANCELLED BY APPLICANT AIRS WEB
BUILDING FINAL 06/26/2013 Disapproved - NO FEE RMARVEL
Note: Inspection Resulted at 6/26/2013 2:46:02 PM UNABLE TO FINAL DUE TO OUTSTANDING ELECTRICAL INSPECTION.
ELECTRIC FINAL 06/26/2013 Disapproved -FEE REQUIRED RMARVEL
Note: Inspection Resulted at 6/26/2013 2:46:01 PM NEC 2008 314.21- REPAIR DRYWALL WHERE MORE THAN 1/8IN GAP AROUND THE BOX.
ELECTRIC 2ND ROUGH 06/18/2013 APPROVED CMINI
Note: THIS IS A REINSPECTION
FRAMING 06/18/2013 APPROVED - AS NOTED CMINI
Note: THIS IS A REINSPECTION Inspection Resulted at 6/18/2013 3:21:07 PM PLEASE BRING BACK COPY OF REVISION TO HAVE STAMP PUT ON
FRAMING 06/14/2013 Disapproved -FEE REQUIRED RMARVEL
Note: THIS IS A REINSPECTION Inspection Resulted at 6/14/2013 2:48:23 PM ENGINEERED PLANS NEED TO BE SUBMITTED TO CITY, STAMPED BY CITY, AND PLACED ON SITE FOR INSPECTION.
ELECTRIC 2ND ROUGH 06/14/2013 Disapproved -FEE REQUIRED RMARVEL
Note: THIS IS A REINSPECTION Inspection Resulted at 6/14/2013 2:48:22 PM OVER ON BOXFILL.BOX FILL FOR ELECTRICAL. NEC 2008 TABLES 314.16(A) AND (B)
ELECTRIC 2ND ROUGH 06/12/2013 Disapproved -FEE REQUIRED RMARVEL
Note: THIS IS A REINSPECTION over on box fill. NEC 2008 table 314.
FRAMING 06/12/2013 Disapproved -FEE REQUIRED RMARVEL
Note: THIS IS A REINSPECTION Inspection Resulted at 6/12/2013 3:02:04 PM WALL IS NOT BUILT TO APPROVED SET OF PLANS.
ELECTRIC 2ND ROUGH 06/11/2013 Disapproved -FEE REQUIRED CMINI
Note: Inspection Resulted at 6/11/2013 2:36:57 PM NEED TO HAVE FULL SET OF PLANS ON JOB SITE. FBC 107.3.NEED TO FIRECAULK PENATRATIONS AT TOP PLATE..PER PLAN
FRAMING 06/11/2013 Disapproved -FEE REQUIRED CMINI
Note: Inspection Resulted at 6/11/2013 2:36:56 PM NEED TO HAVE FULL SET OF PLANS ON JOB SITE. FBC 107.3.NEED TO FIRECAULK PENATRATIONS AT TOP PLATE..PER PLAN

Review History

Department Status Date In Date Out
BLD COMPLETE 06/13/2013 06/13/2013
BLD COMPLETE 06/07/2013 06/07/2013
ELEC COMPLETE 06/07/2013 06/07/2013
FI1 COMPLETE 06/04/2013 06/04/2013
ELEC HOLD 06/04/2013 06/05/2013
Note: Provide electrician’s license number and qualifiers name on proposed electric drawing FBC 107.1
BLD HOLD 05/28/2013 05/29/2013
Note: Held by J. Hindman. 1. Provide a complete plan including wall sections, dimensions, the layout of the building, means of egress. The plans must be suitable for review, construction and inspection per 2010 FBC 107.2.1.
ELEC HOLD 05/28/2013 05/29/2013
Note: Provide drawing to show all added or deleted outlets and locations FBC 107.2.1
FI1 HOLD 05/28/2013 05/29/2013
Note: Held by J.Hindman 1. Provide a life safety plan suitable for review, construction and inspection.
SW1 COMPLETE 05/28/2013 05/30/2013
UD1 COMPLETE 05/28/2013 05/29/2013
ZON COMPLETE 05/28/2013 06/03/2013
Note: No zoning review required.

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADMIN COMMERCIAL ¤60.00 06/10/2013
INSPECTION - COMMERCIAL ADD ¤84.00 06/10/2013
ELECTRIC FEE ¤67.20 06/10/2013
FIRE PLANS REVIEW ¤25.00 06/10/2013
PLAN CHECK FEE ¤100.00 06/10/2013
SITE PLAN 20 ¤20.00 06/10/2013
SURCHARGE FS 533.721 ¤4.67 06/10/2013
SURCHARGE - FS 468.631 ¤4.67 06/10/2013
REINSPECTION FEE ¤40.00
REINSPECTION FEE ¤40.00
REINSPECTION FEE ¤40.00
REINSPECTION FEE ¤40.00
REINSPECTION FEE ¤40.00
REINSPECTION FEE ¤40.00
REINSPECTION FEE ¤40.00
REINSPECTION FEE ¤40.00
REVISION ¤40.00
Fees Total Due: ¤360.00 Total Paid: ¤365.54