Permit #2014010215

Permit Details

Status: COED

Parcel Id: 14-11-30-5540-00000-00D0
Block: 00000
Subdivision: 1188 - ST JOE PLAZA AT PC
Job Phone: (386)931-1917
Location Address: 300 PALM COAST PKWY SW
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 04/17/2014
NOC: RECORDED
Applicant name: BRAD MICHAEL THOMAS
Owner: DOMENECH, ALBERTO

Address

300 PALM CAST PKWY

PALM COAST, FL 32164

Lot: 00D0
Contracted Stated Job Value: ¤7,000.00
Job Description: UNIT 1-4 INTERIOR REMODEL- LATINO MARKET & BAKERY
Type: CN

Contractor

AUBURN HOMES INC.
Status Location Address State License Number Phone
HOLD

1 HARGROVE GRADE STE 1E

PALM COAST, FL 32137

CGC1506292 (Exp: 08/31/2020) (386)931-1917

Sub Contractors

HEATH EDWARD SANFORD
Status Location Address State License Number Phone Fax
ACTIVE

1351 HAZELNUT ST

BUNNELL, FL 32110

CFC1427527 (Exp: 08/31/2026) 386-445-2532 386-445-5575
JOHN EDWARD GAMBONE
Status Location Address State License Number Phone Fax
CANCEL

55 BARRISTER LN

PALM COAST, FL 32137

ER13013466 (Exp: 08/31/2014) 386-586-9144 (386)246-6305
GARY LLOYD SHEFFIELD
Status Location Address State License Number Phone Fax
CANCEL

2 HARGROVE GRADE

PALM COAST, FL 32136

CAC048127 (Exp: 08/31/2018) 386-445-5023 386-446-4614

Inspection History

Type Request Date Result Inspector
BUILDING FINAL 06/26/2014 FINAL APPROVED JHINDMAN
Note: THIS IS A REINSPECTION
FIRE FINAL 06/26/2014 APPROVED JHINDMAN
Note: THIS IS A REINSPECTION
FIRE FINAL 06/16/2014 Disapproved -FEE REQUIRED JHINDMAN
Note: THIS IS A REINSPECTION Inspection Resulted at 6/16/2014 12:53:24 PM 1. THE BOOTHS AND NUMBER OF SEATS DOES NOT MATCH THE APPROVED PLANS.
BUILDING FINAL 06/16/2014 Disapproved - NO FEE JHINDMAN
Note: THIS IS A REINSPECTION Inspection Resulted at 6/16/2014 12:53:24 PM THE BOOTHS AND NUMBER OF SEATS DO NOT MATCH THE APPROVED PLANS. 2010 FBC 107.2.1.
BUILDING FINAL 06/10/2014 Disapproved -FEE REQUIRED JHINDMAN
Note: Inspection Resulted at 6/10/2014 2:51:05 PM 1. PROVIDE PANIC HARDWARE ON THE EXTERIOR DOORS PER PLANS AND 2010 FBC 1008.1.10.
FIRE FINAL 06/10/2014 Disapproved -FEE REQUIRED JHINDMAN
Note: Inspection Resulted at 6/10/2014 2:51:07 PM 1. THE FIXTURES AND THE BOOTHS MUST MATCH THE LIFESAFETY PLAN.
U - UTILITY COMMERCIAL FINAL 06/10/2014 FINAL APPROVED DSPENCER
ELECTRIC FINAL 06/05/2014 APPROVED RMARVEL
ABOVE CEILING 06/05/2014 APPROVED RMARVEL
PLUMBING FINAL 06/05/2014 APPROVED RMARVEL
PLUMBING 2ND ROUGH 05/20/2014 APPROVED RMARVEL
HVAC FINAL 05/20/2014 APPROVED RMARVEL
HVAC ROUGH 05/16/2014 APPROVED RMARVEL
Note: THIS IS A REINSPECTION
MONOLITHIC SLAB 05/16/2014 APPROVED RMARVEL
ELECTRIC 2ND ROUGH 05/14/2014 APPROVED RMARVEL
Note: THIS IS A REINSPECTION
ELECTRIC 2ND ROUGH 05/13/2014 CANCELLED BY APPLICANT CMINI
Note: THIS IS A REINSPECTION
PLUMBING 1ST ROUGH 05/13/2014 APPROVED CMINI
Note: per contractor
HVAC ROUGH 05/07/2014 Disapproved -FEE REQUIRED CMINI
Note: Inspection Resulted at 5/7/2014 3:38:21 PM MECHANCAL PLANS SHOWING RELOCATIONS OF SUPPLIES ON ONE PLAN BUT NOT SEEING RELOCATED SUPPLIES,ON OTHER PLAN SHOWING ADDING ONE TO OUTSIDE AND EXISTING WHICH EXISTING DOES NOT MATCH WHAT HERE..NEED CORRECTION TO PLAN
ELECTRIC 2ND ROUGH 05/07/2014 Disapproved -FEE REQUIRED CMINI
Note: Inspection Resulted at 5/7/2014 3:38:21 PM OULET MOVED FROM EXISTING SPOT SHOWING ON PLAN TO NEW WALL IN CORRIDOR NEEDS TO BE EXPOSED FOR INSPECTION AS WELL AS NEW SWITCH IN WALL HAS BEEN COVERED BY DRYWALL,AND SHALL NOT HAVE POWER TO IT BEFORE IT IS INSPECTED,SWICTH GROUND SCREW NOT CONNECTED ALSO
FRAMING 05/02/2014 APPROVED CMINI

Review History

Department Status Date In Date Out
ELEC COMPLETE 05/14/2014 05/14/2014
MECH COMPLETE 05/14/2014 05/14/2014
PLUM COMPLETE 04/17/2014 04/17/2014
MECH COMPLETE 04/17/2014 04/17/2014
MECH COMPLETE 04/17/2014 04/17/2014
Note: Released By: FREODICA answering holds
ELEC COMPLETE 04/08/2014 04/08/2014
PLUM HOLD 04/08/2014 04/08/2014
Note: Previous comment item 2 shall be addressed. 2. Provide vent for new lavatories per 2010 FBC P 901.2. F. Reodica -386-986-4734
FI1 COMPLETE 04/08/2014 04/08/2014
BLD COMPLETE 04/08/2014 04/08/2014
MECH HOLD 04/08/2014 04/08/2014
Note: 1. Provide outdoor air duct layout including duct size and CFM(s) which is missing on submitted hvac plan per 2010 FBC 107.3.5. 2. Total cooling capacity and latent capacity of hvac units is less than total calculated cooling load and latent load. Verify to comply with 2010 FBCEC 503.2. 3. Provide the location of condenser unit per 2010 FBC 107.3.5. F.Reodica-386-986-4734
BLD HOLD 01/13/2014 01/14/2014
Note: 1. Provide coordinated plans. The Life Safety plan does not match the floor plan. 2010 FBC 107.2.1. 2. Provide dimensions on the Life Safety plan. 2010 FBC 107.2.1. 3. The storage areas must be totally separated from the Assembly occupancy. 2010 FBC 302.1. 4. Provide ADA maneuvering space at the new front door corridor per 2010 FBC Accessibility 404.2.4. 5. Provide a correct occupant load. The fractions must be rounded up. 2010 FBC 1004 6. Based on non-separated mixed use all shared occupancy areas that are used for both the restaurant customers, restaurant staff and mercantile customers must be used in the Assembly occupant load count. 2010 FBC 302.1. 7. The occupant load based on the life safety plan after all of the above corrections are made will require a fire sprinkler system. 2010 FBC 903.2.1.2
ELEC HOLD 01/13/2014 01/13/2014
Note: Provide electric load calculations, panel schedule and existing service size and provide electric contractor doing the work ,verify working space at electric panel NEC article 220, 110.26 and FBC 107.3.5
FI1 HOLD 01/13/2014 01/14/2014
Note: 1. Provide coordinated plans. The Life Safety plan does not match the floor plan. 2. Provide dimensions on the Life Safety plan. 3. Provide a correct occupant load. The fractions must be rounded up. 2010 FFPC 7.3.1.2. 4. Based on non-separated mixed use all shared occupancy areas that are used for both the restaurant customers, restaurant staff and mercantile customers must be used in the Assembly occupant load count. 2010 FFPC 6.1.14.1.3. 5. The exit corridor at the new front entry must have a 2 hour rating per 2010 FFPC 7.1.3.1. 6. Provide an exit and emergency light at the inside front door at the exit corridor. 2010 FFPC 709.1. 7. The floor area in front of the exit corridor must be included in the Assembly load calculation. 2010 FFPC7.3.1.2. 8. The occupant load based on the life safety plan after all of the above corrections are made will require a fire sprinkler system. 2010 FFPC12.3.5.1.
MECH HOLD 01/13/2014 01/14/2014
Note: 1. Provide hvac plan for comprehensive review due to changed in occupancy classification per 2010 FBC Existing Building 909. 2. Provide energy calculations per 2010 FBC 107.3.5. 3. Provide minimum ventilation requirements per 2010 FBC M 403. 4. Provide hvac contractor doing the work per FS 489. 5. Provide cooler specifications and manufacturer installation instructions per 2010 FBC 107.2.1. 6. Provide service sink (additional plumbing comment) per 2010 FBCP Table 403.
PLUM HOLD 01/13/2014 01/14/2014
Note: 1. Existing plumbing fixtures ( water closet and lavatory shown on sanitary riser diagram shall be capped off for clarity per 2010 FBC 107.2.1. 2. Provide vent for new lavatories per 2010 FBC P 901.2.
SW1 COMPLETE 01/13/2014 01/13/2014
UD1 COMPLETE 01/13/2014 01/15/2014
ZON HOLD 01/13/2014 01/16/2014
Note: Provide an approved development order for a special exception for a bar, tavern, or club with live entertainment, or revise plans removing platform.
ZON COMPLETE 02/19/2014
Note: Released By: CBENTLEY

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION FEE ¤40.00 06/26/2014
REINSPECTION FEE ¤40.00 06/26/2014
REINSPECTION FEE ¤40.00 06/26/2014
REINSPECTION FEE ¤40.00 06/26/2014
REINSPECTION FEE ¤40.00 06/26/2014
REVISION ¤40.00 06/26/2014
REVISION ¤40.00 06/26/2014
SITE PLAN 20 ¤20.00 04/17/2014
SURCHARGE FS 533.721 ¤5.29 04/17/2014
SURCHARGE - FS 468.631 ¤5.29 04/17/2014
ADMIN COMMERCIAL ¤60.00 04/17/2014
INSPECTION - COMMERCIAL ADD ¤50.00 04/17/2014
ELECTRIC FEE ¤64.20 04/17/2014
FIRE PLANS REVIEW ¤25.00 04/17/2014
MECHANICAL FEE ¤64.20 04/17/2014
PLAN CHECK FEE ¤100.00 04/17/2014
PLUMBING FEE ¤64.20 04/17/2014
Fees Total Due: ¤0.00 Total Paid: ¤738.18