I want to search for...

Permit #2014040199

Permit Details

Status: COED

Parcel Id: 10-11-30-4937-00000-0180
COMMERCIAL SQUARE FOOTAGE: 1880 sqft
Total Square Footage: 1880 sqft
Block: 00000
Subdivision: 2262 - PALM COAST INDUSTRIAL PARK
Job Phone: 386-238-1570
Location Address: 5 HARGROVE GRADE
Type: CA - COMM ADDITION
Issue Date: 05/30/2014
NOC: RECORDED
Applicant name: GARY LYNN ROBERTS
Owner: GIOIA PROPERTIES LLC % VEE SERVICES INC

Address

11700 PRESTON ROAD #660-193

DALLAS, TX 75230

Lot: 0180
Contracted Stated Job Value: ¤86,420.00
Job Description: 1880 SQ FT STORAGE SPACE
Type: CN

Contractor

COMMERCIAL CONSTRUCTION INC.
Status Location Address State License Number Phone Fax
ACTIVE

7 SUNSHINE BLVD

ORMOND BEACH, FL 32174

CGC059441 (Exp: 08/31/2026) 386-238-1570 386-238-1571

Sub Contractors

MIKE F WHALEY
Status Location Address State License Number Phone Fax
ACTIVE

804 Root Street

Daytona Beach, FL 32114

EC0001334 (Exp: 08/31/2026) (386) 252-2287 (386)257-1920
STEVEN KEITH JONES
Status Mailing Address State License Number Phone Fax
ACTIVE

345 MADISON AVE

DAYTONA BEACH, FL 32114

CMC057027 (Exp: 08/31/2026) (386)253-7774 (386)255-9431

Inspection History

Type Request Date Result Inspector
LDSC- LANDSCAPE FINAL 09/24/2014 FINAL APPROVED WBUTLER
U - UTILITY COMMERCIAL FINAL 09/23/2014 FINAL APPROVED DSPENCER
BUILDING FINAL 07/25/2014 APPROVED JHINDMAN
FIRE FINAL 07/25/2014 APPROVED JHINDMAN
ELECTRIC FINAL 07/17/2014 APPROVED RMARVEL
Note: THIS IS A REINSPECTION
ROOF SHEATHING / BRACE / TIE DOWN 07/16/2014 APPROVED RMARVEL
Note: THIS IS A REINSPECTION
ELECTRIC 1ST ROUGH 07/16/2014 APPROVED RMARVEL
Note: THIS IS A REINSPECTION
ELECTRIC 1ST ROUGH 07/15/2014 Disapproved -FEE REQUIRED RMARVEL
Note: THIS IS A REINSPECTION Inspection Resulted at 7/15/2014 1:47:26 PM RECHECK BOXES FOR OVERFILL. I COUNTED 2 DIFFERANT BOXES AND BOTH ARE OVER FILLED. 2008 NEC 314.16
ELECTRIC FINAL 07/11/2014 Disapproved - NO FEE RMARVEL
Note: THIS IS A REINSPECTION Inspection Resulted at 7/11/2014 2:04:07 PM PROVIDE CITY STAMPED APPROVED REVISED PLANS ON SITE FOR INSPECTION. OUTSTANDING ELECTRICAL ROUGH INSPECTION. NOT READY FOR FINAL.
FOOTER 07/11/2014 APPROVED RMARVEL
LINTEL 07/11/2014 APPROVED - AS NOTED RMARVEL
Note: Inspection Resulted at 7/11/2014 8:04:12 AM NO LINTEL INSPECTION NEEDED.
ROOF SHEATHING / BRACE / TIE DOWN 07/11/2014 Disapproved - NO FEE RMARVEL
Note: Inspection Resulted at 7/11/2014 11:03:37 AM PROVIDE SHEETING ANCHOR SCHEDULE FOR INSPECTION.
ELECTRIC 1ST ROUGH 07/11/2014 Disapproved -FEE REQUIRED RMARVEL
Note: THIS IS A REINSPECTION Inspection Resulted at 7/11/2014 2:04:06 PM PROVIDE CITY STAMPED APPROVED REVISED PLANS ON SITE FOR INSPECTION.
HVAC ROUGH 07/11/2014 APPROVED RMARVEL
Note: THIS IS A REINSPECTION
HVAC FINAL 07/11/2014 APPROVED RMARVEL
Note: THIS IS A REINSPECTION
INSULATION 07/11/2014 APPROVED RMARVEL
ABOVE CEILING 07/10/2014 APPROVED - AS NOTED RMARVEL
Note: Inspection Resulted at 7/10/2014 2:11:01 PM NO DROP CEILING TO INSPECT. CHECKED LIGHTING PLACEMENT.
ELECTRIC 1ST ROUGH 07/08/2014 Disapproved -FEE REQUIRED RMARVEL
Note: Inspection Resulted at 7/8/2014 11:01:12 AM OPEN ALL BOXES FOR INSPECTION. NO POWER SHOULD BE ON AT THIS TIME. PROVIDE REVISIONS FOR CHANGES IN ELECTRICAL.
HVAC FINAL 07/08/2014 Disapproved -FEE REQUIRED RMARVEL
Note: Inspection Resulted at 7/8/2014 11:01:11 AM INSTALL DAMPER ON FRESH AIR INTAKE PER PLANS. LOCKING CAPS FBC.M 1101.10
HVAC ROUGH 07/08/2014 Disapproved - NO FEE RMARVEL
Note: Inspection Resulted at 7/8/2014 11:01:13 AM INSTALL DAMPER ON FRESH AIR INTAKE PER PLANS. LOCKING CAPS FBC.M 1101.10
ELECTRIC FINAL 07/08/2014 Disapproved - NO FEE RMARVEL
Note: Inspection Resulted at 7/8/2014 11:01:12 AM NOT READY FOR INSPECTION.
MONOLITHIC SLAB 06/13/2014 APPROVED RMARVEL
Note: THIS IS A REINSPECTION
MONOLITHIC SLAB 06/12/2014 Disapproved -FEE REQUIRED RMARVEL
Note: Inspection Resulted at 6/12/2014 9:46:35 AM HAIR PINS ARE NOT IN TYHE CORRECT LOCATION. MISSING X BRACE AT CORNER PER APPROVED PLANS.

Review History

Department Status Date In Date Out
DSD COMPLETE 09/24/2014 09/24/2014
PLLA COMPLETE 09/24/2014 09/24/2014
DSD HOLD 08/11/2014 08/13/2014
Note: 1. Upon inspection of the building addition, it appears that it does not match the approved elevations per Application number 2685. Note 3 on the Proposed Elevation shows Denz Glass Board with Synthetic Stucco Base to 3'-4" AFF (Color: Sand) to match existing stucco coated CMU on the existing building. The addition must be constructed per the approved architectural drawing.
PLLA COMPLETE 08/11/2014 08/15/2014
Note: Released By: WBUTLER 5 Hargrove Grade 8/15/14 1. Irrigation was not yet installed, so as-built cannot be submitted.
ELEC COMPLETE 07/14/2014 07/14/2014
BLD COMPLETE 07/10/2014 07/10/2014
ELEC HOLD 07/10/2014 07/10/2014
Note: 1. Provide a coordinated panel schedule. The circuit breaker sizes do not corespond with the equipment on subpanel B. J. Hindman 986-3784.
BLD COMPLETE 06/04/2014 06/04/2014
DSD COMPLETE 05/28/2014 05/28/2014
ZON COMPLETE 05/28/2014 05/28/2014
ELEC COMPLETE 04/17/2014 04/17/2014
UD1 COMPLETE 04/17/2014 04/17/2014
MECH COMPLETE 04/17/2014 04/17/2014
BLD COMPLETE 04/17/2014 04/17/2014
FI1 COMPLETE 04/17/2014 04/17/2014
ZON HOLD 04/17/2014 04/21/2014
Note: Provide an approved technical site plan development order.
ELEC HOLD 04/09/2014 04/09/2014
Note: Locate exit and emergency lights NEC 700.16
BLD HOLD 04/07/2014 04/08/2014
Note: 1. Provide engineered drawings for the building structure. 2010 FBC 107.2.1. 2. Provide Florida product approval for the doors, and roofing. 2010 FBC 107.2.1.
DSD HOLD 04/07/2014 04/08/2014
Note: Provide an approved technical site plan development order.
ENGIN1 COMPLETE 04/07/2014 04/08/2014
FI1 HOLD 04/07/2014 04/08/2014
Note: 1. Provide emergency lighting in new building.
MECH HOLD 04/07/2014 04/08/2014
Note: 1. Provide energy calculations per 2010 FBCEC 503.2. 2. Provide outdoor air requirement calculation per 2010 FBCM 403.2 including the outdoor air duct layout per 2010 FBC 107.3.5. F.Reodica - 386-986-4734
PLUM COMPLETE 04/07/2014 04/08/2014
Note: na
SW1 COMPLETE 04/07/2014 04/08/2014
UD1 HOLD 04/07/2014 04/07/2014
Note: Utility fees and agreements shall be complete prior to issuance of permit. Contact Utility department for information (386-986-2355)
ZON HOLD 04/07/2014 04/08/2014
Note: Provide an approved technical site plan development order.

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION FEE ¤40.00 08/01/2014
REINSPECTION FEE ¤40.00 08/01/2014
REVISION ¤40.00 08/01/2014
REVISION ¤40.00 08/01/2014
REINSPECTION FEE ¤40.00 07/15/2014
REINSPECTION FEE ¤40.00 07/15/2014
REINSPECTION FEE ¤40.00 07/15/2014
SITE PLAN 20 ¤20.00 05/30/2014
SURCHARGE FS 533.721 ¤5.77 05/30/2014
SURCHARGE - FS 468.631 ¤5.77 05/30/2014
ADMIN COMMERCIAL ¤60.00 05/30/2014
INSPECTION - COMMERCIAL ADD ¤609.00 05/30/2014
ELECTRIC FEE ¤112.20 05/30/2014
IMPACT FEE FIRE NONRESIDENTIAL ¤503.28 05/30/2014
FIRE PLANS REVIEW ¤25.00 05/30/2014
IMPACT FEE TRANSPORTATION ¤5,708.85 05/30/2014
MECHANICAL FEE ¤112.20 05/30/2014
PLAN CHECK FEE ¤100.05 05/30/2014
Fees Total Due: ¤0.00 Total Paid: ¤7,542.12