Permit #2013070457

Permit Details

Status: COED

Parcel Id: 18-11-31-0000-02010-0070
Block: 02010
Subdivision: -
Job Phone: (386) 445-4350
Location Address: 5 UTILITY DR
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 08/12/2013
NOC: RECORDED
Applicant name: MICHAEL GLEN MACHIN
Owner: JAYME FERNANDES

Address

8 BOWMAN PLACE

PALM COAST, FL 32137

Lot: 0070
Contracted Stated Job Value: ¤45,000.00
Job Description: UNITS 23 - 27 INDOOR SOCCER FIELD-- "INDOOR REVOLUTION INC."
Type: CN

Contractor

MACHIN CONSTRUCTION CO
Status Location Address State License Number Phone Fax
INACTIVE

3 HARGROVE GRADE SUITE 1

Palm Coast, FL 32137

CGC058789 (Exp: 08/31/2024) (386) 445-4350 (386)446-5459

Sub Contractors

STEVEN DUANE DENSLOW
Status Location Address State License Number Phone Fax
ACTIVE

317 RIO PINR DR

Ormond Beach, FL 32174

EC0001678 (Exp: 08/31/2026) 386-233-1553 386-673-5994
DANIEL P HUCKS
Status Location Address State License Number Phone Fax
CANCEL

400 N. U.S. 1

Ormond Beach, FL 32174

CAC029376 (Exp: 08/31/2024) 386-672-8494 386-673-7856
JONATHAN M PEARSON
Status Location Address State License Number Phone Fax
ACTIVE

209 N FORSYTH ST

BUNNELL, FL 32110

CFC1425941 (Exp: 08/31/2026) 386-597-0944 386-437-4996

Inspection History

Type Request Date Result Inspector
BUILDING FINAL 02/07/2014 FINAL APPROVED JHINDMAN
Note: THIS IS A REINSPECTION
FIRE FINAL 02/07/2014 APPROVED JHINDMAN
Note: THIS IS A REINSPECTION
U - UTILITY COMMERCIAL FINAL 12/19/2013 FINAL APPROVED DSPENCER
FIRE FINAL 12/19/2013 CANCELLED BY APPLICANT JHINDMAN
BUILDING FINAL 12/19/2013 CANCELLED BY APPLICANT JHINDMAN
ELECTRIC FINAL 12/12/2013 APPROVED RMARVEL
Note: THIS IS A REINSPECTION
ELECTRIC FINAL 12/10/2013 Disapproved -FEE REQUIRED CMINI
Note: Inspection Resulted at 12/10/2013 3:35:37 PM PANEL SCHEDULES DO NOT MATCH PLAN..NEED TO REMOVE UNUSED WHIP TO DISCONNECT
PLUMBING FINAL 11/22/2013 APPROVED CMINI
HVAC ROUGH 11/22/2013 APPROVED CMINI
HVAC FINAL 11/22/2013 APPROVED CMINI
ABOVE CEILING 11/22/2013 APPROVED CMINI
FRAMING 09/25/2013 APPROVED RMARVEL
Note: THIS IS A REINSPECTION
PLUMBING 2ND ROUGH 09/25/2013 APPROVED RMARVEL
Note: THIS IS A REINSPECTION
ELECTRIC 2ND ROUGH 09/25/2013 APPROVED RMARVEL
Note: THIS IS A REINSPECTION
ELECTRIC 2ND ROUGH 09/24/2013 Disapproved - NO FEE RMARVEL
Note: Inspection Resulted at 9/24/2013 2:49:59 PM APPROVED CITY STAMPED PLANS NEED TO BE ON SITE FOR INSPECTION.
PLUMBING 2ND ROUGH 09/24/2013 Disapproved -FEE REQUIRED RMARVEL
Note: Inspection Resulted at 9/24/2013 2:49:58 PM APPROVED CITY STAMPED PLANS NEED TO BE ON SITE FOR INSPECTION.
FRAMING 09/24/2013 Disapproved - NO FEE RMARVEL
Note: Inspection Resulted at 9/24/2013 2:50:00 PM APPROVED CITY STAMPED PLANS NEED TO BE ON SITE FOR INSPECTION.
FIREWALL NAILING 09/19/2013 CANCELLED BY INSPECTOR CMINI
Note: PARTIAL DRYWALL SOUTH WALL Inspection Resulted at 9/19/2013 3:09:21 PM NO DRYWALL INSPECTION NEEDED IN PALM COAST
MONOLITHIC SLAB 09/16/2013 APPROVED JHINDMAN
ELECTRIC 2ND ROUGH 09/13/2013 APPROVED RMARVEL
EXTERIOR WALL SHEATHING / SHEARWALL 09/13/2013 APPROVED RMARVEL
PLUMBING 1ST ROUGH 09/12/2013 APPROVED RMARVEL
Note: THIS IS A REINSPECTION
FRAMING 09/12/2013 APPROVED RMARVEL
PLUMBING 1ST ROUGH 09/11/2013 Disapproved -FEE REQUIRED RMARVEL
Note: THIS IS A REINSPECTION ok to add per LARRY W Inspection Resulted at 9/11/2013 2:01:50 PM FPC 2010 605.17 PROVIDE MANUFACTURERS SPECIFICATIONS SHOWING PEX TUBING JOINTS ARE RATED FOR UNDERGROUND USE.
PLUMBING 1ST ROUGH 09/10/2013 CANCELLED BY APPLICANT AIRS WEB
Note: THIS IS A REINSPECTION
FRAMING 09/10/2013 CANCELLED BY APPLICANT AIRS WEB
PLUMBING 1ST ROUGH 08/30/2013 Disapproved -FEE REQUIRED CMINI
Note: Inspection Resulted at 8/30/2013 3:09:17 PM NEED REVISION SHOWING USE OF PEX TUBING FBC 107.1.2

Review History

Department Status Date In Date Out
ELEC COMPLETE 12/11/2013 12/11/2013
ELEC COMPLETE 12/06/2013 12/06/2013
ELEC HOLD 10/31/2013 10/31/2013
Note: Recalculate all service entrance conductor sizes using the adjustment factors for more than three current-carrying conductors per NEC table 310.15 B 2 a
PLUM COMPLETE 09/10/2013 09/10/2013
PLUM HOLD 09/09/2013 09/09/2013
Note: Provide an original signed and sealed letter of revision FBC 107.1
ELEC COMPLETE 08/08/2013 08/08/2013
BLD COMPLETE 08/08/2013 08/08/2013
MECH COMPLETE 08/08/2013 08/08/2013
BLD HOLD 07/19/2013 07/22/2013
Note: 1. Provide details for the new openings in the concrete block wall. 2010 FBC 107.2.1.
ELEC HOLD 07/19/2013 07/22/2013
Note: Revise ground conductor to meet NEC 250.66 provide service load calculations FBC 107.2.1
FI1 COMPLETE 07/19/2013 07/22/2013
MECH HOLD 07/19/2013 07/22/2013
Note: 1. Provide manufacturer specifications and installation instructions of the wall mounted hvac units per 2010 FBC 107.2.1. 2. Provide calculation of minimum outdoor air requirement for both existing hvac supplying spectator area and new hvac supplying soccer field area per 2010 FBC 403.2.
PLUM COMPLETE 07/19/2013 07/22/2013
SW1 COMPLETE 07/19/2013 07/23/2013
UD1 COMPLETE 07/19/2013 07/29/2013
ZON COMPLETE 07/19/2013 07/22/2013

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION FEE ¤40.00 01/24/2014
REINSPECTION FEE ¤40.00 01/24/2014
REINSPECTION FEE ¤40.00 01/24/2014
REINSPECTION FEE ¤40.00 01/24/2014
REVISION ¤40.00 01/24/2014
REVISION ¤40.00 01/24/2014
REVISION ¤40.00 01/24/2014
SITE PLAN 20 ¤20.00 08/12/2013
SURCHARGE FS 533.721 ¤11.04 08/12/2013
SURCHARGE - FS 468.631 ¤11.04 08/12/2013
ADMIN COMMERCIAL ¤60.00 08/12/2013
INSPECTION - COMMERCIAL ADD ¤315.00 08/12/2013
ELECTRIC FEE ¤87.00 08/12/2013
FIRE PLANS REVIEW ¤25.00 08/12/2013
MECHANICAL FEE ¤87.00 08/12/2013
PLAN CHECK FEE ¤100.00 08/12/2013
PLUMBING FEE ¤87.00 08/12/2013
Fees Total Due: ¤0.00 Total Paid: ¤1,083.08