I want to search for...

Permit #2013080671

Permit Details

Status: FINAL

Parcel Id: 07-11-31-7001-000B0-014A
Block: 000B0
Subdivision: 1238 - PALM HARBOR CENTER REPLAT
Job Phone: (386) 445-2222
Location Address: 10 FLORIDA PARK DR
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 09/12/2013
NOC: RECORDED
Applicant name: MICHAEL STEPHAN MULLEN
Owner: ECSA PROPERTIES LC

Address

1400 US HIGHWAY 1 S

ST. AUGUSTINE, FL 32084

Lot: 014A
Contracted Stated Job Value: ¤30,000.00
Job Description: REPAIR WATER DAMAGE ON EXTERIOR WALLS, INSTALL AC SYSTEM "EYE CENTER OF ST. AUGUSTINE"
Type: CN

Contractor

TOWN & COUNTRY HOMES
Status Location Address State License Number Phone
ACTIVE

1 Enterprise Drive

Bunnell, FL 32110

CGC049972 (Exp: 08/31/2026) (386) 445-2222

Sub Contractors

WILLIAM FRANK DUDLEY JR.
Status Location Address State License Number Phone
ACTIVE

P.O. BOX 978

Bunnell, FL 32110

EC0003177 (Exp: 08/31/2026) (386)437-3068
DANIEL P HUCKS
Status Location Address State License Number Phone Fax
CANCEL

400 N. U.S. 1

Ormond Beach, FL 32174

CAC029376 (Exp: 08/31/2024) 386-672-8494 386-673-7856

Inspection History

Type Request Date Result Inspector
FINAL 09/17/2013 FINAL APPROVED JHINDMAN
FIRE FINAL 09/17/2013 APPROVED JHINDMAN
U - UTILITY COMMERCIAL FINAL 09/17/2013 APPROVED DSPENCER
HVAC ROUGH 09/16/2013 APPROVED CMINI
HVAC FINAL 09/16/2013 APPROVED CMINI
LATH/BRICK/WATER BARRIER 09/16/2013 APPROVED CMINI

Review History

Department Status Date In Date Out
BLD COMPLETE 09/11/2013 09/11/2013
MECH COMPLETE 09/11/2013 09/11/2013
BLD HOLD 09/03/2013 09/03/2013
Note: 1. Provide an explaination of how the stucco is to be bonded to waterproofing and still comply with ASTM C926 and 2010 FBC 2510.
MECH HOLD 09/03/2013 09/04/2013
Note: Provide required informations on hvac plan per 2010 FBC 107.2.1. 1. Distributed supply air in CFM(s). 2. Duct sizes of brach duct tied into the main supply. 3. Return air from each individual room to the hvac unit. 4. Clarify duct sizes, CFM, penetration of supply/return at storage area. 5. Duct material specification, support detail, and condensate discharge.
ZON COMPLETE 09/03/2013 09/06/2013
ELEC COMPLETE 08/28/2013 09/03/2013
MECH HOLD 08/28/2013 08/29/2013
Note: Provide hvac plan, energy calculation including sizing of units, proposed location of hvac unit and existing capacity in tons per 2010 FBC 107.3.5.
BLD HOLD 08/28/2013 08/28/2013
Note: 1. Provide a stucco detail that complies with ASTM C 926 for application.
ZON HOLD 08/28/2013 08/31/2013
Note: Provide a note on the construction sheets to state that all exterior work (material and color) shall match that of the existing building.

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADMIN COMMERCIAL ¤60.00 09/12/2013
INSPECTION - COMMERCIAL ADD ¤210.00 09/12/2013
ELECTRIC FEE ¤78.00 09/12/2013
FIRE PLANS REVIEW ¤25.00 09/12/2013
MECHANICAL FEE ¤78.00 09/12/2013
PLAN CHECK FEE ¤100.00 09/12/2013
SITE PLAN 20 ¤20.00 09/12/2013
SURCHARGE FS 533.721 ¤7.89 09/12/2013
SURCHARGE - FS 468.631 ¤7.89 09/12/2013
Fees Total Due: ¤0.00 Total Paid: ¤586.78