Permit #2014040105
Permit Details
Status: FINAL
| Parcel Id: 14-11-30-5538-00000-0080 |
| Block: 00000 |
| Subdivision: 2130 - St. Joe Corporate Park |
| Job Phone: (386)248-0460 |
| Location Address: 515 PALM COAST PKWY SW |
| Type: FCA - COMMERCIAL FIRE ALARM |
| Issue Date: 04/11/2014 |
| NOC: RECORDED |
| Applicant name: GARY L SMITH |
| Owner: 515 PALM COAST LLC |
|
Address 3920 RCA BLVD STE 2002 PALM BEACH GARDENS, FL 33410 |
| Lot: 0080 |
| Contracted Stated Job Value: ¤12,600.00 |
| Job Description: FIRE ALARM SYSTEM |
| Type: CN |
Contractor
CERTIFIED ELECTRONIC SYSTEMS, INC.
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
1120 A ENTERPRISE COURT HOLLY HILL, FL 32117 |
EF0000139 (Exp: 08/31/2026) | (386)248-0460 | (386)248-2003 |
Inspection History
| Type | Request Date | Result | Inspector |
| FIRE ALARM FINAL | 12/18/2014 | FINAL APPROVED | JHINDMAN |
| Note: THIS IS A REINSPECTION | |||
| FIRE ALARM FINAL | 12/12/2014 | Disapproved -FEE REQUIRED | JHINDMAN |
| Note: 1. horns are missing in the hallways. 2. strobe is not working in library. 3. strobe is not working in hall left of office lobby. 4. heat detector in kitchen was not tested. 5. pull and horn/strobe at outside stairs are missing. 6. sprinklers have not been flow tested. | |||
| FIRE ALARM BATTERY TEST | 12/11/2014 | APPROVED | JHINDMAN |
| FIRE ALARM BATTERY TEST | 12/08/2014 | APPROVED | JHINDMAN |
| Note: THIS IS A REINSPECTION breakers are turned off at 10:40 a.m. | |||
| FIRE ALARM FINAL | 12/05/2014 | CANCELLED BY APPLICANT | AIRS WEB |
| Note: THIS IS A REINSPECTION | |||
| FIRE ALARM FINAL | 12/03/2014 | Disapproved -FEE REQUIRED | JHINDMAN |
| Note: THIS IS A REINSPECTION electric is not locked out. | |||
| FIRE ALARM FINAL | 11/20/2014 | Disapproved -FEE REQUIRED | JHINDMAN |
| Note: THIS IS A REINSPECTION no access to panels | |||
| FIRE ALARM FINAL | 10/28/2014 | Disapproved - NO FEE | JHINDMAN |
| FIRE ALARM BATTERY TEST | 10/28/2014 | Disapproved -FEE REQUIRED | JHINDMAN |
| Note: alarm did not pass the 24 hour test | |||
| FIRE ALARM 1ST ROUGH | 04/15/2014 | APPROVED | JHINDMAN |
| Note: THIS IS A REINSPECTION | |||
| FIRE ALARM 1ST ROUGH | 04/14/2014 | Disapproved -FEE REQUIRED | JHINDMAN |
| Note: Inspection Resulted at 4/14/2014 3:16:26 PM 1. PULL STATION WIRING AT CAFETERIA DOUBLE SIDE DOOR IS NOT INSTALLED. |
Review History
| Department | Status | Date In | Date Out |
| FI1 | COMPLETE | 04/09/2014 | 04/09/2014 |
| FI1 | HOLD | 04/03/2014 | 04/07/2014 |
| Note: 1. The existing 75 cd devices do not provide the proper coverage in the activity rooms 1,2,3,8, library, toddlers 2 and toddlers 3. per NFPA 72 Table 18.5.4.3.1. 2. Provide a horn/strobe in activity room 6. 3. Provide a pull station at the exterior cafeteria side door that is not shown on the plans. per NFPA 72 17.14.6. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 12/17/2014 |
| REINSPECTION FEE | ¤40.00 | 12/04/2014 |
| REINSPECTION FEE | ¤40.00 | 11/24/2014 |
| REINSPECTION FEE | ¤40.00 | 11/03/2014 |
| EXTENSION | ¤40.00 | 10/24/2014 |
| REINSPECTION FEE | ¤40.00 | 04/15/2014 |
| SURCHARGE FS 533.721 | ¤2.00 | 04/11/2014 |
| SURCHARGE - FS 468.631 | ¤2.00 | 04/11/2014 |
| FIRE ALARM | ¤75.00 | 04/11/2014 |
| FIRE PLANS REVIEW | ¤25.00 | 04/11/2014 |
| ADMIN COMMERCIAL | ¤60.00 | 04/11/2014 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤404.00 |